ABB 1SCA120506R1001 Switch-Disconnectors - IEC 60947-3

Part Number: 1SCA120506R1001
Manufacturer
ABB
Part number
1SCA120506R1001

Quick Summary

ABB 1SCA120506R1001 switch-disconnector provides reliable circuit isolation for medium voltage switchgear and control panels. This design addresses the common challenge of safe and verifiable disconnection, reducing maintenance risk and downtime. Key certifications for confidence include IEC 60947-3 compliance, CE declaration, and Front IP00 protection, supporting safe operation in controlled industrial environments. By pairing robust electrical ratings with straightforward installation, this device delivers tangible business value through improved uptime, easier compliance reporting, and lower lifecycle costs for panel builders and end users alike.

Product Information

Extended Description

1SCA120506R1001 ABB: OT160EV02 SWITCH-DISCONNECTOR
End Of Life Disassembling Instructions
OT160-250 Disassembling Instruction
Environmental Information
PEI OT160-250
Environmental Product Declaration - EPD
PEP, EPD, OT160-250
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
REACH Declaration
Reach Declaration / AC Switches and Fusegear
RoHS Information
RoHs Declaration / AC Switches and Fusegear
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) Declaration / AC Switches and Fusegear
Data Sheet, Technical Information
No documentation needed
Instructions and Manuals
Switch Disconnectors OT200-250
Mechanical Drawings
OT200-250E02, dwg-file | OT200-250E02, dxf-file
Environmental Product Declaration - EPD
PEP, EPD, OT160-250
Degree of Protection
Front IP00
Environmental Information
PEI OT160-250
Pollution Degree
3
Minimum Order Quantity
1 piece
Customs Tariff Number
85365080
Country of Origin
Finland (FI)
Product Net Width
150 mm
Product Net Height
110.5 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
0.9 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
170 mm | 6.7 in
Package Level 1 Depth / Length
190 mm | 7.5 in
Package Level 1 Height
145 mm | 5.7 in
Package Level 1 Gross Weight
1.1 kg | 2.3 lb
Package Level 1 EAN
6417019518466
Conventional Thermal Current (Ithe)
Fully Enclosed 160 A
Degree of Protection
Front IP00
Handle Type
Handle and shaft not included
Lock Type
No
Mechanical Durability
20000
Number of Poles
2P
Pollution Degree
3
Power Loss
at Rated Operating Conditions per Pole 3.2 W
Rated Impulse Withstand Voltage (Uimp)
12 kV
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 1000 V
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 200 A | (500 V) 200 A | (690 V) 160 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 160 A | (500 V) 160 A | (690 V) 160 A
Rated Operational Power AC-23A (Pe)
(220 ... 240 V) 48 kW | (400 ... 415 V) 88 kW | (500 V) 112 kW | (690 V) 144 kW
Rated Operational Voltage
Main Circuit 1000 V
Rated Short-Circuit Making Capacity (Icm)
(690 V) 30 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 8 kA
Standards
IEC 60947-3
Terminal Type
Lug terminals
Tightening Torque
acc. IEC 60947-1 15 … 22 N·m
Tightening Torque
acc. IEC 60947-1 15 … 22 N·m
A2L Certificate – IEC
A2L Refrigerant Declaration of Conformity / OT160-800
Declaration of Conformity - CE
Declaration of Conformity / OT160EV_, OT200E_, OT250E_, OT200U_
Object Classification Code
Q
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Feature 1: Two pole design with a conventional thermal current of 160 A and rated operational current up to 200 A at 380 415 V or 160 A at 690 V. Business impact: enables reliable circuit isolation for main feeders without oversizing the enclosure, reducing panel footprint while maintaining safety. Application: motor control centers and distribution panels requiring 2P isolation with high current capability. Feature 2: Rated insulation voltage 1000 V and rated impulse withstand voltage 12 kV. Business impact: enhances dielectric strength and surge protection, lowering the risk of insulation failure during transients. Application: harsh industrial environments where voltage spikes are present. Feature 3: Lug terminals with tightening torque 15 22 N m. Business impact: simplifies field wiring, ensuring robust, repeatable connections and reducing installation time. Application: retrofit and new panel builds where secure termination is essential. Feature 4: Mechanical durability of 20000 operations and 2P configuration. Business impact: longer service life and lower maintenance cycles, translating to reduced total cost of ownership. Application: frequent switch operations in process lines and machine centers. Feature 5: Compliance and environmental documentation from ABB EcoSolutions, including End of Life Disassembling Instructions and EPD. Business impact: supports regulatory compliance, sustainability reporting, and easier end of life planning. Application: OEMs seeking verifiable ESG data for product stewardship. Feature 6: Compact dimensions and weight of 150 mm width, 110.5 mm height, 82.5 mm depth and 0.9 kg weight. Business impact: ships easily in standard frames and enclosures, cutting logistics and installation complexity. Application: space constrained control cabinets and modular switchgear layouts.

Get a Quick Quote for a ABB 1SCA120506R1001

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SCA120506R1001? Enquire Now

FAQs

The device uses lug terminals and requires tightening torque of 15–22 N m for secure connections. It is a 2P assembly with a width of 150 mm, height 110.5 mm, depth 82.5 mm, and a weight of 0.9 kg, designed for standard switchgear frames. Ensure enclosure clearance for 1000 V insulation and implement proper torque calibration during panel assembly.
Key ratings include conventional thermal current Ithe 160 A, rated operational current Ie up to 200 A at 380–415 V and 160 A at 690 V, insulation voltage 1000 V, and impulse withstand voltage 12 kV. The device supports a rated short-circuit making capacity Ic m up to 30 kA at 690 V, with a mechanical durability of 20000 cycles.
Yes. With 2P configuration, 160 A Ithe, and 1000 V insulation, it is suitable for motor control panels and switchgear assemblies requiring reliable isolation. Its compact dimensions and lug terminals streamline installation in confined spaces while meeting IEC 60947-3 requirements for safe control of electric motors and feeders.
The device conforms to IEC 60947-3 and carries a CE Declaration of Conformity. Front protection is IP00, and ABB provides associated environmental and material compliance data (EPD, CMRT, RoHS, TSCA) via ABB EcoSolutions. This supports customer regulatory reporting and sustainable procurement practices.
With a mechanical durability of 20000 cycles and robust lug terminations, maintenance intervals are extended and wiring reliability is improved. The device’s rated performance across voltage classes reduces frequent replacements, delivering lower lifecycle costs. End of Life information and disassembly instructions simplify recycling and compliance reporting.