ABB 1SDA062742R1 Moulded Case Circuit Breaker - IEC
Part Number: 1SDA062742R1
Quick Summary
Moulded Case Circuit Breaker protects power distribution systems by interrupting fault currents in industrial automation networks. Engineers often face front-access wiring challenges and uncertain trip reliability in compact control panels. This ABB Tmax T7S unit delivers 1000 A, 3P protection with a front-terminal design and solid-state PR332/P LSI release, backed by IEC standards, CE conformity, and RoHS/REACH declarations. Additional CMRT and TSCA information supports supply-chain transparency, while RoHS status aligns with sustainable manufacturing goals. Whether you're upgrading existing gear or stocking new MCCB panels, this solution offers reliability, installation efficiency, and long-term cost savings. The design supports straightforward front-access installation, minimizing downtime during maintenance.
Product Information
Extended Description
1SDA062742R1 ABB: C.BREAKER TMAX T7S 1000 FIXED THREE-POLE WITH FRONT TERMINALS AND LEVER OPERATING MECHANISM AND SOLID-STATE RELEASE IN AC PR332/P-LSI R 1000
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Product Environmental Information Tmax T7 | Breakers - Packaging disposal information
EAN
8015644652913
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
210 mm
Product Net Height
268 mm
Product Net Depth / Length
154 mm
Product Net Weight
9.7 kg
Package Level 1 Units
1 piece
Package Level 1 Width
280 mm
Package Level 1 Height
350 mm
Package Level 1 Depth / Length
360 mm
Package Level 1 Gross Weight
11.2 kg
Package Level 1 EAN
8015644652913
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable For
T7
Suitable for Product Class
Moulded Case Circuit Breakers
Version
F
Electrical Durability
2000 cycle | 60 cycles per hour
Mechanical Durability
10000 cycle | 60 cycles per hour
Number of Poles
3P
Power Loss
at Rated Operating Conditions per Pole 30 W
Rated Current (In)
1000 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 85 kA | (230 V AC) 85 kA | (380 V AC) 50 kA | (400 V AC) 50 kA | (415 V AC) 50 kA | (440 V AC) 50 kA | (500 V AC) 40 kA | (690 V AC) 30 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 20 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 85 kA | (230 V AC) 85 kA | (380 V AC) 50 kA | (400 V AC) 50 kA | (415 V AC) 50 kA | (440 V AC) 50 kA | (500 V AC) 40 kA | (690 V AC) 30 kA
Rated Uninterrupted Current (Iu)
1000 A
Release
PR332/P LSI
Release Type
EL
Short-Circuit Performance Level
S
Standards
IEC
Sub-type
T7
Terminal Connection Type
Fixed Circuit-Breakers | Front
Data Sheet, Technical Information
1SDC210015D0201
Declaration of Conformity - CE
EC Declaration of Conformity Tmax T7
GL Certificate
1SDL000163R0055
Instructions and Manuals
1SDC210015D0201
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39121100
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature high current rating and fault current capacity. Business Impact with IN 1000 A and Icu up to 85 kA (at 220–230 V) enables rapid interruption of heavy fault currents, protecting feeders and transformers and reducing the risk of equipment damage. Application ideal for power distribution panels and MCCs in manufacturing plants and data centers. Feature front-terminal fixed three-pole design with lever-operating release. Business Impact simplifies wiring and maintenance with reliable, low-impedance connections and quick release operations. Application favors panel builders needing front access for wiring and fast replacement in space-constrained enclosures. PR332/P LSI release enhances tripping reliability in critical protection scenarios.Feature durability and efficiency. Business Impact electrical durability of 2000 cycles and mechanical durability of 10000 cycles reduce replacement costs and downtime, while 30 W per pole power loss minimizes heat and energy waste. Application suits continuous operation environments with demanding duty cycles in heavy industry.Feature environmental and compliance packaging. Business Impact RoHS, REACH, CMRT, TSCA, and EC declarations simplify regulatory compliance and supplier transparency. Application supports sustainable procurement, traceability, and audits for automotive, chemical, and process industries.Feature documentation and compatibility. Business Impact data sheets and certificates (1SDC210015D0201, CE declaration, GL certificate) streamline specification as-built processes. Application ensures seamless integration with Tmax T7 systems and front-terminal MCCB installations in new-build or retrofit projects.
Get a Quick Quote for a ABB 1SDA062742R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA062742R1?
Enquire Now
FAQs
Install the 3P fixed-front-terminal MCCB in a compatible distribution panel, ensuring the busbar width and mounting clearances match the unit's 210 mm width and 268 mm height. Use the lever-operated PR332/P LSI release for reliable, quick tripping and verify the wiring terminals are torqued per standard practice to maintain strong, vibration-resistant connections in demanding industrial environments.
Key ratings include a rated current of 1000 A, rated operational voltage of 690 V AC, rated insulation voltage of 1000 V, and a rated impulse withstand voltage of 8 kV. Short-circuit capacity Icu is up to 85 kA (at 220–230 V) and up to 50 kA at higher voltages, with Icw for 1 s up to 20 kA, delivered by a 3P configuration.
Yes. The 1SDA062742R1 is designed for Tmax T7 applications with a 3P fixed-front-terminal design and PR332/P LSI release, making it well-suited for high-current distribution panels, transformer protection, and other heavy-load scenarios in manufacturing and process environments.
The device is IEC-compliant and CE-declared (EC Declaration of Conformity) with RoHS, REACH, CMRT, and TSCA declarations. Documentation includes data sheets (1SDC210015D0201) and GL certificates, supporting regulatory audits and supply-chain transparency.
Electrical durability is rated at 2000 cycles and mechanical durability at 10000 cycles, reducing replacement and maintenance costs. The front-terminal design simplifies wiring and inspection, while 30 W per pole power loss minimizes heat in the panel, contributing to longer service intervals and lower operating costs.