ABB 1SDA062756R1 Moulded Case Circuit Breaker - IEC
Part Number: 1SDA062756R1
Quick Summary
ABB 1SDA062756R1 Moulded Case Circuit Breaker protects industrial electrical panels by interrupting fault currents during abnormal events, enabling rapid isolation of faulty circuits and minimizing risk to personnel. When short circuits or overloads occur, unplanned downtime and equipment damage threaten production schedules, forcing costly emergency responses and extended outages. Certified to IEC standards with CE marking, RoHS and REACH declarations, plus CMRT and SCIP traceability, this device aligns with global regulatory requirements and responsible sourcing practices. Designed for front-terminal, three-pole installations in Tmax T7 configurations, it helps reduce maintenance costs, improve uptime, simplify integration with modern power distribution architectures, and support scalable protection upgrades.
Product Information
Extended Description
1SDA062756R1 ABB: C.BREAKER TMAX T7S 1000 FIXED THREE-POLE WITH FRONT TERMINALS AND STORED ENERGY OPERATING MECHANISM AND SOLID-STATE RELEASE IN AC PR331/P-LSIG R 1000
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
SCIP
36207852-40b2-4b2a-82a0-8cc8819b47eb Italy (IT)
Simplified SCIP
da888188-aa7c-4e05-881b-0f14748d34ac Germany (DE) | 97c8dbfc-ad47-437a-9241-eba351198865 Netherlands (NL) | 0e75a068-e10b-4d02-9871-75043970bdc8 Norway (NO) | f2e98569-466b-4d54-827b-0b254b8cfaad Estonia (EE) | ae82663f-6238-4dbd-8b50-5291179f2b12 Greece (GR) | ac0825e6-57d2-440e-81a2-5fd426fbf859 Portugal (PT) | a08e9150-d49e-4622-bce0-e0e416319163 Bulgaria (BG) | e25b9ded-2e21-4c83-a6b7-b4b3439339db Sweden (SE) | df4b9b42-fcc3-46ff-a92f-0a92674ce33b Poland (PL) | 2e08dfd1-1b33-401d-a2ed-2d91b1fac1c0 France (FR) | ff2d6c39-6531-4aba-b56f-6a8005fead40 Sweden (SE) | abab3754-0bfc-4256-8f2c-e21c3d13e513 Germany (DE) | 93cb176b-7ea4-4411-a721-c0d75a85396a Germany (DE) | 657fcc0b-4a4f-4703-918d-174286e0b0af France (FR) | 4ae3d817-382d-4ff3-9c38-d00294b4c2ee Netherlands (NL) | 70e7a0a1-9380-4373-9ec6-2012f4b20dab Spain (ES) | 5be121e3-b5a4-4c8c-97a5-94b38ded35c5 Netherlands (NL) | 8bce9cb5-bd28-4699-bd8f-b3039f5427c1 Germany (DE) | 607031b8-3da4-4145-9826-e978db00169b Denmark (DK) | 199ba009-1f35-4b56-8839-56272efc9a49 Germany (DE) | 35ef2393-a471-49d5-a219-d6a0f5785da0 Czech Republic (CZ) | ad997b6b-0f37-497f-8f10-98f5700075c8 Poland (PL) | edf24bbe-cff5-461b-aba3-e97f96d24d16 Croatia (HR) | ba7fa65f-bd9c-4134-8632-de428013957b Netherlands (NL) | 2e163e2b-5eb1-4638-b9d2-a2c009f785c5 Netherlands (NL) | 9d5cafad-95b6-4320-91ab-412c97bbef7a Finland (FI) | 75b8a0de-0eac-4f3f-af72-063316d21525 Poland (PL)
Environmental Information
Product Environmental Information Tmax T7 | Breakers - Packaging disposal information
Order Code US and Canada
T7MSFP3AE000000XX
EAN
8015644653057
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
210 mm
Product Net Height
268 mm
Product Net Depth / Length
178 mm
Product Net Weight
11 kg
Package Level 1 Units
1 piece
Package Level 1 Width
280 mm
Package Level 1 Height
350 mm
Package Level 1 Depth / Length
360 mm
Package Level 1 Gross Weight
12.5 kg
Package Level 1 EAN
8015644653057
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable For
T7M
Suitable for Product Class
Moulded Case Circuit Breakers
Version
F
Electrical Durability
2000 cycle | 60 cycles per hour
Mechanical Durability
10000 cycle | 60 cycles per hour
Number of Poles
3P
Power Loss
at Rated Operating Conditions per Pole 30 W
Rated Current (In)
1000 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 85 kA | (230 V AC) 85 kA | (380 V AC) 50 kA | (400 V AC) 50 kA | (415 V AC) 50 kA | (440 V AC) 50 kA | (500 V AC) 40 kA | (690 V AC) 30 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 20 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 85 kA | (230 V AC) 85 kA | (380 V AC) 50 kA | (400 V AC) 50 kA | (415 V AC) 50 kA | (440 V AC) 50 kA | (500 V AC) 40 kA | (690 V AC) 30 kA
Rated Uninterrupted Current (Iu)
1000 A
Release
PR331/P LSIG
Release Type
EL
Short-Circuit Performance Level
S
Standards
IEC
Sub-type
T7
Terminal Connection Type
Fixed Circuit-Breakers | Front
Data Sheet, Technical Information
1SDC210015D0201
Declaration of Conformity - CE
EC Declaration of Conformity Tmax T7
GL Certificate
1SDL000163R0055
Instructions and Manuals
1SDC210015D0201
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature: Front-terminal fixed 3P design with LSIG release provides safe, accessible wiring and reliable tripping. Business Impact: Reduces field wiring time and maintenance effort, lowering installed costs and downtime. Application: Ideal for panel feeders and MCCs in 690 V AC networks. Feature: PR331/P LSIG release delivers stored-energy operation for fast and predictable interruption. Business Impact: Improves personnel safety and protects downstream equipment from arc flash risk, enabling faster fault clearance. Application: Transformer and motor feeder protections in demanding industrial environments. Feature: High breaking capacity with Ics/Icu ratings across voltages (up to 85 kA at low voltages; 30 kA at 690 V). Business Impact: Maintains system integrity during severe faults, reducing unplanned outages and equipment damage. Application: Low-, medium-, and high-power distribution panels and switchgear. Feature: Rated current of 1000 A and insulation voltage of 1000 V, with rated operational voltage of 690 V AC. Business Impact: Supports large-diameter feeders and heavy motor loads with reliable discrimination. Application: Main feeders and critical load centers in industrial plants. Feature: Electrical durability of 2000 cycles and mechanical durability of 10000 cycles (60 cycles/hour). Business Impact: Extends service life, lowers replacement costs, and improves total cost of ownership. Application: High-cycle protection scenarios in continuous-operation facilities. Feature: Front-terminal, fixed-circuit-breaker design with compact footprint and 210 mm width × 268 mm height × 178 mm depth. Business Impact: Simplifies retrofit and upgrade projects, reduces installation time, and minimizes panel remodels. Application: Retrofit projects and new builds in data centers, process lines, and power rooms. Feature: Compliance and environmental declarations including RoHS, REACH, CMRT, SCIP, CE, and IEC. Business Impact: Eases regulatory approvals, supply-chain risk management, and sustainability reporting. Application: Global deployments with strict regulatory requirements and corporate governance standards.
Get a Quick Quote for a ABB 1SDA062756R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA062756R1?
Enquire Now
FAQs
For effective deployment, use the fixed front-terminal design in three-pole configurations and ensure panel cutouts accommodate a 210 mm width, 268 mm height, and 178 mm depth unit weighing about 11 kg. Verify compatibility with 690 V AC systems, ensure proper wiring torque, and align with ETIM/IEC references for Tmax T7 integrations. Consider space for service access to the LSIG release and front-terminal terminal covers to simplify future maintenance.
Key ratings include a rated current of 1000 A, rated operational voltage of 690 V AC, rated insulation voltage of 1000 V, and an impulse withstand voltage (Uimp) of 8 kV. The device provides Ics and Icu up to 85 kA at low voltages (e.g., 220–230 V) and 30–50 kA at higher voltages up to 690 V, with an Icw of 20 kA for 1 s. It is a 3P fixed-front design with PR331/P LSIG release for reliable protection.
Yes. It is a SACE Tmax T series MCCB configured as a 3P front-terminal device with LSIG release, designed to integrate with Tmax T7 protection schemes. Its mechanical and electrical durability supports high-cycle protection in transformer and motor feeder applications, while IEC compliance ensures alignment with Tmax T7 ecosystem requirements and industry standards.
The device carries IEC standards alignment, CE marking, RoHS and REACH declarations, plus CMRT and SCIP reporting. These certifications indicate compliance with European regulatory and environmental requirements, responsible material sourcing, and traceability for conflict minerals. This simplifies procurement across global operations and supports sustainability and governance goals.
Durability metrics show electrical durability of 2000 cycles and mechanical durability of 10000 cycles at typical usage. The front-terminal design reduces wiring and retrofit time, while high Icu/Ics ratings minimize fault-related downtime. Together, these factors translate to longer component life, lower spare-part expenditure, faster maintenance turnarounds, and improved overall equipment effectiveness (OEE) in regulated, high-demand industrial environments.