ABB 1SDA062836R1 Moulded Case Circuit Breaker - IEC
Part Number: 1SDA062836R1
Quick Summary
Moulded Case Circuit Breaker ABB 1SDA062836R1 delivers reliable overcurrent protection for industrial power distribution. In practice, engineers often wrestle with panel layouts that demand front-terminal access and precise trip coordination; this device simplifies installation and reduces maintenance time. It aligns with IEC standards, carries a CE declaration, and holds GL certification for enhanced regulatory confidence. By pairing robust protection with Tmax T7 family compatibility and a 1000 A rating, it supports scalable power distribution while delivering lower lifecycle costs and improved uptime in demanding environments.
Product Information
Extended Description
1SDA062836R1 ABB: C.BREAKER TMAX T7V 1000 FIXED THREE-POLE WITH FRONT TERMINALS AND LEVER OPERATING MECHANISM AND SOLID-STATE RELEASE IN AC PR331/P-LSIG R 1000
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Product Environmental Information Tmax T7 | Breakers - Packaging disposal information
EAN
8015644653859
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
210 mm
Product Net Height
268 mm
Product Net Depth / Length
154 mm
Product Net Weight
9.7 kg
Package Level 1 Units
1 piece
Package Level 1 Width
280 mm
Package Level 1 Height
350 mm
Package Level 1 Depth / Length
360 mm
Package Level 1 Gross Weight
11.2 kg
Package Level 1 EAN
8015644653859
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable For
T7
Suitable for Product Class
Moulded Case Circuit Breakers
Version
F
Electrical Durability
3000 cycle | 60 cycles per hour
Mechanical Durability
10000 cycle | 60 cycles per hour
Number of Poles
3P
Power Loss
at Rated Operating Conditions per Pole 50 W
Rated Current (In)
1000 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 200 kA | (230 V AC) 200 kA | (380 V AC) 150 kA | (400 V AC) 150 kA | (415 V AC) 150 kA | (440 V AC) 130 kA | (500 V AC) 100 kA | (690 V AC) 45 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 15 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 200 kA | (230 V AC) 200 kA | (380 V AC) 150 kA | (400 V AC) 150 kA | (415 V AC) 150 kA | (440 V AC) 130 kA | (500 V AC) 100 kA | (690 V AC) 60 kA
Rated Uninterrupted Current (Iu)
1000 A
Release
PR331/P LSIG
Release Type
EL
Short-Circuit Performance Level
V
Standards
IEC
Sub-type
T7
Terminal Connection Type
Fixed Circuit-Breakers | Front
Data Sheet, Technical Information
1SDC210015D0201
Declaration of Conformity - CE
EC Declaration of Conformity Tmax T7
GL Certificate
1SDL000163R0056
Wiring Diagram
Wiring diagram T7-T7M
Instructions and Manuals
1SDC210015D0201
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39121100
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature a three-pole fixed design with front terminals and lever operating mechanism delivers quick, tool-free servicing and simplifies wiring in MCCs. Business Impact: faster changeouts and reduced maintenance labor, enabling tighter uptime budgets in high-demand facilities. Application: main distribution panels and switchgear in manufacturing plants. Feature the solid-state PR331/P LSIG release provides precise, reliable tripping and signaling integration with control systems. Business Impact: improved coordination with automation and remote monitoring, minimizing nuisance trips and unplanned downtime. Application: automation-enabled power networks and protection schemes. Feature rated current of 1000 A with Ics up to 200 kA and Icw of 15 kA for 1 s ensures strong fault handling across the 690 V AC range. Business Impact: enhanced fault clearance and reduced equipment damage. Application: large feeders and critical loads in process industries. Feature Uimp of 8 kV and Ui of 1000 V supports robust insulation and withstand performance. Business Impact: safer, regulator-compliant operation under transient events. Application: high-energy environments and transformer protection. Feature mechanical durability of 10000 cycles and electrical durability of 3000 cycles suits frequent switching scenarios. Business Impact: longer service life and lower replacement costs in dynamic plants. Application: routine start/stop cycles in heavy-duty applications. Feature front-terminal connection type and compatibility with SACE Tmax T7 configurations streamline installation. Business Impact: easier retrofits and quicker panel integration. Application: modernisation projects and new builds in industrial facilities. Feature compliance with CE, IEC standards, RoHS/REACH declarations, and GL certification provides a robust compliance package. Business Impact: reduces procurement risk and accelerates supplier approvals. Application: regulated environments requiring traceable certifications and material compliance.
Get a Quick Quote for a ABB 1SDA062836R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA062836R1?
Enquire Now
FAQs
Yes. The 1SDA062836R1 is a fixed three-pole MCC-compatible Moulded Case Circuit Breaker with front-terminal connections designed for straightforward integration into standard ABB SACE Tmax T7 panels and similar MCC configurations, reducing wiring complexity and installation time.
important specs include rated current of 1000 A, rated insulation voltage 1000 V, rated operational voltage 690 V AC, rated impulse withstand voltage 8 kV, and short-circuit breaking capacity Icu up to 200 kA depending on voltage. Ensure your system matches these values for correct protection coordination.
Yes. With 3P design, 3P poles, and PR331/P LSIG release, it supports reliable fault interruption in demanding industrial environments, including large motor feeders and transformer protection schemes common in manufacturing and process industries.
The device ships with IEC conformity, a CE declaration, and GL certification, along with RoHS/REACH compliance and CMRT/TSCA declarations where applicable, helping meet global regulatory and sustainability requirements.
Electrical durability is rated at around 3000 cycles and mechanical durability at about 10000 cycles at a typical 60 cycles per hour, providing predictable maintenance planning and reduced total cost of ownership in high‑duty switching environments.