ABB 1SDA054395R1 Moulded Case Circuit Breaker - IEC

Part Number: 1SDA054395R1
Manufacturer
ABB
Part number
1SDA054395R1

Quick Summary

ABB 1SDA054395R1 Moulded Case Circuit Breaker protects power distribution panels during fault interruption. Managing large motor loads and upstream protection without service interruptions is challenging, especially in retrofit projects. This device complies with IEC standards and carries CE conformity alongside GL certification, giving you regulatory assurance across global deployments. The 4P fixed-front terminal design integrates cleanly into modern switchgear, and the PR222DS/P-LSIG release delivers reliable tripping within the Tmax T5 family, enhancing safety and uptime. Leveraging ABB’s EcoSolutions approach, it supports predictable maintenance cycles and cost-efficient spare parts planning, helping procurement align with long-term reliability and compliance goals.

Product Information

Extended Description

1SDA054395R1 ABB: C.BREAKER TMAX T5V 400 FIXED FOUR-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC PR222DS/P-LSIG R 400
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Product Environmental Information Tmax T5 | Breakers - Packaging disposal information
E-Number (Finland)
3655409
EAN
8015644554934
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
186 mm
Product Net Height
205 mm
Product Net Depth / Length
103.5 mm
Product Net Weight
6.2 kg
Package Level 1 Units
1 piece
Package Level 1 Width
248 mm
Package Level 1 Height
240 mm
Package Level 1 Depth / Length
285 mm
Package Level 1 Gross Weight
6.2 kg
Package Level 1 EAN
8015644554934
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable For
T5
Suitable for Product Class
Moulded Case Circuit Breakers
Version
F
Electrical Durability
7000 cycle | 60 cycles per hour
Mechanical Durability
20000 cycle | 120 cycles per hour
Number of Poles
4P
Power Loss
at Rated Operating Conditions per Pole 16.5 W
Rated Current (In)
400 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 200 kA | (230 V AC) 200 kA | (380 V AC) 200 kA | (400 V AC) 200 kA | (415 V AC) 200 kA | (440 V AC) 180 kA | (500 V AC) 150 kA | (690 V AC) 80 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 5 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 200 kA | (230 V AC) 200 kA | (380 V AC) 200 kA | (400 V AC) 200 kA | (415 V AC) 200 kA | (440 V AC) 180 kA | (500 V AC) 150 kA | (690 V AC) 80 kA
Rated Uninterrupted Current (Iu)
400 A
Release
PR222DS/P-LSIG
Release Type
EL
Short-Circuit Performance Level
V
Standards
IEC
Sub-type
T5
Terminal Connection Type
Fixed Circuit-Breakers | Front
Test Voltage Max (Utest)
3500 V
Test Voltage at Industrial Frequency for 1 Minute
3500 V
Data Sheet, Technical Information
1SDC210004D0203
Declaration of Conformity - CE
EC Declaration of Conformity Tmax T5
GL Certificate
1SDL000163R0062
Instructions and Manuals
Installation instructions Tmax T5
Instructions and Manuals (Part 2)
ITSCE-RH0100001
Instructions and Manuals (Part 3)
Release PR222DS/P and PR222DS/PD T4-T5-T6
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39121100
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature → Business Impact → Application: The 4P fixed-front terminal design simplifies panel layouts and reduces field wiring complexity, accelerating installation and improving serviceability in new builds and retrofits for 690 V AC distribution. This translates to lower commissioning risk and faster time-to-operate in critical automation cells. Application: Ideal for SACE Tmax T5 configurations in manufacturing lines and process industries where space is premium and reliability is non-negotiable. Feature → Business Impact → Application: A rated current of 400 A combined with high insulation (U i 1000 V) enables dependable protection for large motor starters and transformer-fed feeders, reducing nuisance trips and extending equipment life. Application: Suitable for high-load feeders in packaging, metals, and chemical processing facilities requiring robust, industry-grade fault protection. Feature → Business Impact → Application: Rated short-circuit capacity (I cs/I cu) up to 200 kA at multiple voltages delivers strong fault-handling margins, improving plant uptime and safeguarding critical assets. Application: Transformer and switchgear protection in medium-to-large industrial installations where fault energy must be contained quickly. Feature → Business Impact → Application: The PR222DS/P-LSIG release enhances tripping reliability with fast, deterministic operation, improving personnel safety and risk management. Application: Control panels and motor control centers within Tmax T5 ecosystems that demand precise release characteristics. Feature → Business Impact → Application: Compliance and environmental attributes including CE declarations, IEC standards alignment, RoHS/REACH declarations, and GL certification simplify supplier qualification and regulatory audits. This supports lifecycle planning and cost-of-compliance management across global projects. Application: Global manufacturing footprints and OEM builds requiring documented conformity and responsible sourcing.

Get a Quick Quote for a ABB 1SDA054395R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA054395R1? Enquire Now

FAQs

This 4P fixed-front terminal breaker is designed for panel installations in 690 V AC systems. Ensure correct L1-L4 terminal connections, torque values per the installation instructions, and secure mounting within Tmax T5 switchgear. Use appropriate feeder cables and verify clearance for front-terminal entry to maintain cooling and access. Compatible with standard SACE Tmax T5 layouts, it supports straightforward retrofits and new builds alike.
The device provides a rated current of 400 A with a rated insulation voltage of 1000 V and a rated operational voltage of 690 V AC. It offers a Rated Service Short-Circuit Breaking Capacity (Ics) of up to 200 kA across several voltages, ensuring robust protection against short circuits. The release PR222DS/P-LSIG supports reliable tripping in demanding industrial environments.
Yes. The four-pole, front-terminal configuration, high Ics/Icu ratings, and PR222DS/P-LSIG release make it well-suited for transformer protection and feeder protection within Tmax T5 ecosystems. Its IEC compliance and CE declarations further support safe integration in transformer-fed panels and associated protection schemes.
The product carries CE Declaration of Conformity and IEC standard alignment, plus GL certification. It is RoHS and REACH compliant, with CMRT and TSCA declarations available. These certifications facilitate regulatory approvals, supplier qualification, and green procurement programs across international sites.
Electrical durability reaches about 7,000 cycles and mechanical durability around 20,000 cycles, supporting long service life even in high-usage environments. These characteristics help reduce unexpected outages, lower maintenance costs, and improve ROI through predictable spare parts planning and fewer field service interruptions.