ABB 1SDA062751R1 moulded case circuit breaker provides reliable overload protection for industrial switchgear in automation systems. Downtime and mis-tripping can erode productivity; this model delivers precise tripping under heavy fault conditions with front-terminal accessibility for quick inspections and maintenance. The device carries CE conformity, RoHS compliance, and CMRT documentation, aligning with contemporary regulatory and sustainability standards. Engineered for Tmax T7 applications, it supports a 4-pole configuration with PR332/P LSIG release, offering robust protection while simplifying panel integration and serviceability. For OEMs and electrical distributors, it delivers predictable performance, reduced field faults, and a clear path to compliant, efficient electrical protection in high-demand environments.
Product Information
Extended Description
1SDA062751R1 ABB: C.BREAKER TMAX T7S 1000 FIXED FOUR-POLE WITH FRONT TERMINALS AND LEVER OPERATING MECHANISM AND SOLID-STATE RELEASE IN AC PR332/P-LSIG R 1000
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Product Environmental Information Tmax T7 | Breakers - Packaging disposal information
EAN
8015644653002
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
280 mm
Product Net Height
268 mm
Product Net Depth / Length
154 mm
Product Net Weight
12.5 kg
Package Level 1 Units
1 piece
Package Level 1 Width
360 mm
Package Level 1 Height
350 mm
Package Level 1 Depth / Length
360 mm
Package Level 1 Gross Weight
14 kg
Package Level 1 EAN
8015644653002
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable For
T7
Suitable for Product Class
Moulded Case Circuit Breakers
Version
F
Electrical Durability
2000 cycle | 60 cycles per hour
Mechanical Durability
10000 cycle | 60 cycles per hour
Number of Poles
4P
Power Loss
at Rated Operating Conditions per Pole 30 W
Rated Current (In)
1000 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 85 kA | (230 V AC) 85 kA | (380 V AC) 50 kA | (400 V AC) 50 kA | (415 V AC) 50 kA | (440 V AC) 50 kA | (500 V AC) 40 kA | (690 V AC) 30 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 20 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 85 kA | (230 V AC) 85 kA | (380 V AC) 50 kA | (400 V AC) 50 kA | (415 V AC) 50 kA | (440 V AC) 50 kA | (500 V AC) 40 kA | (690 V AC) 30 kA
Rated Uninterrupted Current (Iu)
1000 A
Release
PR332/P LSIG
Release Type
EL
Short-Circuit Performance Level
S
Standards
IEC
Sub-type
T7
Terminal Connection Type
Fixed Circuit-Breakers | Front
Data Sheet, Technical Information
1SDC210015D0201
Declaration of Conformity - CE
EC Declaration of Conformity Tmax T7
GL Certificate
1SDL000163R0055
Instructions and Manuals
1SDC210015D0201
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39121100
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature → Business Impact → Application: High-current capability up to 1000 A reduces the need for intermediate devices, cutting total installed cost and improving system reliability in heavy-load panels. This directly translates to lower downtime and fewer component replacements in data centers, factory automation, and transformer protection schemes. Application: Tmax T7 4-pole installations in switchgear where front-terminal access speeds commissioning and simplifies retrofits. Feature → Front-terminal design enables straightforward wiring, faster assembly, and safer maintenance in cramped control cabinets. Benefit: reduces install time and resident risk for technicians in high-density panels. Application: New installations and modernization programs in process industries where space is limited and reliability is critical. Feature → PR332/P LSIG release provides deterministic tripping and coordination with upstream protection, delivering selective protection and enhanced fault isolation. Benefit: minimizes collateral damage and accelerates fault clearance in motor drives and packaging lines. Application: Panel builders seeking predictable SC protection curves and clear diagnostic signals on Tmax Tmax T7 family. Feature → 4P configuration supports symmetrical protection across phases, improving balance and fault handling in three-phase networks. Benefit: ensures consistent protection across all conductors, reducing unbalanced fault scenarios in heavy machinery. Application: Industrial robotics cells and stamping presses where uniform protection improves uptime. Feature → Rated Iu of 1000 A and Ics/Icu levels tailored to 690 V AC systems provide robust protection at high operating voltages. Benefit: compliant with IEC standards for medium-power distribution and transformer protection, lowering risk of arc flash events. Application: Primary protection in switchgear assemblies, transformers, and distribution panels. Feature → Integrated EPC (Environmental and Material) declarations including REACH, RoHS, CMRT, and TSCA alignment. Benefit: supports compliance catalogs, supplier audits, and ESG reporting. Application: Global procurement for multinational projects demanding verified material compliance.
Get a Quick Quote for a ABB 1SDA062751R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA062751R1?
Enquire Now
FAQs
Yes. The 1SDA062751R1 is designed as a four-pole fixed breaker with a PR332/P LSIG release for Tmax T7 configurations. It fits standard MCCBs in low-voltage switchgear and supports front-terminal wiring for straightforward retrofits. Always verify busbar spacing and terminal torque specifications per the installation manual to ensure seamless compatibility.
Key specs include rated current of 1000 A, rated operational voltage of 690 V AC, and rated insulation voltage of 1000 V. The device provides Ics/Icu ratings that align with high-short-circuit environments and a 4P configuration for full-phase protection. Ensure your panel design accommodates 280 mm width and 268 mm height per the product data for proper mounting clearance.
Absolutely. Its Tmax T7 lineage and high breaking capacity make it suitable for transformer and generator protection. The four-pole fixed design ensures balanced protection across all phases, and the LSIG release supports reliable operation under fault conditions. Confirm coordination with upstream relays and matching Icu/Ics values for the intended voltage level.
The device ships with a CE Declaration of Conformity and RoHS information, plus CMRT for conflict minerals management. It also references ETIM and IEC standards for interoperability in industrial systems. These certifications streamline compliance audits, supplier qualification, and ESG reporting in global supply chains.
With a mechanical durability of 10,000 cycles and electrical durability around 2,000 cycles at rated conditions, the unit supports long service intervals and predictable maintenance windows. Front-terminal accessibility reduces service time, while reliable fault clearance minimizes downtime. The upfront specification alignment with RoHS and CMRT further reduces regulatory risk and lifecycle costs.