ABB 1SCA022744R2910 Switch-Disconnectors - IEC 60947-3
Part Number: 1SCA022744R2910
Quick Summary
ABB 1SCA022744R2910 Switch-Disconnectors provide three-pole isolation for demanding industrial panels. They enable quick, safe disconnection in control cabinets where space is tight and service intervals are frequent. This design addresses common pain points such as unreliable shutdowns, difficult wiring, and limited access for maintenance by combining a front-operated mechanism with a base-mount chassis. The device aligns with IEC 60947-3 and carries a CE declaration of conformity, alongside BV and GL certifications that support global deployment. For buyers, the combination of robust mechanical durability and clear installation documentation translates to reduced downtime, lower lifecycle costs, and easier compliance across multi-site projects.
Product Information
Extended Description
1SCA022744R2910 ABB: 3-pole, front operated, base mounted switch-diconnector with black IP65 handle and shaft, wide phase distance, terminal bolt kit included
End Of Life Disassembling Instructions
OT160-250 Disassembling Instruction
Environmental Information
PEI OT160-250
Environmental Product Declaration - EPD
PEP, EPD, OT160-250
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
REACH Declaration
Reach Declaration / AC Switches and Fusegear
RoHS Information
RoHs Declaration / AC Switches and Fusegear
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
SCIP
2b43c2ae-44f4-4db7-89b3-fb89dc9fdf31 Finland (FI)
Simplified SCIP
2c95ac91-5a1b-47fd-b9de-f8c4bec41f5c Germany (DE) | 9774127b-77c1-4ced-8e97-6be1cf464dd3 Spain (ES) | be42ddf0-3d8a-4326-b20a-3a4185827b9c Norway (NO) | 3907eb31-2600-45d5-bbfe-a2a99272e0d2 Belgium (BE) | 0886faf6-32c9-48e3-baea-23de7eab7338 Sweden (SE) | b94773fa-4b5f-419b-9aa3-bace7876f257 Germany (DE) | 2204f280-07f3-4841-9671-c097dee606e4 Portugal (PT) | a8190387-c6d7-4fdf-9b32-f540375f1908 Greece (GR) | b3d903a3-ba2d-4927-8d8b-1d8af775ea29 Bulgaria (BG) | 2df08c65-e133-412f-be1c-10816e90ee83 France (FR) | d9198895-77e2-4c8e-947e-307e978c5c38 Germany (DE) | e36d682c-f5ad-47c1-a86c-d87adca4ccba Czech Republic (CZ) | 11fb165b-0dfe-4b9d-ba5f-7d869477695d Croatia (HR) | a94c2c88-189d-49c7-b48a-79a27b42bce3 Germany (DE) | 60289eaf-cca2-4a74-a4f2-0c8e12f9103e Poland (PL) | 4d25a178-a70c-4328-aafe-d8baea245a20 Germany (DE) | cf7fc570-21f1-452b-ad11-25139f5b0c01 Belgium (BE) | 12d631ef-4d26-4280-b9d5-6b7924703853 Italy (IT) | 49bbde59-ecd0-400c-913f-db4c5b6b6610 Estonia (EE) | a2b7cb5a-da2e-430a-a58e-756ffe43071c France (FR) | 60c2da41-fcb8-4cc4-b3de-a4f98df5ae64 Poland (PL) | cd9b799f-a643-4bd5-8a5f-2c5d08e64e01 Hungary (HU) | a9b1c2fa-d790-4cbb-93db-1dd2d9ece677 Hungary (HU) | 13a6e0ed-3362-4196-8728-0f90017a619c Netherlands (NL) | c8ae9d02-c800-4b39-91f6-52c0f79907e5 Denmark (DK) | b61f9d6b-b265-4905-8fca-454c07f5820b Poland (PL) | 4b5e0be2-d8ef-46d2-beb2-05d332ac7e20 Sweden (SE)
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) Declaration / AC Switches and Fusegear
Data Sheet, Technical Information
Switches, Switch-disconnectors OT and OTM. Catalogue OT8GB 07-07
Instructions and Manuals
Switch Disconnectors OT200-250
Mechanical Drawings
OT200-250E12W, dwg-file | OT200-250E12W, dxf-file
Environmental Product Declaration - EPD
PEP, EPD, OT160-250
Degree of Protection
Front IP00
Environmental Information
PEI OT160-250
Pollution Degree
3
Minimum Order Quantity
1 piece
Customs Tariff Number
85365080
Country of Origin
Finland (FI)
Product Net Width
174.5 mm
Product Net Height
170 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.5 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
190 mm | 7.5 in
Package Level 1 Depth / Length
290 mm | 11.4 in
Package Level 1 Height
110 mm | 4.3 in
Package Level 1 Gross Weight
1.7 kg | 3.7 lb
Package Level 1 EAN
6417019241357
Conventional Free-air Thermal Current (Ith)
Θ = 40 °C 200 A
Conventional Thermal Current (Ithe)
Fully Enclosed 200 A
Degree of Protection
Front IP00
Distance Between Phases
Wide phase distance
Handle Color
Black
Handle Type
Handle and shaft included
Lock Type
Yes
Mechanical Durability
20000
Mounting Type
Base mounting
Number of Poles
3P
Operating Mode
Front operated
Pollution Degree
3
Position of Line Terminals
Top In - Bottom Out | Bottom In - Top Out
Power Loss
at Rated Operating Conditions per Pole 4.0 W
Rated Conditional Short-Circuit Current (Inc)
(315 A fuse, 500 V) 100 kA | (355 A fuse, 690 V) 80 kA | (250 A fuse, 690 V) 100 kA
Rated Impulse Withstand Voltage (Uimp)
12 kV
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 1000 V
Rated Operational Current AC-21A (Ie)
(380 ... 415 V) 200 A | (500 V) 200 A | (690 V) 200 A
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 200 A | (500 V) 200 A | (690 V) 200 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 200 A | (500 V) 200 A | (690 V) 200 A
Rated Operational Power AC-23A (Pe)
(220 ... 240 V) 60 kW | (400 ... 415 V) 110 kW | (500 V) 132 kW | (690 V) 200 kW
Rated Operational Voltage
Main Circuit 1000 V
Rated Short-Circuit Making Capacity (Icm)
(690 V) 30 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 8 kA
Special Functions
Wide phase distance
Standards
IEC 60947-3
Switches Operating Mechanism
Mechanism Between the Poles | 12 (Between the Poles)
Terminal Type
Lug terminals
Terminal Width
20 mm
Tightening Torque
acc. IEC 60947-1 15 … 22 N·m
Tightening Torque
acc. IEC 60947-1 15 … 22 N·m
A2L Certificate – IEC
A2L Refrigerant Declaration of Conformity / OT160-800
ATEX Certificate
No certification needed
BV Certificate
1SCC301103D0201
Declaration of Conformity - CE
Declaration of Conformity / OT160EV_, OT200E_, OT250E_, OT200U_
DNV GL Certificate
DNV GL Certificate / OT100-160G_OT160EV-400
GL Certificate
1SCC301139D0201
LR Certificate
1SCC301144D0201
UL Certificate
No certification needed
VDE Certificate
No certification needed
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
ETIM 9
EC000216 - Switch disconnector (low voltage)
UNSPSC
39122233
IDEA Granular Category Code (IGCC)
5290 >> Disconnect switch
eClass
V11.1 : 27371403
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
E-Number (Finland)
3661322
E-Number (Norway)
4337882
Feature: The 3-pole, front-operated switch-disconnector with base mounting and a lockable mechanism provides fast, safe isolation. Business Impact: Reduces shutdown time, enhances operator safety, and enables effective lockout-tagout (LOTO) across high-availability lines. Application: Ideal for motor control centers and panel feeders in manufacturing environments. Feature: 200 A conventional free-air thermal current (Ith) rating and robust short-circuit withstand capability. Business Impact: Supports peak loads without nuisance tripping, increasing system reliability. Application: Suitable for distribution boards and feeder circuits in industrial plants. Feature: Ui of 1000 V and Uimp of 12 kV, plus wide phase distance and 3P configuration. Business Impact: Enables safe operation in medium-voltage applications with versatile bus-bar layouts. Application: Electrical switchgear installations and protection assemblies. Feature: Lug terminals with 20 mm terminal width and 15–22 N·m tightening torque. Business Impact: Simplifies wiring, improves connection reliability, and speeds commissioning. Application: Retrofit and new installations in compact enclosures. Feature: Mechanical durability rated at 20,000 cycles and lockable handle. Business Impact: Lower maintenance costs and longer service life, reducing total cost of ownership. Application: Repeated operation in demanding control panels and safety-critical applications. Feature: Comprehensive environmental and compliance data including CMRT, REACH, RoHS, SCIP across multiple EU states, plus CE Declaration and BV/GL certificates. Business Impact: Streamlines supplier audits and regulatory submissions, enabling faster procurement for global operations. Application: Global manufacturing sites and multi-country projects.
Get a Quick Quote for a ABB 1SCA022744R2910
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SCA022744R2910?
Enquire Now
FAQs
The ABB OT200E12WP is a 3-pole, base-mounted switch-disconnector with lug terminals and a 20 mm terminal width, designed for straightforward retrofit in standard control panels. Its top-in, bottom-out or bottom-in, top-out terminal arrangement offers flexible wiring paths, while the lockable front-operated mechanism supports safe LO/TO procedures during maintenance.
Key specs include a conventional free-air current Ith of 200 A, Ui of 1000 V, Uimp of 12 kV, and a rated short-circuit current Icm up to 30 kA (690 V). Power loss is approximately 4.0 W per pole, with 3P configuration and front operation. These figures support reliable clearing of faults in mid-range power distributions.
Yes. With 3P front-operated operation, base mounting, and a robust mechanical design, it suits motor control centers and distribution panels. The device supports wide phase distance and lockable operation, improving safety in frequent switching scenarios. Its compliance with IEC 60947-3 enhances suitability for industrial panels across varied environments.
The product features a CE Declaration of Conformity, BV and GL certificates, and supporting environmental declarations (CMRT, REACH, RoHS) with SCIP references across multiple EU countries. These documents facilitate audits, approvals, and multi-site deployments, reducing procurement friction and ensuring regulatory alignment for global projects.
The switch-disconnector offers about 20,000 mechanical operating cycles and a lockable mechanism for safer maintenance, reducing downtime and compliance risk. Coupled with low per-pole power loss (4.0 W) and reliable 200 A ratings, this leads to lower energy costs and meaningful lifecycle savings over frequent switching cycles in production environments.