ABB 1SDA062765R1 Moulded Case Circuit Breaker - 85 kA
Part Number: 1SDA062765R1
Quick Summary
ABB 1SDA062765R1 Moulded Case Circuit Breaker protects critical industrial power circuits in data centers and automation panels. Engineers often wrestle with front-terminal accessibility and reliable tripping under high fault currents. This device meets IEC standards and carries RoHS and REACH declarations, along with CMRT and TSCA disclosures for global procurement. Designed for Tmax T series in 690 V systems, it helps reduce downtime and simplifies regulatory documentation, while delivering robust protection and traceability for panel builders and plant owners. Its 4-pole, front-terminal configuration supports straightforward installation and reduces wiring errors in crowded switchgear. With 1000 A rated current and 8 kV insulation, it withstands the demanding environments typical of industrial automation facilities.
Product Information
Extended Description
1SDA062765R1 ABB: C.BREAKER TMAX T7S 1000 FIXED FOUR-POLE WITH FRONT TERMINALS AND STORED ENERGY OPERATING MECHANISM AND SOLID-STATE RELEASE IN AC PR332/P-LI R 1000
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Product Environmental Information Tmax T7 | Breakers - Packaging disposal information
Order Code US and Canada
T7MSFP4AP000000XX
EAN
8015644653149
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
280 mm
Product Net Height
268 mm
Product Net Depth / Length
178 mm
Product Net Weight
14 kg
Package Level 1 Units
1 piece
Package Level 1 Width
360 mm
Package Level 1 Height
350 mm
Package Level 1 Depth / Length
360 mm
Package Level 1 Gross Weight
15.5 kg
Package Level 1 EAN
8015644653149
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable For
T7M
Suitable for Product Class
Moulded Case Circuit Breakers
Version
F
Electrical Durability
2000 cycle | 60 cycles per hour
Mechanical Durability
10000 cycle | 60 cycles per hour
Number of Poles
4P
Power Loss
at Rated Operating Conditions per Pole 30 W
Rated Current (In)
1000 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 85 kA | (230 V AC) 85 kA | (380 V AC) 50 kA | (400 V AC) 50 kA | (415 V AC) 50 kA | (440 V AC) 50 kA | (500 V AC) 40 kA | (690 V AC) 30 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 20 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 85 kA | (230 V AC) 85 kA | (380 V AC) 50 kA | (400 V AC) 50 kA | (415 V AC) 50 kA | (440 V AC) 50 kA | (500 V AC) 40 kA | (690 V AC) 30 kA
Rated Uninterrupted Current (Iu)
1000 A
Release
PR332/P LI
Release Type
EL
Short-Circuit Performance Level
S
Standards
IEC
Sub-type
T7
Terminal Connection Type
Fixed Circuit-Breakers | Front
Data Sheet, Technical Information
1SDC210015D0201
Declaration of Conformity - CE
EC Declaration of Conformity Tmax T7
GL Certificate
1SDL000163R0055
Instructions and Manuals
1SDC210015D0201
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature: 4P Tmax T series moulded case circuit breaker with rated current of 1000 A, rated insulation voltage 1000 V, and rated operational voltage 690 V AC. Business impact: enables reliable protection for large feeders and transformer/engineered loads, reducing the risk of cascading faults and unplanned downtime. Application: suitable for main distribution panels and automation cabinets in heavy industry, marine, or data-center environments where high fault current can occur. Feature: Front-terminal fixed configuration and stored-energy operating mechanism with PR332/P LI release. Business impact: safer maintenance and faster replacement; Application: installations requiring front access and stored-energy operation; compatibility with standard front-terminal MCCB accessories. Feature: Power loss 30 W per pole and mechanical durability 10000 cycles; Electrical durability 2000 cycles. Business impact: lower operating temperatures, longer service life, and reduced cooling costs; Application: continuous-duty automation panels in temperature-controlled plant rooms. Feature: RoHS, REACH, CMRT, TSCA compliance and IEC standards. Business impact: mitigates regulatory risk, simplifies supply-chain documentation, and supports global procurement; Application: multinational projects with strict environmental and material declarations. Feature: 4P front-access design, 280 mm W x 268 mm H x 178 mm D footprint and 14 kg weight. Business impact: easier enclosure planning and faster retrofit; Application: upgrades to existing Tmax T installations with minimal space impact.
Get a Quick Quote for a ABB 1SDA062765R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA062765R1?
Enquire Now
FAQs
Installation follows the standard procedures in the 1SDC210015D0201 manuals. Ensure correct alignment with the fixed-front terminals, secure all connections with recommended torque per terminal, and verify the Stored-Energy Release lever PR332/P LI is operational before energizing. Use appropriate PPE and confirm panel clearance. For multichannel panels, observe proper phase grouping and label wiring to prevent misconnection and nuisance trips.
At 690 V AC, the device provides a rated service short-circuit breaking capacity Ics of 30 kA and a rated ultimate short-circuit breaking capacity Icu of 30 kA. For lower voltages such as 220–230 V, Ics and Icu are 85 kA. This range supports diverse applications from low-voltage feeders to high-energy panels while maintaining protection coordination in mixed-voltage systems.
Yes. The MCCB carries IEC standards with a CE Declaration of Conformity for Tmax T series. It also includes RoHS and REACH declarations, CMRT for conflict minerals reporting, and a TSCA declaration, addressing global regulatory and sustainability requirements. This helps simplify compliance documentation for multinational projects and procurement teams.
The unit has a footprint of 280 mm in width, 268 mm in height, and 178 mm in depth, with a product net weight of 14 kg. Packaging adds a bit more mass depending on the container, and the unit uses front-terminal fixed mounting. These dimensions assist in cabinet and bus-bar planning and ensure adequate ventilation and accessibility during service.
Front-terminal access simplifies installation and future servicing, reducing wiring errors and enabling quicker fault isolation. The 4P configuration supports coordinated protection across multiple phases, while the stored-energy mechanism ensures fast, reliable operation. This design is especially beneficial in high-availability automation panels where uptime and maintenance efficiency directly impact production metrics.