ABB 1SDA061982R1 Moulded Case Circuit Breaker - PR232/P-LSI

Part Number: 1SDA061982R1
Manufacturer
ABB
Part number
1SDA061982R1

Quick Summary

Moulded Case Circuit Breaker ABB 1SDA061982R1 provides reliable overcurrent protection for industrial power distribution in medium‑voltage panels. Engineers often contend with downtime during fault isolation and limited front-terminal access that slows maintenance. It aligns with IEC standards and carries CE conformity, RoHS compliance, and TSCA declarations to support global procurement. For OEMs and service teams, the 800 A rating and PR232/P-LSI stored‑energy release translate into safer operations, quicker resets, and lower lifecycle costs across high‑demand applications.

Product Information

Extended Description

1SDA061982R1 ABB: C.BREAKER TMAX T7S 800 FIXED THREE-POLE WITH FRONT TERMINALS AND STORED ENERGY OPERATING MECHANISM AND SOLID-STATE RELEASE IN AC PR232/P-LSI R 800
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Product Environmental Information Tmax T7 | Breakers - Packaging disposal information
Order Code US and Canada
T7MSFA3AC000000XX
EAN
8015644645281
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
210 mm
Product Net Height
268 mm
Product Net Depth / Length
178 mm
Product Net Weight
11 kg
Package Level 1 Units
1 piece
Package Level 1 Width
280 mm
Package Level 1 Height
350 mm
Package Level 1 Depth / Length
360 mm
Package Level 1 Gross Weight
12.5 kg
Package Level 1 EAN
8015644645281
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable For
T7M
Suitable for Product Class
Moulded Case Circuit Breakers
Version
F
Electrical Durability
2000 cycle | 60 cycles per hour
Mechanical Durability
10000 cycle | 60 cycles per hour
Number of Poles
3P
Power Loss
at Rated Operating Conditions per Pole 19.3 W
Rated Current (In)
800 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 85 kA | (230 V AC) 85 kA | (380 V AC) 50 kA | (400 V AC) 50 kA | (415 V AC) 50 kA | (440 V AC) 50 kA | (500 V AC) 40 kA | (690 V AC) 30 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 20 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 85 kA | (230 V AC) 85 kA | (380 V AC) 50 kA | (400 V AC) 50 kA | (415 V AC) 50 kA | (440 V AC) 50 kA | (500 V AC) 40 kA | (690 V AC) 30 kA
Rated Uninterrupted Current (Iu)
800 A
Release
PR232/P-LSI
Release Type
EL
Short-Circuit Performance Level
S
Standards
IEC
Sub-type
T7
Terminal Connection Type
Fixed Circuit-Breakers | Front
Data Sheet, Technical Information
1SDC210015D0201
Declaration of Conformity - CE
EC Declaration of Conformity Tmax T7
GL Certificate
1SDL000163R0055
Instructions and Manuals
1SDC210015D0201
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature → Business Impact → Application: Front terminals and stored-energy mechanism enable fast, controlled operation and safer maintenance with minimal manual effort, reducing downtime and exposure to arc flash during servicing; application in MCCB panels where quick re-energization is critical for production uptime. Feature → Business Impact → Application: Rated 800 A continuous current with high short-circuit withstand (Ics up to 85 kA at multiple voltages) provides robust protection for transformer and distribution lines, lowering the risk of cascading failures in heavy‑duty panels. Feature → Business Impact → Application: 690 V AC rated operational voltage and 1000 V insulation support integration into modern industrial networks, enabling compliant, compact protection in higher‑voltage installations. Feature → Business Impact → Application: PR232/P‑LSI release type delivers precise tripping and reliable energy release, improving fault clearances and operator safety in demanding environments. Feature → Business Impact → Application: RoHS, REACH, CMRT, and TSCA declarations streamline global compliance and supplier risk management, simplifying procurement for multinational facilities. Feature → Business Impact → Application: Documented mechanical durability (10,000 cycles) and electrical durability (2,000 cycles) support predictable maintenance planning and extended service intervals in continuous‑operation facilities.

Get a Quick Quote for a ABB 1SDA061982R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA061982R1? Enquire Now

FAQs

The 1SDA061982R1 MCCB is ideal for medium‑voltage power distribution in industrial panels, transformer protection, and OEM panel builds requiring robust 3P protection with front‑terminal accessibility and stored‑energy release for rapid, safe operation.
It features a rated current of 800 A, rated operational voltage of 690 V AC, rated insulation voltage of 1000 V, and an impulse withstand voltage of 8 kV. It supports high fault currents with a rated service short‑circuit breaking capacity up to 85 kA depending on voltage.
PR232/P-LSI is a stored‑energy release that enables quick, reliable tripping and easier resetting after faults, reducing maintenance time and enhancing operator safety during disconnection and re‑energization.
Yes. The product carries RoHS and REACH declarations, CMRT (Conflict Minerals), and TSCA declarations, aligning with global regulatory expectations and helping streamline cross‑border procurement.
It is a fixed, front‑terminal MCCB for 3P configurations, compatible with Tmax T7 systems and 690 V AC networks. Ensure correct terminal torque, suitable enclosure protection, and proper clearances for safe front‑accessible servicing and maintenance.