ABB 1SDA061969R1 Moulded Case Circuit Breaker - Tmax T7S 800A 3P IEC
Part Number: 1SDA061969R1
Quick Summary
1SDA061969R1 is a molded case circuit breaker that protects industrial power distribution. Operators often struggle with finding protection devices that fit compact panels without sacrificing reliability or service life. This ABB Tmax T7S device complies with IEC standards, CE marking, and RoHS/REACH declarations, delivering regulatory assurance for modern switchgear. With an 800 A rating and front-terminal access, it enables faster installation, easier diagnostics, and reduced maintenance downtime—supporting efficient, compliant power distribution and safer plant operations.
Product Information
Extended Description
1SDA061969R1 ABB: C.BREAKER TMAX T7S 800 FIXED THREE-POLE WITH FRONT TERMINALS AND LEVER OPERATING MECHANISM AND SOLID-STATE RELEASE IN AC PR332/P-LSIRc R 800
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Product Environmental Information Tmax T7 | Breakers - Packaging disposal information
EAN
8015644645076
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
210 mm
Product Net Height
268 mm
Product Net Depth / Length
154 mm
Product Net Weight
9.7 kg
Package Level 1 Units
1 piece
Package Level 1 Width
280 mm
Package Level 1 Height
350 mm
Package Level 1 Depth / Length
360 mm
Package Level 1 Gross Weight
11.2 kg
Package Level 1 EAN
8015644645076
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable For
T7
Suitable for Product Class
Moulded Case Circuit Breakers
Version
F
Electrical Durability
2000 cycle | 60 cycles per hour
Mechanical Durability
10000 cycle | 60 cycles per hour
Number of Poles
3P
Power Loss
at Rated Operating Conditions per Pole 19.3 W
Rated Current (In)
800 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 85 kA | (230 V AC) 85 kA | (380 V AC) 50 kA | (400 V AC) 50 kA | (415 V AC) 50 kA | (440 V AC) 50 kA | (500 V AC) 40 kA | (690 V AC) 30 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 20 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 85 kA | (230 V AC) 85 kA | (380 V AC) 50 kA | (400 V AC) 50 kA | (415 V AC) 50 kA | (440 V AC) 50 kA | (500 V AC) 40 kA | (690 V AC) 30 kA
Rated Uninterrupted Current (Iu)
800 A
Release
PR332/P-LSIRc
Release Type
EL
Short-Circuit Performance Level
S
Standards
IEC
Sub-type
T7
Terminal Connection Type
Fixed Circuit-Breakers | Front
Data Sheet, Technical Information
1SDC210015D0201
Declaration of Conformity - CE
EC Declaration of Conformity Tmax T7
GL Certificate
1SDL000163R0055
Instructions and Manuals
1SDC210015D0201
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39121100
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
The 1SDA061969R1 delivers 800 A rated current and 690 V operating voltage, enabling robust protection for heavy feeders in manufacturing and critical infrastructure. This performance translates to faster interruption of fault currents (Ics/Icu up to 30 kA at 690 V), minimizing damage to transformers and cables while preserving system uptime and allowing smaller conductor sizing in compliant switchgear installations. The front-terminal design paired with a lever-operating mechanism and PR332/P-LSIRc electronic release improves accessibility during panel commissioning and maintenance, reducing installation time and wiring errors. Compliance is reinforced by RoHS, REACH, and CMRT declarations, supporting sustainable procurement and regulatory conformity. Power loss remains efficient at 19.3 W per pole, contributing to cooler enclosures and lower cooling costs in large installations. The product’s 3P configuration and Tmax T lineage provide predictable tripping characteristics for motor and transformer protection, with straightforward retrofitting into existing SACE Tmax T panels and standardized ETIM classifications for parts compatibility.
Get a Quick Quote for a ABB 1SDA061969R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA061969R1?
Enquire Now
FAQs
The 1SDA061969R1 is designed as a fixed-front-terminal 3P MCCB in the Tmax T family, matching ABB Tmax T switchgear footprints and mounting conventions. With 210 mm width, 268 mm height, and 154 mm depth, it integrates into standard 3-pole enclosures while maintaining clear front-access for testing and manual operation. Verify panel cutouts and terminal torque guidelines per the 1SDC210015D0201 datasheet, but typical retrofits are straightforward and reduce wiring complexity.
At 690 V, the unit provides a rated service short-circuit breaking capacity of 30 kA (Ics) and an ultimate capacity (Icu) also up to 30 kA. This high protection level is well suited for transformer and motor feeder protection in industrial plants, allowing selective coordination with upstream protection while minimizing equipment damage during faults.
PR332/P-LSIRc is a solid-state release integrated with the Tmax T7S lineup, supporting electronic/trip-level control within the AC domain. This release enhances tripping precision, improves coordination with protective relays, and enables reliable remote or timed operation within control cabinets. The EL release type indicates electronic actuation suitable for modern automation schemes.
The breaker weighs about 9.7 kg with front-terminal access for easy wiring and removal. It carries RoHS and REACH declarations, plus CMRT for responsible sourcing. Packaging information lists a single unit per package, with EPN-related environmental disclosures. For installation, ensure adequate clearances for front-access operability and verify mounting height and enclosure compatibility in accordance with local electrical codes.
Ideal for transformer protection, motor-control centers, and critical power feeders in manufacturing, energy, and process industries, this MCCB delivers reliable short-circuit interruption with 800 A rating and 690 V capability. Benefits include reduced downtime, safer maintenance, and streamlined compliance with IEC, CE, RoHS, and REACH mandates, contributing to lower lifecycle costs and faster project timelines in large-scale switchgear installations.