ABB 1SCA103718R1001 Switch-Disconnectors - IEC 60947-3
Part Number: 1SCA103718R1001
Quick Summary
The ABB 1SCA103718R1001 switch-disconnector provides frontline isolation for 6‑pole industrial circuits. Engineers often struggle with space constraints and maintenance access; this unit's front operation and base mounting simplify servicing. It aligns with IEC 60947-3 and CE declarations, and carries DNV GL certification for critical applications. This combination supports ABB EcoSolutions workflows, ensures robust isolation at 1000 V and 200 A, and streamlines panel integration with lug terminals and base mounting. Designed for serviceability in confined switchgear bays, it supports quick inspection and secure reseating of connections. With robust lug-terminals and a compact 6P footprint, it minimizes panel depth while maintaining safe isolation under demanding ambient conditions.
Product Information
Extended Description
1SCA103718R1001 ABB: 6-pole, front operated, base mounted switch-diconnector, handle and shaft are not included, terminal bolt kit included
End Of Life Disassembling Instructions
OT160-250 Disassembling Instruction
Environmental Information
PEI OT160-250
Environmental Product Declaration - EPD
PEP, EPD, OT160-250
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
REACH Declaration
Reach Declaration / AC Switches and Fusegear
RoHS Information
RoHs Declaration / AC Switches and Fusegear
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) Declaration / AC Switches and Fusegear
Data Sheet, Technical Information
Switches, Switch-disconnectors OT and OTM. Catalogue OT8GB 07-07
Instructions and Manuals
Switch Disconnectors OT200-250
Mechanical Drawings
OT200E33.igs
Environmental Product Declaration - EPD
PEP, EPD, OT160-250
Degree of Protection
Front IP00
Environmental Information
PEI OT160-250
Pollution Degree
3
Minimum Order Quantity
1 piece
Customs Tariff Number
85365080
Country of Origin
Finland (FI)
Product Net Width
255.5 mm
Product Net Height
150 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
2.1 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
260 mm | 10.2 in
Package Level 1 Depth / Length
290 mm | 11.4 in
Package Level 1 Height
190 mm | 7.5 in
Package Level 1 Gross Weight
2.7 kg | 6 lb
Package Level 1 EAN
6417019380940
Conventional Free-air Thermal Current (Ith)
Θ = 40 °C 200 A
Conventional Thermal Current (Ithe)
Fully Enclosed 200 A
Degree of Protection
Front IP00
Distance Between Phases
Standard
Handle Type
Handle and shaft not included
Lock Type
No
Mechanical Durability
20000
Mounting Type
Base mounting
Number of Poles
6P
Operating Mode
Front operated
Pollution Degree
3
Position of Line Terminals
Top In - Bottom Out | Bottom In - Top Out
Power Loss
at Rated Operating Conditions per Pole 4.0 W
Rated Impulse Withstand Voltage (Uimp)
12 kV
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 1000 V
Rated Operational Current AC-21A (Ie)
(380 ... 415 V) 200 A | (500 V) 200 A | (690 V) 200 A
Rated Operational Current DC-21B (Ie)
(1000 V) 200 A
Rated Operational Voltage
Main Circuit 1000 V
Rated Short-Circuit Making Capacity (Icm)
(690 V) 30 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 8 kA
Special Functions
No
Standards
IEC 60947-3
Switches Operating Mechanism
Mechanism Between the Poles | 33 (Between the Poles)
Terminal Type
Lug terminals
Tightening Torque
acc. IEC 60947-1 15 … 22 N·m
Tightening Torque
acc. IEC 60947-1 15 … 22 N·m
A2L Certificate – IEC
A2L Refrigerant Declaration of Conformity / OT160-800
Declaration of Conformity - CE
1SCC301162D2702
DNV GL Certificate
DNV GL Certificate / OT100-160G_OT160EV-400
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
ETIM 9
EC000216 - Switch disconnector (low voltage)
UNSPSC
39122233
IDEA Granular Category Code (IGCC)
5290 >> Disconnect switch
eClass
V11.1 : 27371403
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Feature → Business Impact → Application: 6-pole, front-operated design delivers clear mechanical isolation for multi-pole circuits in control panels, enabling safe de-energization during maintenance and fault clearance. This improves uptime and operator safety in industrial environments. Feature → Business Impact → Application: Base mounting simplifies installation and reduces mounting time, lowering lifecycle costs for panel builders and distributors while ensuring alignment with standard enclosure layouts. Feature → Business Impact → Application: Lug terminals provide secure, durable connections that resist vibration and thermal cycling, delivering reliable long-term performance in demanding machinery and process systems. Feature → Business Impact → Application: High current and fault ratings—Ith up to 200 A, I_e up to 200 A (AC-21A), Ui 1000 V, Uimp 12 kV, I_cm 30 kA—translate to fewer components and higher fault tolerance in motor drives and power distribution. Feature → Business Impact → Application: Mechanical durability of 20,000 cycles supports extended service life under frequent operation, reducing maintenance intervals and total cost of ownership. Feature → Business Impact → Application: Compliance and environmental declarations (RoHS, CMRT, EPD) and CE/DNV GL certifications mitigate regulatory risk and simplify procurement for regulated facilities, automotive and food/chemical processing plants. Feature → Business Impact → Application: Compact footprint and 2.1 kg net weight ease integration into mid- to large-scale control panels, improving layout efficiency and field installation speed.
Get a Quick Quote for a ABB 1SCA103718R1001
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SCA103718R1001?
Enquire Now
FAQs
This 6-pole switch-disconnector is designed for base mounting and uses lug terminals, aligning with standard control panel cutouts. It supports straightforward wiring, a recommended tightening torque of 15–22 N·m, and minimizes panel depth requirements, making retrofit and new-build projects more efficient.
Rated insulation voltage is 1000 V, with a conventional free-air thermal current Ith of 200 A and a conventional thermal current Ithe of 200 A for fully enclosed operation. It provides an impulse withstand voltage of 12 kV and a rated short-circuit making capacity Icm of 30 kA. Operational currents AC-21A are 200 A across 380–415 V, 500 V, and 690 V.
Yes, it carries a CE Declaration of Conformity and complies with IEC 60947-3. Additional certifications include DNV GL and related environmental declarations (CMRT and EPD) to support regulatory compliance in sensitive industries.
Product net width is 255.5 mm, height 150 mm, and depth 82.5 mm, with a net weight of 2.1 kg (packaged as 2.7 kg). These dimensions support predictable enclosure layouts and consistent mounting requirements in mid- to large-scale applications.
Mechanical durability is rated at 20,000 cycles, with a tightening torque range of 15–22 N·m for terminals. Handle and shaft are not included, so plan for compatible operator mechanisms. Regular inspection of lug connections and verification of torque help maintain reliability in high-duty environments.