ABB 1SDA061989R1 Moulded Case Circuit Breaker - IEC

Part Number: 1SDA061989R1
Manufacturer
ABB
Part number
1SDA061989R1

Quick Summary

ABB 1SDA061989R1 Moulded Case Circuit Breaker is a high‑capacity protective device designed for industrial power distribution. Engineers often struggle with front‑access installation and reliable protection under heavy fault conditions. It meets IEC standards with CE conformity, RoHS and REACH declarations, and SCIP registrations to address regulatory and sustainability requirements. With front terminal access and a four‑pole 800 A rating, it supports scalable protection for MCCB panels and motor feeders. That combination translates to faster commissioning, easier maintenance, and improved uptime in demanding manufacturing environments.

Product Information

Extended Description

1SDA061989R1 ABB: C.BREAKER TMAX T7S 800 FIXED FOUR-POLE WITH FRONT TERMINALS AND STORED ENERGY OPERATING MECHANISM AND SOLID-STATE RELEASE IN AC PR231/P-LS/I R 800
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
SCIP
e36059f7-97dd-4abb-bac3-78623a1211ff Italy (IT)
Simplified SCIP
a3e5b9ff-a538-4b72-83ce-5eda09478d7c Germany (DE) | 58eb3ff5-d529-4c55-a651-dec498db87f0 Poland (PL) | 61797bce-3b90-476b-9aa9-6e3a61fab0b5 Denmark (DK) | edfe12ad-b7b1-41d1-b679-b2ee7699acb8 Germany (DE) | 368a2bff-49b4-4b3c-9356-20551345b680 Czech Republic (CZ) | 664431f0-dd7b-4519-bb01-1d3bb8a40cd1 Sweden (SE) | 69e87f1e-184a-4965-b6b4-dcbd1977ba0c Germany (DE) | b571d6da-04a0-4b96-bb4e-e0e3bc3e8a1e France (FR) | 7a5492b2-0465-45d1-ae3b-09fa54b3f9b3 Netherlands (NL) | 27ecdb6e-acda-4969-9cd5-9e1b0926c2f3 Spain (ES) | 5ed6144a-9f23-4800-b606-fe4bfe3df189 Poland (PL) | d447ede2-98f8-4a62-b8e8-34e3968e5393 Netherlands (NL) | df61bfc0-6f41-471a-b6f3-1dd2d119960d Netherlands (NL) | 98ec3e70-698b-47a4-862c-2cf71304dd14 Estonia (EE) | 47a0ae21-934a-4d55-9b53-fb392cb9db11 Greece (GR) | 31e46f94-7797-44c3-9e38-00024932057b Portugal (PT) | a0391ff3-5980-461b-a114-8d83ea9fc137 Bulgaria (BG) | 86ebb752-502e-483e-9838-eae7a7f7835f Sweden (SE) | e42e863c-c79a-4a6f-8427-a630ecd05560 Poland (PL) | 0841a94b-da59-41de-b1af-b62a77399b8e Germany (DE) | 7c9e6f90-55c8-460a-878c-848c1bc1fe96 Netherlands (NL) | 67ec689b-3a94-4c29-b8ed-7a6923209974 Finland (FI) | a9f0de4e-1103-4651-8ea3-04d88e8b962f Norway (NO) | 3418ecb2-14fc-47e4-8a02-fb6e6a014c45 Croatia (HR) | 0fa9bf2c-369b-4e2d-b0a1-43c7ec23d649 France (FR) | f9b9187d-a9a9-4ca1-8e7e-1045b3a0e1f9 Netherlands (NL) | e6403f1c-8d01-4d20-a95a-baad313e91d7 Germany (DE)
Environmental Information
Product Environmental Information Tmax T7 | Breakers - Packaging disposal information
EAN
8015644645359
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
280 mm
Product Net Height
268 mm
Product Net Depth / Length
178 mm
Product Net Weight
14 kg
Package Level 1 Units
1 piece
Package Level 1 Width
360 mm
Package Level 1 Height
350 mm
Package Level 1 Depth / Length
360 mm
Package Level 1 Gross Weight
15.5 kg
Package Level 1 EAN
8015644645359
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable For
T7M
Suitable for Product Class
Moulded Case Circuit Breakers
Version
F
Electrical Durability
2000 cycle | 60 cycles per hour
Mechanical Durability
10000 cycle | 60 cycles per hour
Number of Poles
4P
Power Loss
at Rated Operating Conditions per Pole 19.3 W
Rated Current (In)
800 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 85 kA | (230 V AC) 85 kA | (380 V AC) 50 kA | (400 V AC) 50 kA | (415 V AC) 50 kA | (440 V AC) 50 kA | (500 V AC) 40 kA | (690 V AC) 30 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 20 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 85 kA | (230 V AC) 85 kA | (380 V AC) 50 kA | (400 V AC) 50 kA | (415 V AC) 50 kA | (440 V AC) 50 kA | (500 V AC) 40 kA | (690 V AC) 30 kA
Rated Uninterrupted Current (Iu)
800 A
Release
PR231/P-LS/I
Release Type
EL
Short-Circuit Performance Level
S
Standards
IEC
Sub-type
T7
Terminal Connection Type
Fixed Circuit-Breakers | Front
Data Sheet, Technical Information
1SDC210015D0201
Declaration of Conformity - CE
EC Declaration of Conformity Tmax T7
GL Certificate
1SDL000163R0055
Instructions and Manuals
1SDC210015D0201
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Front-terminal, fixed 4P design provides dependable wiring and streamlined installation, reducing field wiring errors and enabling quicker panel assembly, which translates to lower commissioning time and total cost of ownership. The 800 A rated current and 690 V AC operational voltage deliver robust protection for high‑demand feeders, supporting reliable uptime in continuous process industries and large motor drives. High short‑circuit performance, with Ics up to 85 kA at 220/230 V and up to 30 kA at 690 V, ensures selective coordination and reduced damage in fault events, minimizing downtime and maintenance costs. The PR231/P‑LS/I stored‑energy release enhances trip reliability and fast disconnection, improving safety margins during overloads and short circuits in control cabinets and distribution boards. Compliance goals are strengthened by RoHS, REACH, and SCIP declarations, helping procurement meet global sustainability and regulatory requirements. The product’s compatibility with Tmax T and T7 series simplifies device siting in existing MCCB panels, easing retrofit projects and standardizing protection across facilities.

Get a Quick Quote for a ABB 1SDA061989R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA061989R1? Enquire Now

FAQs

This 4P device uses fixed front terminals, simplifying wiring routing and panel layout. Its compact footprint and front-access design streamline commissioning and future maintenance, reducing field labor and potential connection faults.
Rated current is 800 A with a rated operational voltage of 690 V AC and rated insulation voltage of 1000 V. It withstands impulses up to 8 kV and provides robust short‑circuit protection up to 85 kA at 220/230 V and 30 kA at 690 V.
Yes. The model carries RoHS and REACH declarations and SCIP registration, aligning with European and global sustainability and regulatory requirements for electrical protection devices.
Ideal for motor feeders, Transformer protection, and main distribution panels in manufacturing, process industries, and data centers where reliable high‑current protection and front‑panel serviceability are valued.
With front terminals and a stored‑energy release, routine inspection should verify mechanical operation of the PR231/P‑LS/I mechanism, contact wear, and terminal torque. The device supports straightforward replacement within Tmax T7 series ecosystems, reducing downtime during service.