ABB 1SDA062758R1 Moulded Case Circuit Breaker - PR332/P LSI
Part Number: 1SDA062758R1
Quick Summary
ABB 1SDA062758R1 Moulded Case Circuit Breaker provides rugged overload and short-circuit protection for 690 V distribution panels. Engineers often struggle with unreliable trips and downtime when protection devices don’t coordinate with heavy loads; this unit delivers fast, reliable trips with a stored-energy mechanism and convenient front-terminal access for maintenance. CE conformity (EC Declaration of Conformity for Tmax T7), RoHS compliance under EU Directive 2011/65/EU, and TSCA declarations help meet regulatory and sustainability requirements. By combining a 1000 A rating with a fixed 3P configuration and a compact footprint, it supports scalable protection for motor control centers, transformers and switchgear while reducing installation time and total cost of ownership.
Product Information
Extended Description
1SDA062758R1 ABB: C.BREAKER TMAX T7S 1000 FIXED THREE-POLE WITH FRONT TERMINALS AND STORED ENERGY OPERATING MECHANISM AND SOLID-STATE RELEASE IN AC PR332/P-LSI R 1000
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Product Environmental Information Tmax T7 | Breakers - Packaging disposal information
Order Code US and Canada
T7MSFP3AR000000XX
EAN
8015644653071
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
210 mm
Product Net Height
268 mm
Product Net Depth / Length
178 mm
Product Net Weight
11 kg
Package Level 1 Units
1 piece
Package Level 1 Width
280 mm
Package Level 1 Height
350 mm
Package Level 1 Depth / Length
360 mm
Package Level 1 Gross Weight
12.5 kg
Package Level 1 EAN
8015644653071
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable For
T7M
Suitable for Product Class
Moulded Case Circuit Breakers
Version
F
Electrical Durability
2000 cycle | 60 cycles per hour
Mechanical Durability
10000 cycle | 60 cycles per hour
Number of Poles
3P
Power Loss
at Rated Operating Conditions per Pole 30 W
Rated Current (In)
1000 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 85 kA | (230 V AC) 85 kA | (380 V AC) 50 kA | (400 V AC) 50 kA | (415 V AC) 50 kA | (440 V AC) 50 kA | (500 V AC) 40 kA | (690 V AC) 30 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 20 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 85 kA | (230 V AC) 85 kA | (380 V AC) 50 kA | (400 V AC) 50 kA | (415 V AC) 50 kA | (440 V AC) 50 kA | (500 V AC) 40 kA | (690 V AC) 30 kA
Rated Uninterrupted Current (Iu)
1000 A
Release
PR332/P LSI
Release Type
EL
Short-Circuit Performance Level
S
Standards
IEC
Sub-type
T7
Terminal Connection Type
Fixed Circuit-Breakers | Front
Data Sheet, Technical Information
1SDC210015D0201
Declaration of Conformity - CE
EC Declaration of Conformity Tmax T7
GL Certificate
1SDL000163R0055
Instructions and Manuals
1SDC210015D0201
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Three-pole design with front terminals and a stored-energy operating mechanism delivers precise, repeatable tripping under high fault currents, reducing panel downtime and maintenance cycles. Business impact: improved line reliability and faster service restoration in critical automation cells; suitable for MCCs and distribution boards in heavy industry. Application: motor control centers, transformers protection and switchgear assemblies at up to 690 V AC. Long-tail keywords integrated: three-pole molded case circuit breaker, front-terminal MCC protection, Tmax T7S family compatibility. Release PR332/P LSI provides selective tripping and reliable coordination with upstream protection, minimizing undesired outages in complex power systems. Application: transformer and generator protection in energy-heavy facilities. Electrical durability of 2000 cycles and mechanical durability of 10000 cycles support frequent switching in high-demand environments, reducing total cost of ownership over the equipment lifecycle. Front-terminal fixed connection simplifies wiring, improves reliability, and accelerates commissioning in new builds or retrofits. With RoHS and REACH compliance, the product aligns with sustainability goals while meeting procurement standards. Compact footprint and robust packaging facilitate easy installation in dense panel layouts without compromising safety or accessibility. Dimensions and weight (210 mm x 268 mm x 178 mm; 11 kg) enable predictable space planning and standardized mounting across multiple panels.
Get a Quick Quote for a ABB 1SDA062758R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA062758R1?
Enquire Now
FAQs
This is a fixed, front-terminal 3P device designed for panel boards and MCC assemblies. With a net width of 210 mm, height of 268 mm, and depth of 178 mm, it weighs 11 kg and offers straightforward front-access wiring. Ensure proper clearance, ventilation, and mounting in standard enclosures to maintain optimal heat dissipation and ease of maintenance.
Nominal current In is 1000 A, rated operational voltage is 690 V AC, rated insulation voltage 1000 V, and rated impulse withstand voltage 8 kV. It provides a short-circuit breaking capacity up to 85 kA at common distribution voltages, with a 3P configuration and PR332/P LSI release for selective protection in heavy-duty panels.
Yes. The 3P 1000 A unit with PR332/P LSI release is well-suited for transformer and generator protection within Tmax T7 family installations. Its front-terminal design and high Icu rating support reliable selective protection and coordination with upstream devices, making it a solid choice for critical power distribution in industrial settings.
The breaker carries CE conformity (EC Declaration of Conformity for Tmax T7), RoHS compliance under EU directive 2011/65/EU with amendment 2015/863, TSCA declarations, and a GL certificate. CMRT data is available for supply-chain transparency. These certifications support regulatory adherence and responsible sourcing for OEMs and contractors.
Electrical durability is rated at 2000 cycles and mechanical durability at 10000 cycles at 60 cycles/hour, supporting long service life with reduced maintenance. The front-terminal wiring simplifies commissioning, lowering installation time. Together with high reliability, this translates to reduced downtime, better equipment availability, and favorable ROI in high-availability automation environments.