ABB 1SCA022744R2830 Switch-Disconnectors - IEC 60947-3

Part Number: 1SCA022744R2830
Manufacturer
ABB
Part number
1SCA022744R2830

Quick Summary

ABB 1SCA022744R2830 switch-disconnectors provide safe isolation for 3-pole main circuits in industrial control panels. This solution addresses the common challenge of achieving reliable, fast de-energization in high-energy systems, reducing downtime from mis-isolation or slow switching. It aligns with CE conformity and IEC 60947-3 standards, and offers front-operated control in a compact base-mounted body with a wide phase distance for safer wiring. With lug terminals and an included terminal bolt kit, it enables quicker, error-free assembly. For automation projects, this translates to faster commissioning, streamlined maintenance, and safer servicing, while meeting RoHS and CMRT expectations and supporting robust panel-level compliance.

Product Information

Extended Description

1SCA022744R2830 ABB: 3-pole, front operated, base mounted switch-diconnector, wide phase distance, handle and shaft are not included, terminal bolt kit included
End Of Life Disassembling Instructions
OT160-250 Disassembling Instruction
Environmental Information
PEI OT160-250
Environmental Product Declaration - EPD
PEP, EPD, OT160-250
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
REACH Declaration
Reach Declaration / AC Switches and Fusegear
RoHS Information
RoHs Declaration / AC Switches and Fusegear
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) Declaration / AC Switches and Fusegear
Data Sheet, Technical Information
Switches, Switch-disconnectors OT and OTM. Catalogue OT8GB 07-07
Instructions and Manuals
Switch Disconnectors OT200-250
Mechanical Drawings
OT200-250E12W, dwg-file | OT200-250E12W, dxf-file
Environmental Product Declaration - EPD
PEP, EPD, OT160-250
Degree of Protection
Front IP00
Environmental Information
PEI OT160-250
Pollution Degree
3
Minimum Order Quantity
1 piece
Customs Tariff Number
85365080
Country of Origin
Finland (FI)
Product Net Width
174.5 mm
Product Net Height
150 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.3 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
190 mm | 7.5 in
Package Level 1 Depth / Length
290 mm | 11.4 in
Package Level 1 Height
110 mm | 4.3 in
Package Level 1 Gross Weight
1.5 kg | 3.2 lb
Package Level 1 EAN
6417019241340
Conventional Free-air Thermal Current (Ith)
Θ = 40 °C 200 A
Conventional Thermal Current (Ithe)
Fully Enclosed 200 A
Degree of Protection
Front IP00
Distance Between Phases
Wide phase distance
Handle Type
Handle and shaft not included
Lock Type
No
Mechanical Durability
20000
Mounting Type
Base mounting
Number of Poles
3P
Operating Mode
Front operated
Pollution Degree
3
Position of Line Terminals
Top In - Bottom Out | Bottom In - Top Out
Power Loss
at Rated Operating Conditions per Pole 4.0 W
Rated Impulse Withstand Voltage (Uimp)
12 kV
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 1000 V
Rated Operational Current AC-21A (Ie)
(380 ... 415 V) 200 A | (500 V) 200 A | (690 V) 200 A
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 200 A | (500 V) 200 A | (690 V) 200 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 200 A | (500 V) 200 A | (690 V) 200 A
Rated Operational Power AC-23A (Pe)
(220 ... 240 V) 60 kW | (400 ... 415 V) 110 kW | (500 V) 132 kW | (690 V) 200 kW
Rated Operational Voltage
Main Circuit 1000 V
Rated Short-Circuit Making Capacity (Icm)
(690 V) 30 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 8 kA
Special Functions
Wide phase distance
Standards
IEC 60947-3
Switches Operating Mechanism
Mechanism Between the Poles | 12 (Between the Poles)
Terminal Type
Lug terminals
Tightening Torque
acc. IEC 60947-1 15 … 22 N·m
Tightening Torque
acc. IEC 60947-1 15 … 22 N·m
A2L Certificate – IEC
A2L Refrigerant Declaration of Conformity / OT160-800
Declaration of Conformity - CE
Declaration of Conformity / OT160EV_, OT200E_, OT250E_, OT200U_
DNV GL Certificate
DNV GL Certificate / OT100-160G_OT160EV-400
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
ETIM 9
EC000216 - Switch disconnector (low voltage)
eClass
V11.1 : 27371403
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Feature: 3-pole, front-operated, base-mounted design with wide phase distance → Business Impact: Safer, more compact panel layouts and easier wiring in control cabinets → Application: Motor feeders and main circuits in industrial automation. Feature: 200 A rated current across multiple voltages (380–415 V, 500 V, 690 V) → Business Impact: Handles high-power loads with a single device, reducing component count and wiring complexity → Application: Large conveyors and process lines. Feature: Mechanical durability rated at 20,000 cycles → Business Impact: Longer service life and lower maintenance cost in frequent switching environments → Application: Frequent isolation in production lines and safety interlock sequences. Feature: Power loss of 4.0 W per pole at rated conditions → Business Impact: Lower heat generation, enabling denser panel fits and improved thermal management → Application: Enclosed switchgear with tight space constraints. Feature: Terminal lug terminals with a terminal bolt kit included → Business Impact: Simplified installation, secure connections, and reduced installation time → Application: High-vibration environments and robust electrical unions. Feature: IP00 front protection and wide phase distance → Business Impact: Clear isolation performance in open-frame or protected enclosures, with enhanced creepage distances → Application: Front-access switchgear in controlled environments. Feature: Compliance with IEC 60947-3 and CE declarations + RoHS/CMRT documentation → Business Impact: Smooth regulatory approvals and traceability for supply chains → Application: Industrial control panels requiring formal certifications.

Get a Quick Quote for a ABB 1SCA022744R2830

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SCA022744R2830? Enquire Now

FAQs

The device uses base mounting with lug terminals. It ships with a terminal bolt kit and is designed for front operation. Ensure the enclosure supports IP00 protection and that wiring follows the 3P configuration with Top In - Bottom Out or Bottom In - Top Out terminal positioning for optimal phase spacing.
It supports 3P operation with 200 A rated currents across voltages from 380–415 V up to 690 V, insulation rated to 1000 V, and short-time withstands 8 kA for 1 s. Impulse withstand voltage is 12 kV, and it complies with IEC 60947-3 standards.
Yes. The product carries Declaration of Conformity for OT series and conforms to IEC 60947-3, with CE labeling. RoHS/CMRT documentation is available to support regulatory compliance and supply-chain traceability.
Net dimensions are 174.5 mm wide, 150 mm high, and 82.5 mm deep, with a net weight of 1.3 kg. These metrics help in enclosure planning and ensure adequate clearance for front operation and terminals.
Mechanical durability is rated at 20,000 cycles, supporting frequent switching. The unit is front-operated with no handle or shaft included; plan for compatible handle accessories. Power loss is 4.0 W per pole, affecting thermal design and cooling requirements in continuous operation.