ABB 1SDA062761R1 Moulded Case Circuit Breaker - IEC
Part Number: 1SDA062761R1
Quick Summary
Moulded Case Circuit Breaker protects electrical circuits in industrial switchgear and power distribution. Engineers often struggle with unreliable protection devices that fail under peak load, causing downtime. This ABB solution aligns with CE conformity, IEC standards, and RoHS declarations to ensure dependable performance, extended service life, and simplified compliance. With Tmax T compatibility and front-terminal installation, it delivers safer operation and reduced wiring time, supporting a more efficient and resilient power distribution architecture.
Product Information
Extended Description
1SDA062761R1 ABB: C.BREAKER TMAX T7S 1000 FIXED FOUR-POLE WITH FRONT TERMINALS AND STORED ENERGY OPERATING MECHANISM AND SOLID-STATE RELEASE IN AC PR231/P-I R 1000
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Product Environmental Information Tmax T7 | Breakers - Packaging disposal information
EAN
8015644653101
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
280 mm
Product Net Height
268 mm
Product Net Depth / Length
178 mm
Product Net Weight
14 kg
Package Level 1 Units
1 piece
Package Level 1 Width
360 mm
Package Level 1 Height
350 mm
Package Level 1 Depth / Length
360 mm
Package Level 1 Gross Weight
15.5 kg
Package Level 1 EAN
8015644653101
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable For
T7M
Suitable for Product Class
Moulded Case Circuit Breakers
Version
F
Electrical Durability
2000 cycle | 60 cycles per hour
Mechanical Durability
10000 cycle | 60 cycles per hour
Number of Poles
4P
Power Loss
at Rated Operating Conditions per Pole 30 W
Rated Current (In)
1000 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 85 kA | (230 V AC) 85 kA | (380 V AC) 50 kA | (400 V AC) 50 kA | (415 V AC) 50 kA | (440 V AC) 50 kA | (500 V AC) 40 kA | (690 V AC) 30 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 20 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 85 kA | (230 V AC) 85 kA | (380 V AC) 50 kA | (400 V AC) 50 kA | (415 V AC) 50 kA | (440 V AC) 50 kA | (500 V AC) 40 kA | (690 V AC) 30 kA
Rated Uninterrupted Current (Iu)
1000 A
Release
PR231/P-I
Release Type
EL
Short-Circuit Performance Level
S
Standards
IEC
Sub-type
T7
Terminal Connection Type
Fixed Circuit-Breakers | Front
Data Sheet, Technical Information
1SDC210015D0201
Declaration of Conformity - CE
EC Declaration of Conformity Tmax T7
GL Certificate
1SDL000163R0055
Instructions and Manuals
1SDC210015D0201
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
The unit delivers high-current protection with a 4P configuration and front-terminal access, enabling dense MCC layouts and faster wiring during panel assembly, improving overall installation efficiency and reducing labor costs. This translates to better reliability in industrial switchgear and power distribution systems where space is at a premium. The stored-energy operating mechanism (SEO) and PR231/P-I release reduce maintenance windows and improve operator safety during testing or replacement, supporting higher uptime in critical production lines. With a rated current of 1000 A and a 690 V AC operating voltage, it supports transformer protection and large motor control centers while delivering precise tripping characteristics and rapid fault isolation. The device offers a robust short-circuit profile (Ics up to 85 kA, Icw 20 kA for 1 s, Icu up to 85 kA at various voltages), which helps containment strategies and protects high-value assets. Durability figures—mechanical 10000 cycles and electrical 2000 cycles—translate to longer service life and lower spare parts usage in demanding environments. RoHS, REACH, CMRT, and CE declarations simplify regulatory compliance and procurement, while ETIM alignment ensures seamless cataloging and compatibility with Tmax Tmax T components. Front-terminal design and a compact footprint (280 × 268 × 178 mm; 14 kg) enable easy retrofits and scalable system upgrade paths for growing industrial facilities.
Get a Quick Quote for a ABB 1SDA062761R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA062761R1?
Enquire Now
FAQs
The 1SDA062761R1 uses fixed front terminals in a four-pole layout designed for MCC integration. Plan for a depth of 178 mm and width of 280 mm, with a unit weight of 14 kg. The stored-energy operating mechanism and PR231/P-I release streamline wiring, testing, and safe operation during maintenance.
Key specs include rated current of 1000 A, four poles, Ui 1000 V, rated operational voltage 690 V AC, Uimp 8 kV, Ics up to 85 kA, Icw 20 kA for 1 s, and Iu 1000 A. These figures support reliable protection in transformer and generator circuits and fast isolation during fault events.
Yes. Designed for Tmax T applications, the 1SDA062761R1 is ideal for transformer protection in switchgear and distribution boards. Its 4P configuration, high Ics/Icu ratings, and front-terminal installation enable robust fault isolation, minimizing downtime and protecting transformers and other high-value assets in industrial facilities.
The breaker complies with CE conformity and IEC standards, with EC Declaration of Conformity, RoHS compliance, REACH, and CMRT disclosures. Additional documentation such as GL certification and product manuals further support traceability and regulatory audits, helping with faster approvals and standardized procurement processes in engineering projects.
Durability is strong: mechanical 10000 cycles and electrical 2000 cycles reduce maintenance needs. Stored-energy operation accelerates testing and replacements, while high short-circuit ratings improve protection reliability and minimize downtime. Standardization with Tmax T components lowers spare parts variety and accelerates repair, delivering tangible cost savings over time.