ABB 1SDA054405R1 Moulded Case Circuit Breaker - IEC
Part Number: 1SDA054405R1
Quick Summary
ABB 1SDA054405R1 is a Moulded Case Circuit Breaker for high-current protection in industrial switchgear and motor control centers. Engineers often face installation constraints, front-terminal access challenges, and the need for reliable fault isolation within Tmax T5 ecosystems. This model carries IEC certification, CE conformity, RoHS and REACH declarations, as well as SCIP information to support regulatory compliance and responsible sourcing. By combining robust electrical performance with front-terminal installation and a 630 A rating, it helps reduce wiring complexity, minimize downtime, and streamline spare-part planning across power-distribution networks.
Product Information
Extended Description
1SDA054405R1 ABB: C.BREAKER TMAX T5S 630 FIXED THREE-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC PR221DS-I R 630
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
SCIP
eec7443e-5a00-408d-8a19-02e2dad6ba0c China (CN)
Simplified SCIP
e309ca93-7967-48d5-b2de-91e88e863ded Netherlands (NL) | 51dda1cc-4a28-4c69-890a-9f6770060694 Belgium (BE) | caf0f502-bbc0-453d-999c-52c7a61cad69 Greece (GR) | d48ab051-c22c-42f5-b45e-dd6cd783b46a Germany (DE) | c9b9c504-0144-425b-973f-508d3bce6f0d France (FR) | e500290f-bdc7-4418-b25d-efaf36e645cc Germany (DE) | 4ddeab55-f4c7-41f1-9cf4-fe0e229ebe6a Sweden (SE) | e3380de5-58a5-4671-afef-da96adf0506d France (FR) | d17c0d14-7bd0-41ae-81ee-5f9a7aac72e3 Poland (PL) | e8e834cd-8da0-4066-ab8f-193508b0497e Sweden (SE) | 6827c415-01e5-4013-93aa-2916e5900815 Poland (PL) | 99b55596-4a22-4c7e-bdaf-3e3ea0719a18 Bulgaria (BG) | 8738138b-0b29-4e13-aac1-6e4b0a344e6a Spain (ES) | f0258afc-b16c-4069-adee-f5b0c10cdeff Poland (PL) | 5d662e0c-6d5e-4f58-9e80-f9a6d6772b96 Portugal (PT) | 6133f87e-423f-45f7-b849-0ca41ae9fd71 Hungary (HU) | fb9dac65-04df-4832-8b87-5e7e22bb6abf Czech Republic (CZ) | 8791f3b7-5db8-4ac7-9d14-6f873d59ac1d Germany (DE) | 7ffc234d-5b0b-45a6-8ddd-6fe49a367bc0 Germany (DE) | bd829b0f-5a3b-477e-875e-e1e888a39e4f Denmark (DK) | 9dd78b0c-c450-491f-8fad-3eed9d762969 Finland (FI) | b65ea1ac-93c5-46bf-a93b-f86e5c877eb2 Norway (NO) | b1507a97-eed8-4dbd-bd10-81216e412e34 Germany (DE)
Environmental Information
Product Environmental Information Tmax T5 | Breakers - Packaging disposal information
E-Number (Finland)
3655532
EAN
8015644555030
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
140 mm
Product Net Height
205 mm
Product Net Depth / Length
103.5 mm
Product Net Weight
5.1 kg
Package Level 1 Units
1 piece
Package Level 1 Width
248 mm
Package Level 1 Height
240 mm
Package Level 1 Depth / Length
285 mm
Package Level 1 Gross Weight
5.1 kg
Package Level 1 EAN
8015644555030
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable For
T5
Suitable for Product Class
Moulded Case Circuit Breakers
Version
F
Electrical Durability
5000 cycle | 60 cycles per hour
Mechanical Durability
20000 cycle | 120 cycles per hour
Number of Poles
3P
Power Loss
at Rated Operating Conditions per Pole 41 W
Rated Current (In)
630 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 85 kA | (230 V AC) 85 kA | (380 V AC) 50 kA | (400 V AC) 50 kA | (415 V AC) 50 kA | (440 V AC) 40 kA | (500 V AC) 30 kA | (690 V AC) 25 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 85 kA | (230 V AC) 85 kA | (380 V AC) 50 kA | (400 V AC) 50 kA | (415 V AC) 50 kA | (440 V AC) 40 kA | (500 V AC) 30 kA | (690 V AC) 25 kA
Rated Uninterrupted Current (Iu)
630 A
Release
PR221DS-I
Release Type
EL
Short-Circuit Performance Level
S
Standards
IEC
Sub-type
T5
Terminal Connection Type
Fixed Circuit-Breakers | Front
Test Voltage Max (Utest)
3500 V
Test Voltage at Industrial Frequency for 1 Minute
3500 V
Data Sheet, Technical Information
1SDC210004D0203
Declaration of Conformity - CE
EC Declaration of Conformity Tmax T5
GL Certificate
1SDL000163R0062
Instructions and Manuals
Installation instructions Tmax T5
Instructions and Manuals (Part 2)
ITSCE-RH0100001
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature: High current rating and 3P design → Business Impact: Enables safe, reliable protection for large motors and feeders with a 630 A rated current and fixed three-pole configuration → Application: Suitable for 690 V AC distribution in industrial plants, transformers, and MCCs. Feature: Front-terminal connection and fixed construction → Business Impact: Simplifies panel mounting, reduces installation time, and improves maintainability in crowded switchgear areas → Application: Ideal for retrofit projects and new Tmax T5 installations where front access is required. Feature: PR221DS-I release with solid-state coordination → Business Impact: Improves tripping accuracy and selective protection, lowering fault propagation risk → Application: Critical in motor protection and transformer-feeder circuits. Feature: Environmental and regulatory compliance → Business Impact: Ensures RoHS/REACH adherence, SCIP reporting, and CE conformity, mitigating regulatory risk and easing supplier audits → Application: Useful for industries with strict sustainability and traceability requirements. Feature: Durability and efficiency metrics → Business Impact: Electrical durability up to 5000 cycles and mechanical durability up to 20000 cycles; power loss 41 W per pole → Application: Reduces lifecycle costs and energy waste in continuous operation environments.
Get a Quick Quote for a ABB 1SDA054405R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA054405R1?
Enquire Now
FAQs
This MCCB uses fixed front-terminal connections designed for straightforward alignment in compatible Tmax T5 switchgear. Verify panel cutouts and busbar spacing, then torque terminals to the manufacturer’s specification. The PR221DS-I release coordinates with Tmax T5 assemblies to ensure correct trip settings and adjustable short-circuit protection without repositioning components.
The device supports multiple Ics values depending on voltage: at 230 V AC approximately 85 kA, while at higher voltages such as 380–690 V AC ratings range down to 25 kA for Ics and Icu. This enables reliable short-circuit interruption across typical industrial distributions while maintaining selective protection in mixed-voltage installations.
Yes. With a 630 A rated current, 3P configuration, and 690 V AC operating voltage, the ABB 1SDA054405R1 is well-suited for transformer protection in 690 V networks. Its PR221DS-I release and front-terminal design support reliable fault isolation and easy integration into transformer feeder circuits within MCC configurations.
This model includes IEC standards compliance, CE Declaration of Conformity for Tmax T5, RoHS and REACH declarations, and SCIP documentation. Additional environmental and material declarations (CMRT, TSCA) provide comprehensive regulatory coverage and supply-chain transparency.
With electrical durability up to 5000 cycles and mechanical durability up to 20000 cycles, the device reduces maintenance frequency. The front-terminal design speeds installation and reduces retrofits, while RoHS/REACH and CE compliance minimize regulatory risk and potential lifecycle costs in large-scale deployment.