ABB 1SDA060630R1 Moulded Case Circuit Breaker - UL/CSA TMA
Part Number: 1SDA060630R1
Quick Summary
ABB 1SDA060630R1 Moulded Case Circuit Breaker protects industrial power panels with reliable trip protection. For engineers wrestling with wiring complexity and lengthy commissioning, this 3P device streamlines front-terminal installation and fast integration. UL/CSA listing, CE conformity, and RoHS/REACH compliance support global markets and regulatory alignment. With robust short-circuit protection and a 300 A rating, it delivers reliable, safe performance in demanding automation environments. This combination reduces rework, speeds assembly, and helps sustain uptime for critical processes. Designed for Tmax T family compatibility, it slots into standard switchgear and panel boards using fixed front terminals. In practice, maintenance intervals are predictable thanks to mechanical durability rated at up to twenty thousand cycles. By combining high interrupting capacity with front-terminal design, it supports safe, efficient upgrades for aging installations.
Product Information
Extended Description
1SDA060630R1 ABB: C.BREAKER TMAX T5N 400 UL/CSA FIXED THREE-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMA R 300 I3=1500...3000 A
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
SCIP
0e04b4f5-df44-4f7c-8c7c-f4ca5530c512 Italy (IT)
Simplified SCIP
68c071f9-5150-42bb-9c34-ddd47000c6d0 France (FR) | d8dd9fdb-c966-439a-8a91-5bd073631164 Germany (DE) | 91edbb5c-ee31-4a6f-8376-99bc17554fae France (FR) | d7a002b2-bd1f-419d-a9ff-98d3545f9126 Denmark (DK) | 0efd16b5-16fe-4dd6-b8a8-6258edcd87bf Greece (GR) | fc2146f6-5fee-4d7b-a53b-73d9d37649d3 Germany (DE) | 5974f858-1c12-49ae-adb7-016699ac6d45 Germany (DE) | db0747ef-e415-48b2-866d-d33625389bd6 Sweden (SE) | 8dffef27-cf51-45a0-84db-2c35a0514dc9 Germany (DE) | b5de5c44-476c-4bfb-b12e-f5ee2779e7f9 Croatia (HR) | 7eae36a1-823d-4025-a9d6-3bf825907ff4 Spain (ES) | 2e546f83-f4e8-4e02-a971-426190230495 Belgium (BE) | 7a90c75c-184b-40c6-b051-0d014ceb2267 Hungary (HU) | 353d959a-220d-44a7-95bb-c72b63adfe0e Belgium (BE) | daf61c30-775d-4cb0-b287-0ae8728aa22d Estonia (EE) | 22796ef6-dfd2-43b3-963a-16bc545a3021 Finland (FI) | 9b75e8dd-6cb5-4c38-a579-2cb3fbf4d40f Sweden (SE) | 2e0d3361-13ea-413e-ac07-b3b0e72220c2 Poland (PL) | 87a4d712-eb57-4663-a201-72013914643a Hungary (HU) | 092648ac-5020-408c-88d1-86b05480f02b Portugal (PT) | 0716b5f6-d0ad-4533-bf76-dbc66c6359e0 Czech Republic (CZ) | 16cd8edc-85e5-4528-8688-0c25d07c6573 Poland (PL) | dd4cc262-b608-4040-b025-6375c0c09ac0 Poland (PL) | 1311ced9-418e-4aaa-a750-251b0aeadaf2 Germany (DE) | cf040e48-a5e0-402e-b6d6-e06cddd2f890 Netherlands (NL) | 12b5a506-9bcb-44f7-a5a9-43af3a51d998 Norway (NO) | 18ff416b-c0a8-4712-ba10-f659ff4c96cb Bulgaria (BG)
Environmental Information
Product Environmental Information Tmax T5 | Breakers - Packaging disposal information
Order Code US and Canada
T5N300TW
EAN
8015644631253
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
140 mm
Product Net Height
205 mm
Product Net Depth / Length
103.5 mm
Product Net Weight
4.8 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
248 mm
Package Level 1 Height
240 mm
Package Level 1 Depth / Length
285 mm
Package Level 1 Gross Weight
4.8 kg
Package Level 1 EAN
8015644631253
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable For
T5
Suitable for Product Class
Moulded Case Circuit Breakers
Version
F
Mechanical Durability
20000 cycle | 120 cycles per hour
Number of Poles
3P
Power Loss
at Rated Operating Conditions per Pole 12.3 W
Rated Current (In)
300 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
600 V AC | 600 V DC
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(240 V AC) 65 kA | (480 V AC) 25 kA | (600 V AC) 18 kA | (500 V DC) 2 Poles in Series 25 kA | (600 V DC) 3 Poles in Series 16 kA
Rated Uninterrupted Current (Iu)
400 A
Release
TMA
Release Type
TM
Short-Circuit Performance Level
N
Standards
UL
Sub-type
T5
Terminal Connection Type
Fixed Circuit-Breakers | Front
Test Voltage Max (Utest)
3500 V
Interrupting Rating acc. to UL489
(240 V AC) 65 kA | (480 V AC) 25 kA | (600 V AC) 18 kA | (500 V DC) 2 Poles in Series 25 kA | (600 V DC) 3 Poles in Series 16 kA
Data Sheet, Technical Information
9AKK105713A5947
Declaration of Conformity - CE
EC Declaration of Conformity Tmax T5
Instructions and Manuals
Tmax. T Generation - Low voltage molded case circuit breakers up to 1200 A - UL 489 and CSA C22.2 Standard
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
IDEA Granular Category Code (IGCC)
4927 >> Molded case circuit breakers
UNSPSC
39121616
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature: Fixed front-terminal 3P design with TMA release enables rapid wiring, reducing wiring errors and commissioning time. Business Impact: Faster panel assembly and safer field connections translate to lower labor costs and reduced downtime. Application: Ideal for panel boards in machine building and process lines where reliability and speed matter. Feature: Rated current of 300 A and rated voltage of 600 V AC/DC provide robust protection for demanding loads. Business Impact: Keeps motors and drives within safe operating limits, improving process stability and extending equipment life. Application: Electrical distribution in manufacturing, helping meet uptime targets. Feature: High short-circuit interruption capacity (Icu up to 65 kA at 240 V AC, 25 kA at 480/600 V AC; DC 25 kA in 2 poles, 16 kA in 3 poles) ensures fast isolation of faults. Business Impact: Reduces damage to downstream equipment and minimizes arc energy exposure. Application: Critical power circuits, transformers, and switchgear protection. Feature: Front-terminal, fixed design with Tmax T compatibility and 140 mm width, 205 mm height, 103.5 mm depth and 4.8 kg weight. Business Impact: Simplifies retrofits and replacements in existing enclosures and minimizes space planning. Application: Retrofit projects and new builds with tight installation envelopes. Feature: Compliance and declarations (UL/CSA, CE DoC, RoHS/REACH, SCIP, TSCA, WEEE) provide regulatory assurance. Business Impact: Lowers compliance risk across geographies and supports sustainable sourcing. Application: Global panels and industrial installations needing traceable certifications. Feature: Mechanical durability rated at up to 20,000 cycles delivers predictable service life. Business Impact: Reduces maintenance intervals and total cost of ownership. Application: Continuous production environments with frequent switching demands.
Get a Quick Quote for a ABB 1SDA060630R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA060630R1?
Enquire Now
FAQs
This unit uses fixed front-terminal connections in a three-pole format, designed to fit standard MCCB footprints used in industrial panels. It simplifies wiring with accessible front terminals and a compact 140 mm width, easing retrofits and new installations alike. Compatible with Tmax T family gear, it supports straightforward replacement of older MCCBs in control panels and switchgear assemblies.
Key specs include three poles (3P), rated current of 300 A, rated operational voltage of 600 V AC/DC, and a rated impulse withstand voltage of 8 kV. Interrupting ratings follow UL 489: up to 65 kA at 240 V AC, 25 kA at 480/600 V AC, and 16–25 kA in DC configurations depending on pole count. Mechanical durability is rated at up to 20,000 cycles.
Yes. With a 600 V rating and 65 kA short-circuit capacity at 240 V AC, it provides reliable transformer protection and distribution in low- to medium-voltage panels. The front-terminal, fixed-mount design simplifies integration into switchgear and feeder panels, while the Tmax T release (TMA) supports selective protection coordination in transformer cabinets and related applications.
The 1SDA060630R1 is UL/CSA listed and CE compliant, with RoHS and REACH declarations. It also references SCIP registrations for multiple regions, TSCA declarations, and WEEE classification. These certifications support global procurement, regulatory compliance, and responsible supply chain management for industrial automation projects.
With a mechanical durability of up to 20,000 cycles and a front-terminal design, maintenance intervals are predictable and faster to perform, reducing downtime. The 3P 300 A rating supports dependable protection for critical loads, helping lower unplanned outages and extend equipment life, which translates to a favorable total cost of ownership over the panel’s service life.