ABB 1SDA060634R1 Moulded Case Circuit Breaker - UL/CSA
Part Number: 1SDA060634R1
Quick Summary
ABB 1SDA060634R1 Moulded Case Circuit Breaker provides reliable overload and short‑circuit protection for industrial switchgear. In demanding environments, nuisance trips and complex wiring slow maintenance and hinder uptime. It carries UL/CSA certification for North American use and CE conformity for European markets, underscoring compliance and safety. Designed for Tmax T series protection with front terminals, it supports compact, easy installation and reliable lifecycle cost. Its 3P fixed-front terminal design simplifies panel wiring and reduces field retrofit time, while 600 V ratings support typical industrial networks. This makes procurement easier by offering standardized specs and clear documentation for RoHS, REACH, and CMRT reporting.
Product Information
Extended Description
1SDA060634R1 ABB: C.BREAKER TMAX T5S 400 UL/CSA FIXED THREE-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMA R 300 I3=1500...3000 A
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Product Environmental Information Tmax T5 | Breakers - Packaging disposal information
Order Code US and Canada
T5S300TW
EAN
8015644631291
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
140 mm
Product Net Height
205 mm
Product Net Depth / Length
103.5 mm
Product Net Weight
4.8 kg
Package Level 1 EAN
8015644631291
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable For
T5
Suitable for Product Class
Moulded Case Circuit Breakers
Version
F
Mechanical Durability
20000 cycle | 120 cycles per hour
Number of Poles
3P
Power Loss
at Rated Operating Conditions per Pole 12.3 W
Rated Current (In)
300 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
600 V AC | 600 V DC
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(240 V AC) 100 kA | (480 V AC) 35 kA | (600 V AC) 25 kA | (500 V DC) 2 Poles in Series 35 kA | (600 V DC) 3 Poles in Series 25 kA
Rated Uninterrupted Current (Iu)
400 A
Release
TMA
Release Type
TM
Short-Circuit Performance Level
S
Standards
UL
Sub-type
T5
Terminal Connection Type
Fixed Circuit-Breakers | Front
Test Voltage Max (Utest)
3500 V
Interrupting Rating acc. to UL489
(240 V AC) 100 kA | (480 V AC) 35 kA | (600 V AC) 25 kA | (500 V DC) 2 Poles in Series 35 kA | (600 V DC) 3 Poles in Series 25 kA
Data Sheet, Technical Information
9AKK105713A5947
Declaration of Conformity - CE
EC Declaration of Conformity Tmax T5
GL Certificate
1SDL000163R0062
Instructions and Manuals
Tmax. T Generation - Low voltage molded case circuit breakers up to 1200 A - UL 489 and CSA C22.2 Standard
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
IDEA Granular Category Code (IGCC)
4927 >> Molded case circuit breakers
UNSPSC
39121616
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature: 3P fixed-front terminal design for Tmax T5 provides straightforward panel wiring. Business Impact: Reduces installation time and field wiring errors, lowering commissioning costs. Application: Ideal for compact switchgear in manufacturing lines where space is at a premium and quick maintenance is needed. Feature: Rated current of 300 A and 600 V operating range supports heavy loads with reliable protection. Business Impact: Ensures consistent protection for motors, transformers, and feeders while enabling safe upstream coordination. Application: Suitable for distribution boards and motor feeder segments in industrial facilities. Feature: High short-circuit protection with Icu up to 25 kA at 600 V AC (3P in series) and 35 kA for certain configurations. Business Impact: Improves system resilience against faults and minimizes downtime during fault events. Application: Critical power paths in cranes, presses, and conveyors. Feature: Front terminals and fixed mounting facilitate fast installation and easy serviceability. Business Impact: Streamlines retrofit projects and reduces maintenance window time. Application: Ideal for retrofits in legacy panels and new builds using Tmax T protection. Feature: Comprehensive compliance and documentation including RoHS, REACH, CMRT, TSCA, and CE declarations. Business Impact: Lowers regulatory risk and speeds procurement through ready-to-audit information. Application: Suitable for industries with strict material and supply-chain reporting needs.
Get a Quick Quote for a ABB 1SDA060634R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA060634R1?
Enquire Now
FAQs
The 1SDA060634R1 uses fixed-front terminals designed for direct panel mounting in a 3P configuration. During installation, confirm 600 V operating voltage, provide adequate clearance for front-access terminals, and secure connections with appropriate hardware. The front-terminal design reduces wiring complexity and enables quicker connections while keeping the device accessible for testing and tripping operations.
Key specs include rated current 300 A, rated insulation voltage 1000 V, rated operational voltage 600 V AC/DC, and test voltage max 3500 V. Interrupting rating varies by voltage level and configuration, with up to 25 kA at 600 V AC for 3P in series and 35 kA under certain arrangements. These ratings support reliable protection in typical industrial networks.
Yes. The 1SDA060634R1 is designed for Tmax T protection and is well-suited for motor feeders, transformer protection, and panelboard applications. Its 3P design, front-terminal mounting, and TM release configuration align with standard Tmax T protection schemes, while UL489 and CE certifications ensure regulatory compatibility across North American and European installations.
The device carries UL/CSA certification for North America and CE conformity for Europe. It also includes RoHS and REACH declarations, a CMRT report, and TSCA documentation. Additional references include a CE declaration of conformity and a GL certificate, ensuring broad regulatory compliance and robust supply-chain documentation.
With mechanical durability rated at 20,000 cycles and a low 12.3 W per-pole power loss, the breaker offers low running costs and extended service life. Front-terminal design speeds installation and servicing, while comprehensive documentation reduces compliance overhead. Together, these factors contribute to lower maintenance costs and improved uptime over the panel’s lifecycle.