ABB 1SDA062734R1 Moulded Case Circuit Breaker - PR332/P LSI
Part Number: 1SDA062734R1
Quick Summary
ABB 1SDA062734R1 Moulded Case Circuit Breaker provides reliable 800A protection for industrial power feeds. This high-current device is designed for compact installations with front terminals and a stored-energy operating mechanism, addressing space and maintenance challenges common in switchgear enclosures. CE conformity, IEC standards compliance, RoHS declarations, and CMRT disclosures support regulatory and supply-chain expectations. For design engineers and procurement teams, the product offers a robust combination of protection, safety, and lifecycle efficiency, enabling predictable downtime performance and simplified spares management. When selecting Tmax Tmax T protection, you gain a scalable solution that integrates with T7M and other distribution configurations while supporting sustainable sourcing and compliant waste management practices.
Product Information
Extended Description
1SDA062734R1 ABB: C.BREAKER TMAX T7V 800 FIXED FOUR-POLE WITH FRONT TERMINALS AND STORED ENERGY OPERATING MECHANISM AND SOLID-STATE RELEASE IN AC PR332/P-LSI R 800
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Product Environmental Information Tmax T7 | Breakers - Packaging disposal information
Order Code US and Canada
T7MVFA4AR000000XX
EAN
8015644652838
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
280 mm
Product Net Height
268 mm
Product Net Depth / Length
178 mm
Product Net Weight
14 kg
Package Level 1 Units
1 piece
Package Level 1 Width
360 mm
Package Level 1 Height
350 mm
Package Level 1 Depth / Length
360 mm
Package Level 1 Gross Weight
15.5 kg
Package Level 1 EAN
8015644652838
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable For
T7M
Suitable for Product Class
Moulded Case Circuit Breakers
Version
F
Electrical Durability
3000 cycle | 60 cycles per hour
Mechanical Durability
10000 cycle | 60 cycles per hour
Number of Poles
4P
Power Loss
at Rated Operating Conditions per Pole 32 W
Rated Current (In)
800 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 200 kA | (230 V AC) 200 kA | (380 V AC) 150 kA | (400 V AC) 150 kA | (415 V AC) 150 kA | (440 V AC) 130 kA | (500 V AC) 100 kA | (690 V AC) 45 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 15 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 200 kA | (230 V AC) 200 kA | (380 V AC) 150 kA | (400 V AC) 150 kA | (415 V AC) 150 kA | (440 V AC) 130 kA | (500 V AC) 100 kA | (690 V AC) 60 kA
Rated Uninterrupted Current (Iu)
800 A
Release
PR332/P LSI
Release Type
EL
Short-Circuit Performance Level
V
Standards
IEC
Sub-type
T7
Terminal Connection Type
Fixed Circuit-Breakers | Front
Data Sheet, Technical Information
1SDC210015D0201
Declaration of Conformity - CE
EC Declaration of Conformity Tmax T7
GL Certificate
1SDL000163R0056
Wiring Diagram
Wiring diagram T7-T7M
Instructions and Manuals
1SDC210015D0201
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature → Business Impact → Application: Four-pole fixed-front-terminal design provides easy access during installation and maintenance, reducing wiring errors and field service time while enabling safer front-access connections in panel boards. This translates to tangible labor savings and lower risk during commissioning in harsh industrial environments, especially where space is at a premium. Feature → Business Impact → Application: 800 A rated current with 690 V AC operation and 8 kV rated impulse withstand ensures strong fault protection and resilience against transient overvoltages, supporting safer motor-distribution feeds and transformer safeguarding in heavy-duty applications. Feature → Business Impact → Application: PR332/P LSI stored-energy release and EL-type operation deliver precise, rapid tripping with minimal manual intervention, improving system uptime and operator confidence in automated protection schemes within process plants. Feature → Business Impact → Application: RoHS and CMRT disclosures, along with CE conformity and IEC standards, reduce compliance risk and simplify supplier audits for regulated environments, aiding procurement workflows and green manufacturing reporting. Feature → Business Impact → Application: 4P Tmax T lineage compatibility and ETIM/EC classification alignment streamline engineering drawings, BOMs, and warehouse categorization, accelerating project kick-offs and reducing design iteration time. Feature → Business Impact → Application: Mechanical durability of 10000 cycles and electrical durability of 3000 cycles translate to longer service life under typical industrial duty cycles, lowering total cost of ownership and spare-part inventory for maintenance teams.
Get a Quick Quote for a ABB 1SDA062734R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA062734R1?
Enquire Now
FAQs
This MCCB uses fixed front terminals designed for straightforward panel mounting and front-access wiring, simplifying installation and future maintenance in compact switchgear. It is compatible with Tmax T protection schemes and is readily integrated into motor feeder and transformer protection configurations.
Key specs include a rated current of 800 A, rated operational voltage of 690 V AC, insulation voltage of 1000 V, rated impulse withstand of 8 kV, and a 4P configuration with PR332/P LSI release. Short-circuit and endurance ratings ensure dependable performance under fault conditions.
Yes. The unit carries CE conformity with the EC Declaration of Conformity and RoHS declarations for restricted substances. CMRT and TSCA disclosures are also provided to support global supply-chain transparency and responsible sourcing.
Standard Tmax T protection applications include switchgear, distribution boards, transformers, and critical distribution feeders in industrial plants. It supports high-current protection, front-terminal accessibility, and reliable operation in demanding environments.
Electrical durability is rated at 3000 cycles and mechanical durability at 10000 cycles under typical duty. These metrics translate to longer service life, reduced maintenance intervals, and lower total cost of ownership for plants with frequent switching or protection reconfigurations.