ABB 1SDA054592R1 Moulded Case Circuit Breaker - 70 kA Ics
Part Number: 1SDA054592R1
Quick Summary
Moulded Case Circuit Breaker ABB 1SDA054592R1 guards electrical networks by interrupting fault currents in industrial power distribution. Engineers often struggle with nuisance tripping, panel downtime, and maintenance complexity during upgrades. This unit aligns with IEC standards, carries a CE Declaration, and follows RoHS compliance, supporting global regulatory needs. Designed for Tmax T protection with front terminals and a four-pole configuration, it enables fast installation, predictable diagnostics, and reliable long-term protection for critical loads, helping facilities reduce downtime, improve safety, and simplify spare-part planning across multi-site operations.
Product Information
Extended Description
1SDA054592R1 ABB: BREAKING PART TMAX T5N 630 FIXED FOUR-POLE WITH FRONT TERMINALS
Country of Origin
India (IN)
Lead Time
0 day
Made To Order
No
Warranty Return
Product under warranty must be returned
Product Sales Status
Active
Quote Only
No
Stocked At Warehouses
AETAD009EXPU
Country of Origin
India (IN)
Lead Time
0 day
Made To Order
No
Warranty Return
Product under warranty must be returned
Product Sales Status
Active
Quote Only
No
Stocked At Warehouses
BRABB008EXPU
Country of Origin
India (IN)
Lead Time
0 day
Made To Order
No
Warranty Return
Product under warranty must be returned
Product Sales Status
Active
Quote Only
No
Stocked At Warehouses
CHSEC006EXPU
Country of Origin
India (IN)
Made To Order
No
Product Sales Status
Active
Quote Only
No
Stocked At Warehouses
INABB003EXPU
Warranty Return
Product under warranty must be returned
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Product Environmental Information Tmax T5 | Breakers - Packaging disposal information
EAN
8015644556907
Minimum Order Quantity
1 piece
Customs Tariff Number
85389099
Product Net Width
186 mm
Product Net Height
205 mm
Product Net Depth / Length
103.5 mm
Product Net Weight
4.15 kg
Package Level 1 Units
1 piece
Package Level 1 Width
248 mm
Package Level 1 Height
240 mm
Package Level 1 Depth / Length
285 mm
Package Level 1 Gross Weight
4.5 kg
Package Level 1 EAN
8015644556907
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
Breaking Part
Suitable For
T5
Suitable for Product Class
Moulded Case Circuit Breakers
Version
F
Device
Breaking Part
Electrical Durability
5000 cycle | 60 cycles per hour
Mechanical Durability
20000 cycle | 120 cycles per hour
Number of Poles
4P
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC | 750 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 70 kA | (230 V AC) 70 kA | (380 V AC) 36 kA | (400 V AC) 36 kA | (415 V AC) 36 kA | (440 V AC) 30 kA | (500 V AC) 25 kA | (690 V AC) 20 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 70 kA | (230 V AC) 70 kA | (380 V AC) 36 kA | (400 V AC) 36 kA | (415 V AC) 36 kA | (440 V AC) 30 kA | (500 V AC) 25 kA | (690 V AC) 20 kA | (250 V DC) 2 Poles in Series 36 kA | (500 V DC) 2 Poles in Series 25 kA | (750 V DC) 3 Poles in Series 16 kA
Rated Uninterrupted Current (Iu)
630 A
Short-Circuit Performance Level
N
Standards
IEC
Sub-type
T5
Terminal Connection Type
Fixed Circuit-Breakers | Front
Test Voltage Max (Utest)
3500 V
Test Voltage at Industrial Frequency for 1 Minute
3500 V
Data Sheet, Technical Information
1SDC210004D0202
Declaration of Conformity - CE
EC Declaration of Conformity Tmax T5
Instructions and Manuals
Installation instructions Tmax T5
Instructions and Manuals (Part 2)
ITSCE-RH0100001
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature: Front-terminal 4P design simplifies wiring and panel assembly → Business Impact: Reduces installation time and wiring errors, improving commissioning efficiency in new panels and retrofits → Application: MCCB protection in distribution panels and transformer feed sections. Feature: High short-circuit rating up to 70 kA (Ics) across multiple voltages → Business Impact: Enhances system resilience, minimizing equipment damage during faults and allowing safe ride-through during faults → Application: Motor feeders and distribution networks in high-demand industrial environments. Feature: Rated operational voltage of 690 V AC / 750 V DC with Ui of 1000 V → Business Impact: Enables safe operation in mixed AC/DC installations, reducing component counting and wiring complexity → Application: Power distribution boards, switchgear interfaces, and hybrid facilities. Feature: Mechanical durability up to 20,000 cycles and electrical durability up to 5,000 cycles at 60 cycles/hour → Business Impact: Extends service life, lowers maintenance frequency, and lowers total cost of ownership → Application: Continuous load switching in demanding manufacturing lines. Feature: Comprehensive compliance and documentation (CE, RoHS, REACH) and sourcing transparency → Business Impact: Simplifies regulatory audits, supplier qualification, and environmental reporting → Application: Global manufacturing plants with strict compliance requirements. Feature: Stocked at multiple warehouses with zero-lead-time availability → Business Impact: Improves project scheduling and reduces downtime waiting for parts → Application: Nationwide or global rollouts and maintenance campaigns.
Get a Quick Quote for a ABB 1SDA054592R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA054592R1?
Enquire Now
FAQs
The 1SDA054592R1 uses a fixed, front-terminal design suitable for standard MCCB assemblies in distribution panels. Its four-pole configuration fits common busbar layouts, and it supports straightforward retrofits in existing Tmax T-based installations, reducing upgrade risk and downtime.
Key specs include 4P configuration, 690 V AC / 750 V DC rated operational voltage, Ui 1000 V, Iu 630 A, and short-circuit ratings up to 70 kA (Ics) across multiple voltages. Test voltage up to 3500 V confirms robust insulation, and 8 kV withstand voltage supports reliable transients handling.
Yes. It carries the CE Declaration of Conformity, supports RoHS compliance, and aligns with REACH requirements, with additional documentation such as CMRT and TSCA where applicable for global supply chains.
Lead time is listed as 0 day, and the product is stocked at multiple warehouses (e.g., AETAD009EXPU, BRABB008EXPU, CHSEC006EXPU, INABB003EXPU), enabling rapid deployment and shorter project schedules.
Ideal for transformer protection, motor feeder circuits, and main distribution panels in manufacturing and process plants. The four-pole design supports synchronized protection, while the high Ics and voltage ratings provide reliable fault clearing and protection of critical loads.