ABB 1SCA117334R1001 Switch-Disconnectors - UL 98 / CSA C22.2 NO.4

Part Number: 1SCA117334R1001
Manufacturer
ABB
Part number
1SCA117334R1001

Quick Summary

ABB 1SCA117334R1001 Switch-Disconnectors deliver four-pole, front-operated isolation for high-current power distribution in industrial panels. This design enables safe maintenance by providing reliable, visible disconnects even in tight spaces. Engineers often face installation challenges in large switchgear where space, mounting simplicity, and regulatory compliance must align with demanding standards. The OT2000U22 variant supports non-fusible operation with a robust base-mount configuration and lug terminals; handle and shaft are not included, which simplifies retrofit into existing frames. Compliance highlights include UL 98 / CSA C22.2 NO.4 certification, RoHS declarations, and REACH alignment. By combining ABB EcoSolutions with proven performance, you gain predictable uptime and easier maintenance planning across facilities.

Product Information

Extended Description

1SCA117334R1001 ABB: 4-pole, front operated, base mounted non-fusible diconnect switch, handle and shaft are not included, terminal bolt kit included
End Of Life Disassembling Instructions
OT1000-1600 Disassembly Instructions
Environmental Product Declaration - EPD
PEP, EPD, OT1000-2000E_, OT800-2000U_
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
REACH Declaration
Reach Declaration / AC Switches and Fusegear
RoHS Information
RoHs Declaration / AC Switches and Fusegear
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) Declaration / AC Switches and Fusegear
Data Sheet, Technical Information
Switches, Switch-disconnectors OT and OTM. Catalogue OT8GB 07-07
Instructions and Manuals
Switch Disconnectors OT1600U_, OT2000U_
Mechanical Drawings
OT1600-2000U22.stp
Environmental Product Declaration - EPD
PEP, EPD, OT1000-2000E_, OT800-2000U_
Degree of Protection
Front IP00
Pollution Degree
3
Minimum Order Quantity
1 piece
Customs Tariff Number
85365080
Country of Origin
Finland (FI)
Product Net Width
615 mm
Product Net Height
546 mm
Product Net Depth / Length
415 mm
Product Net Weight
68.9 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
420 mm
Package Level 1 Depth / Length
650 mm
Package Level 1 Height
620 mm
Package Level 1 Gross Weight
72.1 kg
Package Level 1 EAN
6417019493435
Degree of Protection
Front IP00
Distance Between Phases
Standard
Fourth Pole Position
Right Side
Fourth Pole Type
Switched - Simultaneous Function
Handle Type
Handle and shaft not included
Lock Type
No
Mechanical Durability
2500
Mounting Type
Base mounting
Number of Poles
4P
Operating Mode
Front operated
Pollution Degree
3
Position of Line Terminals
Top In - Bottom Out | Bottom In - Top Out
Power Loss
at Rated Operating Conditions per Pole 96 W
Rated Impulse Withstand Voltage (Uimp)
12 kV
Rated Operational Voltage
Main Circuit 1000 V
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 50 kA
Special Functions
No
Standards
UL 98 / CSA C22.2 NO.4
Switches Operating Mechanism
Mechanism Between the Poles | 22 (Between the Poles)
Terminal Type
Lug terminals
Tightening Torque
acc. IEC 60947-1 56 N·m
Maximum Operating Voltage UL/CSA
600 V
Ampere Rating
2000 A
Tightening Torque
acc. IEC 60947-1 56 N·m
Tightening Torque UL/CSA
500 in·lb
ATEX Certificate
No certification needed
cUL Certificate
cULus certificate OT1600-2000
UL Certificate
cULus certificate OT1600-2000
VDE Certificate
No certification needed
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
ETIM 9
EC000216 - Switch disconnector (low voltage)
UNSPSC
39122233
IDEA Granular Category Code (IGCC)
5293 >> Switch disconnector
eClass
V11.1 : 27371403
WEEE Category
4. Large Equipment (Any External Dimension More Than 50 cm)
Feature: 4-pole, front-operated, base-mounted design simplifies safe isolation in large control cabinets. Benefit: improves maintenance safety and reduces front clearance requirements, enabling more compact layouts in data centers and manufacturing lines. Application: ideal for base-mounted disconnects in panel doors where space is at a premium and clear visibility of the switch status is critical. Feature: 2000 A ampere rating supports main feeder switching without paralleling, reducing point-of-use components and installation complexity. Benefit: lowers total system cost and upfront wiring effort while enhancing reliability for high-load applications. Application: main feeders in machine shops and process industries. Feature: Rated operational voltage of 1000 V and 12 kV impulse withstand voltage provide robust protection for medium- and high-voltage control circuits. Benefit: ensures regulatory compliance and safe operation across diverse industrial environments. Application: switchgear panels and distributed power systems. Feature: Lug terminals and mechanical durability of 2500 cycles offer rugged, repeatable performance. Benefit: easier wiring, longer service life, and predictable maintenance windows. Application: frequent make/break cycles in production lines. Feature: RoHS/REACH declarations and cUL/UL certifications underpin regulatory compliance and global market access. Benefit: simplifies procurement and reduces risk of non-compliant supply chains. Application: OEM assemblies needing traceable environmental and safety declarations. Feature: Front IP00 protection and specified mounting/terminal geometry enable straightforward integration into standard frames. Benefit: minimizes retrofit effort and accelerates installation schedules. Application: retrofits and new builds in standard 4P switchgear assemblies with lug termination.

Get a Quick Quote for a ABB 1SCA117334R1001

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SCA117334R1001? Enquire Now

FAQs

Yes. This ABB switch-disconnector is a 4P, front-operated unit designed for base mounting with lug terminals. It aligns with common distribution panel footprints and offers 615 mm width, 546 mm height, and 415 mm depth in its net form, making it compatible with many standard frames and busbar layouts while preserving secure wire connections.
Key specs include a 2000 A ampere rating, 1000 V rated operational voltage, 12 kV rated impulse withstand voltage, and 96 W power loss per pole under rated conditions. It supports 4P operation with front actuation and a 4-pole configuration, suitable for high-current isolation in industrial panels.
Absolutely. The device carries UL 98 / CSA C22.2 NO.4 compatibility through its OT range and cULus certification for OT1600-2000 variants. It also aligns with RoHS and REACH requirements, helping you meet regulatory expectations in North American and international markets.
ABB provides End Of Life Disassembly Instructions for related OT ranges, including OT1000-1600. This guidance supports safe removal, recycling, and disposal in line with environmental policies. Plan for lifecycle management early, ensuring spare parts availability and compliant disassembly procedures in your facility.
While upfront costs depend on configuration, the 1SCA117334R1001 offers durable mechanical performance (2500 cycles), high current capacity, and robust regulatory compliance, which reduce downtime and maintenance frequency. The result is lower maintenance labor costs, fewer mid-life replacements, and faster MTTR, delivering favorable ROI in automation and power distribution projects.