ABB 1SCA022860R0200 Switch-Disconnectors - IEC 60947-3
Part Number: 1SCA022860R0200
Quick Summary
ABB 1SCA022860R0200 Switch-Disconnectors enable safe isolation in three-pole mains circuits for industrial control panels. In demanding environments, downtime and maintenance costs erode uptime and extend project timelines. This device complies with IEC 60947-3 and carries a CE Declaration of Conformity, supported by a DNV GL certificate, and Front IP00 protection, underpinning safety and traceability. With base mounting, side-operated actuation, and a 200 A per-pole rating, it speeds installation while preserving fault tolerance. The combination of robust compliance, straightforward lug-terminal integration, and ABB EcoSolutions documentation helps procurement teams mitigate risk and streamline changeouts in automation projects.
Product Information
Extended Description
1SCA022860R0200 ABB: 3-pole, side operated, base mounted switch-diconnector, handle and shaft are not included, terminal bolt kit included
End Of Life Disassembling Instructions
OT160-250 Disassembling Instruction
Environmental Information
PEI OT160-250
Environmental Product Declaration - EPD
PEP, EPD, OT160-250
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
REACH Declaration
Reach Declaration / AC Switches and Fusegear
RoHS Information
RoHs Declaration / AC Switches and Fusegear
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) Declaration / AC Switches and Fusegear
Data Sheet, Technical Information
Switches, Switch-disconnectors OT and OTM. Catalogue OT8GB 07-07
Instructions and Manuals
1SCC301068M0204
Mechanical Drawings
OT200-250ES03, dwg-file | OT200-250ES03, dxf-file | OT200ES03.igs
Environmental Product Declaration - EPD
PEP, EPD, OT160-250
Degree of Protection
Front IP00
Environmental Information
PEI OT160-250
Pollution Degree
3
Minimum Order Quantity
1 piece
Customs Tariff Number
85365080
Country of Origin
Finland (FI)
Product Net Width
181.5 mm
Product Net Height
150 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.5 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
170 mm | 6.7 in
Package Level 1 Depth / Length
250 mm | 9.8 in
Package Level 1 Height
155 mm | 6.1 in
Package Level 1 Gross Weight
1.7 kg | 3.7 lb
Package Level 1 EAN
6417019308722
Conventional Free-air Thermal Current (Ith)
Θ = 40 °C 200 A
Conventional Thermal Current (Ithe)
Fully Enclosed 200 A
Degree of Protection
Front IP00
Distance Between Phases
Standard
Handle Type
Handle and shaft not included
Lock Type
No
Mechanical Durability
20000
Mounting Type
Base mounting
Number of Poles
3P
Operating Mode
Side operated
Pollution Degree
3
Position of Line Terminals
Top In - Bottom Out | Bottom In - Top Out
Power Loss
at Rated Operating Conditions per Pole 4.0 W
Rated Conditional Short-Circuit Current (Inc)
(315 A fuse, 500 V) 100 kA | (355 A fuse, 690 V) 80 kA | (250 A fuse, 690 V) 100 kA
Rated Impulse Withstand Voltage (Uimp)
12 kV
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 1000 V
Rated Operational Current AC-21A (Ie)
(380 ... 415 V) 200 A | (500 V) 200 A | (690 V) 200 A
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 200 A | (500 V) 200 A | (690 V) 200 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 200 A | (500 V) 200 A | (690 V) 200 A
Rated Operational Power AC-23A (Pe)
(220 ... 240 V) 60 kW | (400 ... 415 V) 110 kW | (500 V) 132 kW | (690 V) 200 kW
Rated Operational Voltage
Main Circuit 1000 V
Rated Short-Circuit Making Capacity (Icm)
(690 V) 30 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 8 kA
Special Functions
No
Standards
IEC 60947-3
Switches Operating Mechanism
Mechanism at the End of the Switch | 03 (Left Side)
Terminal Type
Lug terminals
Tightening Torque
acc. IEC 60947-1 15 … 22 N·m
Tightening Torque
acc. IEC 60947-1 15 … 22 N·m
A2L Certificate – IEC
A2L Refrigerant Declaration of Conformity / OT160-800
ATEX Certificate
No certification needed
Declaration of Conformity - CE
Declaration of Conformity / OT160EV_, OT200E_, OT250E_, OT200U_
DNV GL Certificate
DNV GL Certificate / OT100-160G_OT160EV-400
UL Certificate
No certification needed
VDE Certificate
No certification needed
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
ETIM 9
EC000216 - Switch disconnector (low voltage)
UNSPSC
39122233
IDEA Granular Category Code (IGCC)
5290 >> Disconnect switch
eClass
V11.1 : 27371403
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
E-Number (Finland)
3661701
Feature: 3-pole, side-operated design enables straightforward isolation in 3-phase mains. Benefits: reduces installation time and minimizes wiring complexity, improving first-run panel assembly efficiency for control cabinets and motor starters. Application: switchgear assemblies and main control panels in manufacturing environments. Feature: 200 A rated current per pole with 12 kV impulse withstand and 1000 V insulation. Benefits: supports high-current circuits while maintaining safe insulation and surge protection, reducing overheating risk and enabling reliable control of motors and feeders. Application: heavy-duty process automation and energy-intensive equipment. Feature: Base mounting and lug-terminal terminals with a tightening torque of 15–22 N·m. Benefits: simplifies panel mounting and maintenance, enables robust, vibration-tolerant connections, and eases retrofit projects. Application: OEM panel builds and retrofit upgrades in electrical rooms. Feature: Power loss rated at 4.0 W per pole under rated conditions. Benefits: lower heat generation in enclosures, improving reliability and reducing cooling requirements. Application: energy-conscious panel designs and compact switchgear. Feature: IEC 60947-3 compliance and CE declarations, plus RoHS and CMRT references. Benefits: ensures regulatory alignment, environmental responsibility, and supply-chain traceability. Application: certified equipment for regulated industries and public-sector installations. Feature: 3P base-mounted arrangement with 3P terminal configuration and horizontal/vertical installation flexibility. Benefits: accelerates field installation, simplifies wiring layouts, and supports compact panel designs. Application: switchboards, motor control centers, and automation cabinets.
Get a Quick Quote for a ABB 1SCA022860R0200
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SCA022860R0200?
Enquire Now
FAQs
The device features base mounting suitable for panel installations and 3P lug-terminals, enabling straightforward wiring and secure, vibration-resistant connections. This reduces assembly time in control cabinets and simplifies retrofits in existing switchgear. Engineers often choose base-mounted switch-disconnectors to streamline installation in compact panels without sacrificing accessibility for maintenance.
It provides 200 A per pole with a rated insulation voltage of 1000 V, a rated impulse withstand voltage of 12 kV, and a conventional free-air thermal current Ith of 200 A. Short-circuit capability is rated at up to 100 kA depending on fuse configuration and voltage, making it suitable for demanding motor and feeder isolation in industrial plants.
Yes. It is designed for switchgear and control panels, offering 3P isolation, side-operated actuation, and reliable 200 A per-pole performance. Compliance with IEC 60947-3 and CE DoC supports regulatory requirements, while RoHS and CMRT documentation aid in environmental and supply-chain considerations.
Key certifications include IEC 60947-3 compliance, CE Declaration of Conformity, and a DNV GL certificate. IP00 protection indicates low external protection in open environments. These align with common safety, environmental, and regulatory expectations for industrial switchgear and help reduce qualification time for regulated projects.
With 20000 mechanical durability operations and 4.0 W power loss per pole, the device promises long service life with minimal maintenance intervals and cooler enclosure temperatures. The combination of easy lug-terminals, clear torque specs, and reliable isolation translates to lower lifecycle costs and faster changeouts in automated lines.