ABB 1SCA108494R1001 Change-Over Switch - CE

Part Number: 1SCA108494R1001
Manufacturer
ABB
Part number
1SCA108494R1001

Quick Summary

ABB 1SCA108494R1001 Change-Over Switch provides reliable 4-pole switching for industrial power distribution in control cabinets. It minimizes transfer gaps and contact wear, reducing downtime during power transfers. Certified with CE declarations, RoHS compliance, and Reach information, it aligns with critical industrial standards. Designed for ABB EcoSolutions compatibility and straightforward base mounting, it supports efficient procurement and reliable field service. Rated at 160 A and suitable for 380–415 V, 500 V, and 690 V systems, it accommodates scalable plant architectures. With clear installation instructions and a robust, protection-focused build, operators gain predictable performance, safer operation, and lower total cost of ownership over its life cycle.

Product Information

Extended Description

1SCA108494R1001 ABB: 160, 4 pole manual change-over switch with phase barriers operating on closed transition principle. i.e. make-before-break operation without OFF-position. Between positions I and II, there is a position I+II where both switches are closed simultaneously. The overlapping time when both contacts are closed is minimum 20 ms. Operating angle of the handle is 90°. Including a black plastic IP65 I - I+II - II pistol type handle (see the table below), shaft and bolt set for the cable connection. Handle not padlockable and no door interlocking.
End Of Life Disassembling Instructions
OT160-250_C Disassembly Instructions
Environmental Information
1SCC303050D0201
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
REACH Declaration
Reach Declaration / AC Switches and Fusegear
RoHS Information
RoHs Declaration / AC Switches and Fusegear
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Data Sheet, Technical Information
Transfer, change-over and bypass switches. Catalogue OTC1GB 23-04
Instructions and Manuals
Manual change-over and transfer switches OT-C
Degree of Protection
Front IP20
Environmental Information
1SCC303050D0201
Pollution Degree
3
Minimum Order Quantity
1 piece
Customs Tariff Number
85365080
Country of Origin
Finland (FI)
Product Net Width
237 mm | 9.33 in
Product Net Height
170 mm | 6.69 in
Product Net Depth / Length
160 mm | 6.3 in
Product Net Weight
3.8 kg | 8.38 lb
Package Level 1 Units
box 1 box
Package Level 1 Width
186 mm | 7.32 in
Package Level 1 Depth / Length
310 mm | 12.2 in
Package Level 1 Height
185 mm | 7.28 in
Package Level 1 Gross Weight
4.1 kg | 9.04 lb
Package Level 1 EAN
6417019399461
Conventional Free-air Thermal Current (Ith)
Θ = 40 °C 160 A
Conventional Thermal Current (Ithe)
Fully Enclosed 160 A
Degree of Protection
Front IP20
Distance Between Phases
Wide phase distance
Fourth Pole Position
Right Side
Fourth Pole Type
Switched - Simultaneous Function
Handle Color
Black
Handle Type
Handle and shaft included
Mounting Type
Base mounting
Number of Poles
4P
Operating Mode
Front operated
Pollution Degree
3
Position of Line Terminals
Top In - Bottom Out, Bottom In - Top Out
Power Loss
at Rated Operating Conditions per Pole 2.4 W
Rated Impulse Withstand Voltage (Uimp)
12 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Current AC-21A (Ie)
(380 ... 415 V) 160 A | (500 V) 160 A | (690 V) 160 A
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 160 A | (500 V) 160 A | (690 V) 160 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 160 A | (500 V) 160 A | (690 V) 160 A
Rated Operational Current AC-31B (Ie)
(380 ... 415 V) 160 A
Rated Operational Current AC-33B (Ie)
(380 ... 415 V) 160 A
Rated Operational Power AC-23A (Pe)
(380 ... 415 V) 90 kW | (500 V) 110 kW | (690 V) 160 kW
Rated Operational Voltage
Main Circuit 1000 V
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 8 kiloampere rms
Switches Operating Mechanism
Mechanism at the End of the Switch | 04 (Left Side)
Terminal Type
Screw Terminals
Tightening Torque
acc. IEC 60947-1 15 ... 22 N·m
Transition Type
Closed
Ampere Rating
160 A
Tightening Torque
acc. IEC 60947-1 15 ... 22 N·m
Declaration of Conformity - CE
Declaration of Conformity / OT160-250_CL
DNV Certificate
DNV Certificate / OT16-2500_C
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
ETIM 9
EC000216 - Switch disconnector (low voltage)
eClass
V11.1 : 27371403
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
E-Number (Finland)
3641605
The 4-pole manual change-over switch with closed transition (make-before-break) ensures seamless source transfer by overlapping contacts between positions I and II. Business Impact: minimizes interruption and arc risk, improving equipment uptime and operator safety. Application: essential for critical feeders in control cabinets and machine rooms where uninterrupted supply is required. The unit delivers Ith of 160 A and Ie ratings across 380–415 V, 500 V, and 690 V, with a power loss of 2.4 W per pole and a rated impulse withstand voltage of 12 kV. Business Impact: supports reliable, continuous operation under load while keeping heat and electrical stress within design limits. Application: main feeders and process lines in manufacturing and infrastructure projects. The device features front IP20 protection and Pollution Degree 3, enabling safe indoor panel installation and predictable performance in standard plant environments. Business Impact: simplifies compliance with panel-building standards and reduces contamination-related faults. Application: electrical cabinets in industrial facilities. The switch supports base mounting with screw terminals and a 90° operating angle, with the handle and shaft included for quick actuation. Business Impact: speeds installation, minimizes field labor, and improves reliability during routine maintenance and retrofits. Application: retrofit projects and new builds requiring straightforward integration. The package also includes robust regulatory compliance components, such as RoHS and Reach, plus CMRT, ETIM classifications, and DNV certificate references. Business Impact: streamlines audits, enables global deployment, and reduces compliance risk. Application: multi-site manufacturing, process automation, and energy sector installations.

Get a Quick Quote for a ABB 1SCA108494R1001

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SCA108494R1001? Enquire Now

FAQs

Yes. The ABB 1SCA108494R1001 is designed for base mounting in traditional switchgear cabinets and uses secure screw terminals. It fits standard 4P configurations and aligns with ABB EcoSolutions installation practices, enabling straightforward retrofits or new-build panel assemblies without specialized adapters.
Key specs include Ith of 160 A, Ie rated at 160 A across 380–415 V, 500 V, and 690 V, Ui 1000 V, Uimp 12 kV, and a transition type of Closed. It also features a 2.4 W per pole power loss and front IP20 protection. These values support reliable, high‑current transfer in medium‑to‑large panel applications.
Yes. With a four-pole design, 160 A rating, closed-transition operation, and IP20 front protection, the unit is well-suited for indoor control panels and distribution boards in demanding industries. Its robust construction and documented RoHS/Reach compliance support clean-room and regulated environments while maintaining dependable transfer switching.
Key certifications include CE Declaration of Conformity for OT160-250_CL, RoHS information, Reach compliance, and CMRT. The product also lists a DNV certificate reference, ETIM classification, and WEEE categorization. These documents streamline regulatory reviews and supplier qualification across regional markets.
The make-before-break, closed-transition design minimizes downtime during source changes, reducing production interruptions. With 160 A ratings, low per-pole power loss, and a compact base-mounted footprint, installation and maintenance costs are reduced. In addition, CE/RoHS/CMRT compliance simplifies audits, supporting longer service life and lower total cost of ownership in multi-site facilities.