ABB 1SDA061994R1 Moulded Case Circuit Breaker - IEC
Part Number: 1SDA061994R1
Quick Summary
ABB 1SDA061994R1 Moulded Case Circuit Breaker provides reliable overcurrent protection for medium‑voltage switchgear and industrial control panels. For engineers upgrading legacy gear, downtime and compatibility are constant pain points, so a high‑performance, front‑terminal design helps speed installation and service. It carries CE conformity (EC Declaration of Conformity), RoHS and REACH declarations, and CMRT/TSCA compliance to meet global regulatory expectations. The 800 A rated current with 690 V AC operation and 85 kA short‑circuit capability supports scalable protection for transformers and MCCs, while the Tmax T7 family fit ensures procurement consistency across fleets. This combination delivers improved uptime, safer operation, and lower lifecycle costs for critical electrical protection workloads.
Product Information
Extended Description
1SDA061994R1 ABB: C.BREAKER TMAX T7S 800 FIXED FOUR-POLE WITH FRONT TERMINALS AND STORED ENERGY OPERATING MECHANISM AND SOLID-STATE RELEASE IN AC PR332/P-LSIG R 800
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Product Environmental Information Tmax T7 | Breakers - Packaging disposal information
Order Code US and Canada
T7MSFA4AS000000XX
EAN
8015644645403
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
280 mm
Product Net Height
268 mm
Product Net Depth / Length
178 mm
Product Net Weight
14 kg
Package Level 1 Units
1 piece
Package Level 1 Width
360 mm
Package Level 1 Height
350 mm
Package Level 1 Depth / Length
360 mm
Package Level 1 Gross Weight
15.5 kg
Package Level 1 EAN
8015644645403
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable For
T7M
Suitable for Product Class
Moulded Case Circuit Breakers
Version
F
Electrical Durability
2000 cycle | 60 cycles per hour
Mechanical Durability
10000 cycle | 60 cycles per hour
Number of Poles
4P
Power Loss
at Rated Operating Conditions per Pole 19.3 W
Rated Current (In)
800 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 85 kA | (230 V AC) 85 kA | (380 V AC) 50 kA | (400 V AC) 50 kA | (415 V AC) 50 kA | (440 V AC) 50 kA | (500 V AC) 40 kA | (690 V AC) 30 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 20 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 85 kA | (230 V AC) 85 kA | (380 V AC) 50 kA | (400 V AC) 50 kA | (415 V AC) 50 kA | (440 V AC) 50 kA | (500 V AC) 40 kA | (690 V AC) 30 kA
Rated Uninterrupted Current (Iu)
800 A
Release
PR332/P LSIG
Release Type
EL
Short-Circuit Performance Level
S
Standards
IEC
Sub-type
T7
Terminal Connection Type
Fixed Circuit-Breakers | Front
Data Sheet, Technical Information
1SDC210015D0201
Declaration of Conformity - CE
EC Declaration of Conformity Tmax T7
GL Certificate
1SDL000163R0055
Instructions and Manuals
1SDC210015D0201
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature: Front-terminal fixed construction with four poles. Business impact: Simplified wiring, faster installation, and reliable conductor terminations, reducing commissioning time and field errors. Application: Ideal for MCCs, switchgear racks, and transformer feeders in industrial environments. Feature: PR332/P LSIG release. Business impact: Precise, stored-energy release enhances protection accuracy and operator safety during trip events. Application: Critical protection in large distribution panels and motor control centers. Feature: 800 A rated current and 690 V AC rating. Business impact: High-capacity protection for medium‑voltage feeders, enabling fewer devices per bus and streamlined coordination. Application: Transformer protection and MCC upstream of high‑demand loads. Feature: 85 kA short-circuit breaking capacity (Ics). Business impact: Robust fault handling reduces arc exposure and equipment damage. Application: Facilities with high fault current potential in manufacturing and process industries. Feature: Mechanical 10000 cycles and electrical 2000 cycles durability. Business impact: Longer service life and lower maintenance frequency. Application: Continuous production lines with frequent switching. Feature: Compliance and environmental data. Business impact: Ensures regulatory adherence and sustainable procurement. Application: Global operations requiring RoHS, REACH, CMRT, TSCA, and packaging disposal considerations. Feature: Compatibility with Tmax T7 family and front-terminal design. Business impact: Streamlined sourcing and uniform installation practices across multiple sites. Application: Systems consolidating spare parts and standardizing upgrades across OEM and end-user installations.
Get a Quick Quote for a ABB 1SDA061994R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA061994R1?
Enquire Now
FAQs
Installation should follow ABB’s Tmax T7 guidelines (ref: 1SDC210015D0201). Ensure the panel allows front-terminal wiring access, align the four poles for correct phase sequencing, secure all connections to the fixed terminals, and verify the LSIG release mechanism is properly reset after installation to ensure reliable tripping behavior.
Key specs include four poles (4P), rated current 800 A, rated operational voltage 690 V AC, rated insulation voltage 1000 V, rated impulse withstand voltage 8 kV, short‑time withstand current 20 kA for 1 s, and short‑circuit breaking capacity up to 85 kA. Release type is PR332/P LSIG, with a front-terminal connection.
Yes. Its 85 kA Ics rating and 690 V AC operation make it suitable for transformer protection and MCC sections. The front-terminal design simplifies wiring in dense switchgear enclosures, while the 800 A rated current supports high-demand feeders, reducing the device count and improving system reliability.
The device carries CE conformity with the EC Declaration of Conformity, RoHS and REACH declarations, CMRT and TSCA declarations, and packaging/disposal information. These certifications support regulatory compliance, safer procurement, and sustainable sourcing across global operations.
Durability specs show electrical endurance of 2000 cycles and mechanical endurance of 10000 cycles, reducing maintenance intervals. The front-terminal design speeds servicing, while high fault‑current rating minimizes downtime during fault events, delivering lower total cost of ownership for critical protection workloads.