ABB 1SDA062762R1 Moulded Case Circuit Breaker - 8 kV
Part Number: 1SDA062762R1
Quick Summary
ABB 1SDA062762R1 Moulded Case Circuit Breaker is designed to protect power distributions in industrial environments while simplifying panel integration. This device delivers reliable overcurrent and short-circuit protection with a fixed four-pole design and front-terminal access, easing wiring in compact switchgear. In today’s manufacturing settings, teams face rising energy costs and stricter compliance requirements; this MCCB supports fast, repeatable tripping and reduced maintenance through a stored-energy mechanism and robust PR231/P-LS/I release. CE conformity, RoHS compliance, and SCIP registration help ensure global deployability, while GL certification reinforces quality. For engineers and procurement professionals, the solution offers predictable performance, seamless compatibility with ABB Tmax T family components, and a clear path to compliant, safe protection across panels and machines.
Product Information
Extended Description
1SDA062762R1 ABB: C.BREAKER TMAX T7S 1000 FIXED FOUR-POLE WITH FRONT TERMINALS AND STORED ENERGY OPERATING MECHANISM AND SOLID-STATE RELEASE IN AC PR231/P-LS/I R 1000
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
SCIP
857c5f03-41ae-4a5d-b9cd-9e3e946d3cac Italy (IT)
Simplified SCIP
547764d1-7dfd-4775-bcd5-83988ccf2b10 Hungary (HU) | 9b4a7b3c-69c5-4e5d-8d6c-e4c8213162c8 Poland (PL) | 39944c7f-9b96-4fa7-a952-f5837316724e Germany (DE) | 967a531e-52e6-49c6-8ec1-132ddb3ff06f Croatia (HR) | 220ab326-c35f-4778-90a1-3a2fc46f529b Denmark (DK) | 732691ca-d5c0-448e-a199-b4298cd8f217 Sweden (SE) | 2dceec17-0ba5-411f-997c-35259c9d76a9 Germany (DE) | 69b6f5b8-cceb-4bb7-8752-9e8ca35f428c Germany (DE) | 42643ccb-61de-4c34-8676-a3ee1a7bd8ec Czech Republic (CZ) | a4893ee9-9111-4a3b-b194-17d171084015 France (FR) | 0c028dea-e517-4654-a5d4-8c128cb19818 Hungary (HU) | a02541c4-93d8-4d05-88cb-5c4699ca248e Belgium (BE) | 29185527-353a-4158-9713-4681d1c8f770 Spain (ES) | 653b0502-1033-474d-a704-fe023c6de648 Portugal (PT) | e8f30c31-74a6-45bf-92a5-9c123e73512c Poland (PL) | ad1deb24-1639-45f4-b79c-c8a685584128 Bulgaria (BG) | 2be6004c-5a48-4285-971f-fdaec50428b9 Poland (PL) | 638fb7ee-f4b2-4e53-b5c8-904391d42752 Germany (DE) | 0f1c5d26-2c23-4ff9-9e19-6605dc64eefb Sweden (SE) | 3dd4e41e-dfa8-4044-a9b6-398c79323b92 Netherlands (NL) | fd4ff008-fb01-4cfd-81cc-6a801393ec14 Norway (NO) | 4ff85168-7e82-48a5-9fcb-381ffdfadce4 France (FR) | dd8a40cb-9e9b-4466-b198-dcb1c4f0e8b2 Germany (DE) | fef1a2d4-fbbf-40bf-a6fc-bd4b6bf97bea Greece (GR) | 5fbfd89e-40d1-4a86-9b05-b0cb152f83b9 Belgium (BE) | f88e07a6-2fb2-4749-8363-70f9a47ad640 Estonia (EE) | 26ce99a0-c2c2-459e-a1f6-ba7374cb83d5 Finland (FI)
Environmental Information
Product Environmental Information Tmax T7 | Breakers - Packaging disposal information
EAN
8015644653118
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
280 mm
Product Net Height
268 mm
Product Net Depth / Length
178 mm
Product Net Weight
14 kg
Package Level 1 Units
1 piece
Package Level 1 Width
360 mm
Package Level 1 Height
350 mm
Package Level 1 Depth / Length
360 mm
Package Level 1 Gross Weight
15.5 kg
Package Level 1 EAN
8015644653118
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable For
T7M
Suitable for Product Class
Moulded Case Circuit Breakers
Version
F
Electrical Durability
2000 cycle | 60 cycles per hour
Mechanical Durability
10000 cycle | 60 cycles per hour
Number of Poles
4P
Power Loss
at Rated Operating Conditions per Pole 30 W
Rated Current (In)
1000 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 85 kA | (230 V AC) 85 kA | (380 V AC) 50 kA | (400 V AC) 50 kA | (415 V AC) 50 kA | (440 V AC) 50 kA | (500 V AC) 40 kA | (690 V AC) 30 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 20 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 85 kA | (230 V AC) 85 kA | (380 V AC) 50 kA | (400 V AC) 50 kA | (415 V AC) 50 kA | (440 V AC) 50 kA | (500 V AC) 40 kA | (690 V AC) 30 kA
Rated Uninterrupted Current (Iu)
1000 A
Release
PR231/P-LS/I
Release Type
EL
Short-Circuit Performance Level
S
Standards
IEC
Sub-type
T7
Terminal Connection Type
Fixed Circuit-Breakers | Front
Data Sheet, Technical Information
1SDC210015D0201
Declaration of Conformity - CE
EC Declaration of Conformity Tmax T7
GL Certificate
1SDL000163R0055
Instructions and Manuals
1SDC210015D0201
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature → Business Impact → Application: The 4P fixed-front-terminal design supports reliable, repeatable protection with straightforward wiring, reducing installation time and panel footprint in large distribution boards used for motors and feeders. This translates to lower labor costs and higher system availability in manufacturing lines. Feature → Application: Rated current of 1000 A and a 690 V AC operating voltage enable protection for high-demand motor loads and critical feeders, improving uptime in process industries. Feature → Application: Ics up to 85 kA and Icu up to 85 kA (voltage dependent) provide robust fault clearance for heavy fault currents, minimizing damage to transformers and switchgear during faults. Feature → Application: Release PR231/P-LS/I with EL type ensures fast, reliable disconnection, reducing arc energy and improving personnel safety during maintenance. Feature → Application: 8 kV impulse withstand voltage (Uimp) and 1000 V insulation voltage (Ui) support safe operation in medium-voltage panels, widening the range of compliant installations. Feature → Application: Front-terminal construction and a stored-energy mechanism help streamline installation and maintenance, enabling quick replacements and minimizing downtime when servicing MCCBs in field replaceable panels. Feature → Application: Compliance with RoHS, REACH, and SCIP demonstrates sustainable procurement and risk mitigation in global supply chains, aiding audits and regulatory reporting. Feature → Application: Mechanical durability (10000 cycles) paired with electrical durability (2000 cycles at 60 cycles/hour) provides predictable lifecycle performance for continuous production environments, reducing lifecycle costs and maintenance intervals.
Get a Quick Quote for a ABB 1SDA062762R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA062762R1?
Enquire Now
FAQs
Install the MCCB in a panel that provides front-access wiring and sufficient clearance for 280 mm width, 268 mm height, and 178 mm depth. Use proper torque on terminal connections, align the four poles for even busbar distribution, and verify the stored-energy mechanism engages correctly before power-up. The front-terminal arrangement simplifies wiring in tight switchgear enclosures and reduces wiring errors during assembly.
Key ratings includeRated Current 1000 A, Rated Operational Voltage 690 V AC, Rated Insulation Voltage 1000 V, and Rated Impulse Withstand Voltage 8 kV. Short-circuit performance is rated with Ics up to 85 kA and Icu up to 85 kA (voltage-dependent). These values enable precise protection coordination for large motor feeders and high-current circuits while maintaining safe, code-compliant operation.
Yes. With 4P configuration, 1000 A rating, robust Ics/Icu figures, and a PR231/P-LS/I release, the device is well-suited for motor protection in high-current distribution systems. Front-terminal wiring facilitates rapid installation, while the Tmax T7 family compatibility supports seamless integration with existing ABB protection schemes.
This MCCB comes with CE conformity (EC Declaration of Conformity), RoHS compliance, REACH declarations, CMRT for conflict minerals, SCIP registration, and GL certification. These certifications support regulatory alignment, sustainability reporting, and quality assurance across global installations in manufacturing, energy, and infrastructure projects.
Electrical durability is rated at 2000 cycles and mechanical durability at 10000 cycles (60 cycles/hour). Plan periodic functional tests, inspect the stored-energy mechanism, verify actuator integrity, and replace worn components before performance drift occurs. Front-terminal access simplifies maintenance and reduces downtime during routine inspections in high-demand production environments.