ABB 1SDA054433R1 Moulded Case Circuit Breaker - Ics 200 kA
Part Number: 1SDA054433R1
Quick Summary
ABB 1SDA054433R1 Moulded Case Circuit Breaker protects power distribution networks in industrial facilities. Engineers often wrestle with downtime from fault events, needing fast, reliable tripping and robust arc extinction. This Tmax T5 device carries CE declarations of conformity, IEC standards alignment, and RoHS/REACH compliance for safe, compliant installations. With a 4P front-terminal design and a 630 A rating, it reduces panel footprint and wiring complexity while meeting stringent industry requirements. In addition, compatibility with Tmax T5 release PR221DS-I and a high Ics capability supports efficient protection across motor drives, transformers, and critical load panels, delivering business value through improved uptime and safer maintenance routines.
Product Information
Extended Description
1SDA054433R1 ABB: C.BREAKER TMAX T5V 630 FIXED FOUR-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC PR221DS-I R 630
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Product Environmental Information Tmax T5 | Breakers - Packaging disposal information
EAN
8015644555375
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
186 mm
Product Net Height
205 mm
Product Net Depth / Length
103.5 mm
Product Net Weight
6.2 kg
Package Level 1 Units
1 piece
Package Level 1 Width
248 mm
Package Level 1 Height
240 mm
Package Level 1 Depth / Length
285 mm
Package Level 1 Gross Weight
6.2 kg
Package Level 1 EAN
8015644555375
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable For
T5
Suitable for Product Class
Moulded Case Circuit Breakers
Version
F
Electrical Durability
5000 cycle | 60 cycles per hour
Mechanical Durability
20000 cycle | 120 cycles per hour
Number of Poles
4P
Power Loss
at Rated Operating Conditions per Pole 41 W
Rated Current (In)
630 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 200 kA | (230 V AC) 200 kA | (380 V AC) 200 kA | (400 V AC) 200 kA | (415 V AC) 200 kA | (440 V AC) 180 kA | (500 V AC) 75 kA | (690 V AC) 40 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 200 kA | (230 V AC) 200 kA | (380 V AC) 200 kA | (400 V AC) 200 kA | (415 V AC) 200 kA | (440 V AC) 180 kA | (500 V AC) 150 kA | (690 V AC) 80 kA
Rated Uninterrupted Current (Iu)
630 A
Release
PR221DS-I
Release Type
EL
Short-Circuit Performance Level
V
Standards
IEC
Sub-type
T5
Terminal Connection Type
Fixed Circuit-Breakers | Front
Test Voltage Max (Utest)
3500 V
Test Voltage at Industrial Frequency for 1 Minute
3500 V
Data Sheet, Technical Information
1SDC210004D0203
Declaration of Conformity - CE
EC Declaration of Conformity Tmax T5
GL Certificate
1SDL000163R0062
Instructions and Manuals
Installation instructions Tmax T5
Instructions and Manuals (Part 2)
ITSCE-RH0100001
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39121100
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
4P Fixed Front-Terminal Design → Simplified installation and faster panel wiring while reducing torque and clearance issues in crowded switchgear environments. This translates to lower commissioning time and fewer field faults during assembly, improving project timelines in MCCs and control panels. 630 A Rated Current at 690 V AC → Supports medium-to-high current distribution with robust headroom for peak loads, enabling scalable panel designs and fewer future upgrades. High Ics of 200 kA → Provides strong short-circuit protection across multiple voltages (220–690 V), reducing the risk of cascading faults and minimizing downtime during fault events in industrial facilities. PR221DS-I Release (EL) → Reliable, tested release mechanism with predictable tripping behavior, improving diagnostic clarity and serviceability in rigorous maintenance programs. Front-Terminal, 4P Configuration → Compatible with compact switchgear footprints and streamlined wiring harnesses, delivering safer installations in space-constrained environments. RoHS and REACH Declarations → Compliance supports sustainability programs and supplier risk management while meeting global procurement standards. EPD/Environmental and CMRT Data → Facilitates green procurement and conflict-mineral disclosures in line with corporate ESG commitments. 41 W Power Loss per Pole → Efficient heat management in dense panels, reducing thermal stress and cooling requirements over the equipment lifecycle. Compatible with Tmax T5 ecosystem (Uimp 8 kV, Ui 1000 V) → Seamless integration with ABB protection strategies, minimizing engineering overhead for engineers migrating to Tmax architecture.
Get a Quick Quote for a ABB 1SDA054433R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA054433R1?
Enquire Now
FAQs
Install as a fixed four-pole front-terminal device within compatible switchgear or distribution panels. Ensure panel cutouts and mounting clearances follow Tmax T5 installation instructions, and connect feeders to the front terminals to simplify wiring and enable quick tripping and maintenance.
Rated current In is 630 A, rated operational voltage Ue is 690 V AC, insulation voltage Ui is 1000 V, and impulse withstand voltage Uimp is 8 kV. Short-circuit performance (Ics) reaches up to 200 kA at multiple voltages; the device uses a PR221DS-I release and offers 4P configuration with front terminals.
Yes. It includes a CE Declaration of Conformity for Tmax T5, RoHS information/status, and REACH declarations, along with CMRT for conflict minerals, aligning with common EU and global compliance requirements.
Ideal for motor control centers, transformer and generator protection, and critical power distribution panels in manufacturing plants and data centers. Its 4P front-terminal design and 630 A rating support reliable protection for medium-to-high load circuits while maintaining a compact footprint.
Electrical durability is rated at 5000 cycles and mechanical durability at 20000 cycles, with 41 W power loss per pole. Plan periodic inspection of release mechanism PR221DS-I, front-terminal connections, and adherence to installation manuals to minimize downtime and maximize uptime in mission-critical facilities.