ABB 1SDA061980R1 Moulded Case Circuit Breaker - CE
Part Number: 1SDA061980R1
Quick Summary
The ABB 1SDA061980R1 Moulded Case Circuit Breaker protects high-current power systems in industrial switchgear. It addresses common panel-wiring and accessibility challenges by offering front-terminal connections and a robust 3P design for reliable protection. Certifications and declarations like CE, RoHS, REACH, TSCA, and ETIM support regulatory alignment and global applicability. This solution delivers clear business value by enabling faster panel assembly, improved safety, and predictable maintenance cycles, while supporting the Tmax T family’s engineering standards. For systems requiring high reliability and lifecycle cost control, this MCCB is a strong fit within transformer houses, machine rooms, and distribution panels that demand durable, code-compliant protection.
Product Information
Extended Description
1SDA061980R1 ABB: C.BREAKER TMAX T7S 800 FIXED THREE-POLE WITH FRONT TERMINALS AND STORED ENERGY OPERATING MECHANISM AND SOLID-STATE RELEASE IN AC PR231/P-I R 800
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Product Environmental Information Tmax T7 | Breakers - Packaging disposal information
EAN
8015644645267
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
210 mm
Product Net Height
268 mm
Product Net Depth / Length
178 mm
Product Net Weight
11 kg
Package Level 1 Units
1 piece
Package Level 1 Width
280 mm
Package Level 1 Height
350 mm
Package Level 1 Depth / Length
360 mm
Package Level 1 Gross Weight
12.5 kg
Package Level 1 EAN
8015644645267
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable For
T7M
Suitable for Product Class
Moulded Case Circuit Breakers
Version
F
Electrical Durability
2000 cycle | 60 cycles per hour
Mechanical Durability
10000 cycle | 60 cycles per hour
Number of Poles
3P
Power Loss
at Rated Operating Conditions per Pole 19.3 W
Rated Current (In)
800 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 85 kA | (230 V AC) 85 kA | (380 V AC) 50 kA | (400 V AC) 50 kA | (415 V AC) 50 kA | (440 V AC) 50 kA | (500 V AC) 40 kA | (690 V AC) 30 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 20 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 85 kA | (230 V AC) 85 kA | (380 V AC) 50 kA | (400 V AC) 50 kA | (415 V AC) 50 kA | (440 V AC) 50 kA | (500 V AC) 40 kA | (690 V AC) 30 kA
Rated Uninterrupted Current (Iu)
800 A
Release
PR231/P-I
Release Type
EL
Short-Circuit Performance Level
S
Standards
IEC
Sub-type
T7
Terminal Connection Type
Fixed Circuit-Breakers | Front
Data Sheet, Technical Information
1SDC210015D0201
Declaration of Conformity - CE
EC Declaration of Conformity Tmax T7
GL Certificate
1SDL000163R0055
Instructions and Manuals
1SDC210015D0201
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature → Business Impact → Application: The 3P 800 A MCCB with PR231/P-I release delivers robust overcurrent protection for large motor loads and distribution feeders, reducing unplanned downtime and safeguarding expensive equipment. Application: Ideal for switchgear and machine control centers where quick, repeatable tripping is essential for uptime. Feature → Front-terminal fixed connection → Installation efficiency and safer wire routing. Business Impact → Faster commissioning and reduced installer risk, especially in confined panel spaces. Application → Control panels and transformer housings where front-accessibility is a must. Feature → Rated 690 V AC operation with 8 kV impulse withstand → Enhanced safety margins and compliance for medium-voltage networks. Application → Industrial plants and packaging lines with higher voltage requirements. Feature → Electrical durability of 2000 cycles and mechanical durability of 10000 cycles → Lower lifecycle maintenance and extended service intervals. Application → High-use protection points such as conveyors and presses where cycling is frequent. Feature → RoHS, REACH, CMRT, TSCA declarations and CE conformity → Regulatory compliance reduces risk of non-conformance penalties and supports sustainability programs. Application → Global rollouts and regulated sectors including energy, water treatment, and heavy manufacturing. The product’s compact Tmax T footprint and 210 mm width help engineers fit protective devices into compact switchgear designs while meeting international standards, making it a practical choice for OEMs and integrators seeking reliable protection without oversized cabinets.
Get a Quick Quote for a ABB 1SDA061980R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA061980R1?
Enquire Now
FAQs
The ABB 1SDA061980R1 is a fixed circuit-breaker with front-terminal connections, designed for easy integration into switchgear and control panels. The front-access design simplifies wiring during assembly and maintenance, reducing field labor and minimizing panel opening time. It is compatible with SACE Tmax T configurations and aligns with IEC standards for safe, reliable installation.
The device is rated for 800 A and 690 V AC operating voltage, with a rated impulse withstand voltage of 8 kV. Short-circuit protection offers Ics up to 85 kA at lower voltages and 30 kA at higher voltages, while Icw is 20 kA for 1 second. These ratings support dependable protection for feeders, transformers, and motor circuits in industrial environments.
Yes. The MCCB carries a CE declaration of conformity for Tmax T7 protection, and ABB provides RoHS and REACH declarations for Sace Tmax T circuit breakers. It also supports CMRT and TSCA declarations, ensuring regulatory compliance across European, North American, and global supply chains.
Product net dimensions are 210 mm in width, 268 mm in height, and 178 mm in depth, with a net weight of 11 kg. Packaging and freight details show a Package Level 1 width of 280 mm and height of 350 mm, with a gross weight of 12.5 kg. These measurements help engineers allocate correct panel space and enclosure clearances.
Durability specs include 10000 mechanical cycles and 2000 electrical cycles, supporting long service life under typical load profiles. The front-terminal design reduces wiring time during servicing, while reliable Ics/Icu performance minimizes nuisance trips. Together, these factors lower downtime, extend component life, and deliver favorable total cost of ownership for critical power protection.