ABB 1SDA062759R1 Moulded Case Circuit Breaker - IEC Tmax T7
Part Number: 1SDA062759R1
Quick Summary
Moulded Case Circuit Breaker ABB 1SDA062759R1 provides reliable overcurrent protection for industrial electrical panels. Engineers often struggle with space, complex wiring, and retrofit downtime when upgrading protection in existing switchboards. This unit complies with IEC standards and CE conformity, and carries RoHS and CMRT declarations to ease global sourcing and regulatory risk. Designed for Tmax T applications with 3P front-terminal installation, it supports up to 1000 A continuous service and high short-circuit ratings, delivering robust performance in manufacturing, data centers, and utility infrastructure. Beyond protection, it enables scalable, upgrade-friendly panels and reduces downtime with a front-terminal, SEOM-based release. Together with IEC CE RoHS CMRT, it helps procurement meet compliance while simplifying maintenance.
Product Information
Extended Description
1SDA062759R1 ABB: C.BREAKER TMAX T7S 1000 FIXED THREE-POLE WITH FRONT TERMINALS AND STORED ENERGY OPERATING MECHANISM AND SOLID-STATE RELEASE IN AC PR332/P-LSIG R 1000
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Product Environmental Information Tmax T7 | Breakers - Packaging disposal information
Order Code US and Canada
T7MSFP3AS000000XX
EAN
8015644653088
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
210 mm
Product Net Height
268 mm
Product Net Depth / Length
178 mm
Product Net Weight
11 kg
Package Level 1 Units
1 piece
Package Level 1 Width
280 mm
Package Level 1 Height
350 mm
Package Level 1 Depth / Length
360 mm
Package Level 1 Gross Weight
12.5 kg
Package Level 1 EAN
8015644653088
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable For
T7M
Suitable for Product Class
Moulded Case Circuit Breakers
Version
F
Electrical Durability
2000 cycle | 60 cycles per hour
Mechanical Durability
10000 cycle | 60 cycles per hour
Number of Poles
3P
Power Loss
at Rated Operating Conditions per Pole 30 W
Rated Current (In)
1000 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 85 kA | (230 V AC) 85 kA | (380 V AC) 50 kA | (400 V AC) 50 kA | (415 V AC) 50 kA | (440 V AC) 50 kA | (500 V AC) 40 kA | (690 V AC) 30 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 20 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 85 kA | (230 V AC) 85 kA | (380 V AC) 50 kA | (400 V AC) 50 kA | (415 V AC) 50 kA | (440 V AC) 50 kA | (500 V AC) 40 kA | (690 V AC) 30 kA
Rated Uninterrupted Current (Iu)
1000 A
Release
PR332/P LSIG
Release Type
EL
Short-Circuit Performance Level
S
Standards
IEC
Sub-type
T7
Terminal Connection Type
Fixed Circuit-Breakers | Front
Data Sheet, Technical Information
1SDC210015D0201
Declaration of Conformity - CE
EC Declaration of Conformity Tmax T7
GL Certificate
1SDL000163R0055
Instructions and Manuals
1SDC210015D0201
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature: 3P fixed circuit-breaker with front terminals and stored-energy operating mechanism (SEOM) and PR332/P LSIG release. Business Impact: Ensures fast, reliable tripping and straightforward maintenance during panel upgrades and routine testing. Application: Panel modernization in manufacturing lines and process control rooms. Feature: Rated current of 1000 A with high short-circuit capability. Business Impact: Supports large motor feeders and high-load distributions with minimized fault risk and limited downtime. Application: Heavy industry, plant distribution, and data-center power rails. Feature: Rated operational voltage of 690 V AC and insulation voltage of 1000 V. Business Impact: Safe operation across diverse industrial networks with tolerance for peak transients. Application: Global installations, transformer substations, and DC link protection interfaces. Feature: Ics up to 85 kA and Icw 20 kA for 1 s. Business Impact: Enhanced fault-handling capability reduces equipment damage and downstream outages. Application: Equipment aisles and switchgear compartments with high fault currents. Feature: RoHS, CMRT, TSCA declarations and CE conformity. Business Impact: Streamlines global procurement, lowers regulatory risk, and supports sustainable sourcing. Application: multinational facilities requiring strict material and compliance visibility. Feature: Front-terminal design and Tmax T family compatibility. Business Impact: Faster wiring, easier retrofits, and compatibility with existing front-access installations. Application: Retrofitting legacy MCCB layouts in control panels and switchboards.
Get a Quick Quote for a ABB 1SDA062759R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA062759R1?
Enquire Now
FAQs
For proper installation, ensure sufficient frontal clearance for wiring and operation of the stored-energy mechanism, torque specs on terminal connections are followed, and mounting aligns with panel rails. Front-terminal MCCBs simplify wiring runs in cabinets with limited rear space and facilitate faster retrofit projects with minimal panel downtime.
Key specs include a rated current of 1000 A, rated operational voltage of 690 V AC, rated insulation voltage of 1000 V, and a high short-circuit rating (Ics up to 85 kA). The device also offers a 8 kV impulse withstand and 20 kA short-time withstand for 1 s, enabling robust protection for motors and transformers against faults.
Yes. The unit is part of the SACE Tmax T family and is suitable for Tmax T7 configurations, including 3P front-terminal installations. It supports PR332/P LSIG release and integrates with T7M protection schemes, offering a streamlined path for upgrades from older MCCB generations in power distribution panels.
The device carries CE conformity documentation, RoHS compliance, CMRT (Conflict Minerals Reporting Template), and TSCA declarations, supporting global sourcing and regulatory alignment. These certifications help procurement satisfy environmental, health, and safety standards in multiple regions and simplify supplier qualification.
Maintenance benefits come from the SEOM-based release and front-terminal wiring, which reduce maintenance time and contact torque variability. The high Ics capability minimizes downstream equipment damage, and the 30 W per pole power loss is managed within expected operating energy budgets, contributing to lower total cost of ownership in high-demand industrial networks.