ABB 1SDA062833R1 Moulded Case Circuit Breaker - Tmax T7

Part Number: 1SDA062833R1
Manufacturer
ABB
Part number
1SDA062833R1

Quick Summary

The ABB 1SDA062833R1 Moulded Case Circuit Breaker protects power distribution panels in industrial settings. Nuisance trips and downtime under heavy loads threaten productivity, while front-terminal access simplifies field service. CE conformity, IEC standards compliance, and GL certification support regulatory and safety expectations across industrial environments. Designed for SACE Tmax T series applications, it also aligns with RoHS and REACH commitments, delivering reliable, maintainable protection. Its 3P configuration, 1000 A rated current, and 690 V AC operating voltage support critical loads in manufacturing, utilities, and data centers. The front-terminal design and fixed enclosure mounting streamline installation and reduce service time during upgrades.

Product Information

Extended Description

1SDA062833R1 ABB: C.BREAKER TMAX T7V 1000 FIXED THREE-POLE WITH FRONT TERMINALS AND LEVER OPERATING MECHANISM AND SOLID-STATE RELEASE IN AC PR231/P-I R 1000
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
SCIP
c71ed8a3-95af-4a17-b56e-f0efee734d90 Italy (IT)
Simplified SCIP
bc27cd43-0285-4fa4-bcc8-ca055d4ec6f5 Norway (NO) | e65c7bea-b026-4cec-86e7-0524bb42477f Poland (PL) | 711eab5e-a180-41d1-8580-808a2aae7bf9 Germany (DE) | 8f60774e-468c-43c4-afc4-7431d90628cd Finland (FI) | 83aa4244-e716-4edb-afde-16e65800d775 Belgium (BE) | 0ffca93c-b80b-4b08-87c9-4173c269cb09 France (FR) | bbe13aa6-211d-4110-83d9-0d892687af71 Estonia (EE) | 75134ee0-9035-4ec2-ae69-4f83ca97808d Netherlands (NL) | 305c52e9-3f51-4e39-ae50-7ccea63a5f72 Germany (DE) | 7fe7cd9c-88a5-42f4-a42c-909fbe545409 Croatia (HR) | 09131097-8a72-46d2-8a99-65aa3eee64f0 Germany (DE) | 67a3e8fe-f516-488e-b2ac-cc0cad0818f4 Denmark (DK) | 906dbf88-cdcb-4798-85bb-10f53f1d9eca Czech Republic (CZ) | 0a139813-d74a-455e-9830-5e7c807172d1 Portugal (PT) | db026c18-ae81-4147-8a13-92a7ffc7291c Greece (GR) | 74d1b0d3-a514-4987-9f2b-fbb33454e06c Bulgaria (BG) | 66d73645-5e73-4350-80cc-5800a2557299 Poland (PL) | d5f0e6e9-2795-4a65-a4d7-0b76af16e847 Sweden (SE) | d30c0538-3c79-48c9-967f-ca361c15f5e0 Belgium (BE) | 28267a60-83cf-4590-b6ff-2bf5b28971a0 Spain (ES) | d0672794-7c95-47c1-a2d7-2080c8b82ff9 France (FR) | 08ea6b12-8596-43f5-b546-af6ef2e9e653 Hungary (HU) | 075c9d0b-02e4-4b93-b7d0-a69485a6ae36 Germany (DE) | 8ae5bf27-828c-47a6-8ca1-c8958a1d2d4a Germany (DE) | 51daa204-c282-45db-addc-3e8c130e7a38 Sweden (SE) | c5832cdb-ecb7-4bec-bef7-012a1bd45d89 Hungary (HU) | 6ab6498c-aaab-4fec-9c6e-b77848e2323d Poland (PL)
Environmental Information
Product Environmental Information Tmax T7 | Breakers - Packaging disposal information
EAN
8015644653828
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
210 mm
Product Net Height
268 mm
Product Net Depth / Length
154 mm
Product Net Weight
9.7 kg
Package Level 1 Units
1 piece
Package Level 1 Width
280 mm
Package Level 1 Height
350 mm
Package Level 1 Depth / Length
360 mm
Package Level 1 Gross Weight
11.2 kg
Package Level 1 EAN
8015644653828
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable For
T7
Suitable for Product Class
Moulded Case Circuit Breakers
Version
F
Electrical Durability
3000 cycle | 60 cycles per hour
Mechanical Durability
10000 cycle | 60 cycles per hour
Number of Poles
3P
Power Loss
at Rated Operating Conditions per Pole 50 W
Rated Current (In)
1000 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 200 kA | (230 V AC) 200 kA | (380 V AC) 150 kA | (400 V AC) 150 kA | (415 V AC) 150 kA | (440 V AC) 130 kA | (500 V AC) 100 kA | (690 V AC) 45 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 15 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 200 kA | (230 V AC) 200 kA | (380 V AC) 150 kA | (400 V AC) 150 kA | (415 V AC) 150 kA | (440 V AC) 130 kA | (500 V AC) 100 kA | (690 V AC) 60 kA
Rated Uninterrupted Current (Iu)
1000 A
Release
PR231/P-I
Release Type
EL
Short-Circuit Performance Level
V
Standards
IEC
Sub-type
T7
Terminal Connection Type
Fixed Circuit-Breakers | Front
Data Sheet, Technical Information
1SDC210015D0201
Declaration of Conformity - CE
EC Declaration of Conformity Tmax T7
GL Certificate
1SDL000163R0056
Wiring Diagram
Wiring diagram T7-T7M
Instructions and Manuals
1SDC210015D0201
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39121100
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature → Business Impact → Application: The 3P fixed front-terminal design with a lever-operated release enables fast, safe installation and easy field servicing, reducing commissioning time and maintenance labor across panel assemblies and MCCs. This translates to lower lifecycle costs and quicker turnarounds on critical lines. Feature → Business Impact → Application: The PR231/P‑I solid-state release delivers precise protection and fast response under fault conditions, minimizing damage to motors, transformers, and feeders while preserving uptime in demanding production lines. Feature → Business Impact → Application: High fault-current ratings (Ics up to 200 kA, Icu up to 60 kA, with Icw of 15 kA for 1 s) provide robust fault clearance, reducing unplanned outages in heavy industry and utility switching applications. Feature → Business Impact → Application: Ui 1000 V and Uimp 8 kV enable flexible use in European and global distribution networks, supporting MCCs and transformer protection with compliant insulation margins. Feature → Business Impact → Application: RoHS, REACH, and SCIP declarations improve procurement compliance and supply-chain transparency, helping maintenance teams meet regulatory demands with confidence. Feature → Business Impact → Application: Front-terminal design, compact footprint, and 9.7 kg weight simplify handling, installation, and retrofits in compact switchgear, minimizing installation risk and downtime during upgrades.

Get a Quick Quote for a ABB 1SDA062833R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA062833R1? Enquire Now

FAQs

Install as a fixed 3P MCCB with front terminals. Ensure secure conductor termination per local utility guidelines and use the lever-operated release for quick operation. Verify the unit is properly seated in the panel and torque each terminal to the manufacturer’s specification to prevent hot spots and ضمان ensure consistent fault clearing.
Rated current is 1000 A; rated operational voltage is 690 V AC; rated insulation voltage is 1000 V; rated impulse withstand voltage is 8 kV. Short-circuit capabilities include Ics up to 200 kA and Icu up to 60 kA, with Icw at 15 kA for 1 s. It is a 3P device with a front-terminal configuration.
Yes. The unit features a CE EC Declaration of Conformity for Tmax T7, plus RoHS declarations and REACH compliance for ABB Sace circuit breakers. It also references SCIP data, CMRT, and related environmental disclosures, helping ensure regulatory alignment across European and global supply chains.
The Tmax T7 family is designed for three-pole protection in medium- to high-power distribution panels, MCCs, and transformer feeders. With front-terminal access and fixed installation, it’s well-suited for industrial plants, utilities subpanels, and data-center power distribution environments requiring robust fault clearance and reliable protection.
Durability figures include 10000 mechanical cycles and 3000 electrical cycles, supporting long service life under typical industrial duty. Front-access design reduces maintenance time, while high Ics/Icu ratings minimize downtime during faults. Overall, these features translate into lower total cost of ownership and faster payback in protective-coordination strategies.