ABB 1SDA062837R1 Moulded Case Circuit Breaker - PR332/P LI

Part Number: 1SDA062837R1
Manufacturer
ABB
Part number
1SDA062837R1

Quick Summary

ABB 1SDA062837R1 Moulded Case Circuit Breaker protects power distribution in industrial plants. This compact, fixed-front-terminal device delivers safe isolation and dependable short-circuit protection, simplifying installation in compact switchgear. Engineers often face space constraints, frequent field upgrades, and compliance hurdles; this breaker’s robust architecture supports quick retrofits and reliable operation in demanding environments. It carries CE conformity, RoHS and REACH declarations, and IEC-based safety standards, along with CMRT and TSCA declarations where applicable. With a rated current of 1000 A, rated operational voltage of 690 V AC, and Uimp of 8 kV, it provides strong protection while enabling scalable expansion across distribution panels. This combination supports lower total cost of ownership and longer service life.

Product Information

Extended Description

1SDA062837R1 ABB: C.BREAKER TMAX T7V 1000 FIXED THREE-POLE WITH FRONT TERMINALS AND LEVER OPERATING MECHANISM AND SOLID-STATE RELEASE IN AC PR332/P-LI R 1000
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Product Environmental Information Tmax T7 | Breakers - Packaging disposal information
EAN
8015644653866
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
210 mm
Product Net Height
268 mm
Product Net Depth / Length
154 mm
Product Net Weight
9.7 kg
Package Level 1 Units
1 piece
Package Level 1 Width
280 mm
Package Level 1 Height
350 mm
Package Level 1 Depth / Length
360 mm
Package Level 1 Gross Weight
11.2 kg
Package Level 1 EAN
8015644653866
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable For
T7
Suitable for Product Class
Moulded Case Circuit Breakers
Version
F
Electrical Durability
3000 cycle | 60 cycles per hour
Mechanical Durability
10000 cycle | 60 cycles per hour
Number of Poles
3P
Power Loss
at Rated Operating Conditions per Pole 50 W
Rated Current (In)
1000 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 200 kA | (230 V AC) 200 kA | (380 V AC) 150 kA | (400 V AC) 150 kA | (415 V AC) 150 kA | (440 V AC) 130 kA | (500 V AC) 100 kA | (690 V AC) 45 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 15 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 200 kA | (230 V AC) 200 kA | (380 V AC) 150 kA | (400 V AC) 150 kA | (415 V AC) 150 kA | (440 V AC) 130 kA | (500 V AC) 100 kA | (690 V AC) 60 kA
Rated Uninterrupted Current (Iu)
1000 A
Release
PR332/P LI
Release Type
EL
Short-Circuit Performance Level
V
Standards
IEC
Sub-type
T7
Terminal Connection Type
Fixed Circuit-Breakers | Front
Data Sheet, Technical Information
1SDC210015D0201
Declaration of Conformity - CE
EC Declaration of Conformity Tmax T7
GL Certificate
1SDL000163R0056
Wiring Diagram
Wiring diagram T7-T7M
Instructions and Manuals
1SDC210015D0201
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39121100
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature → Business Impact → Application: The 3-pole, fixed-front-terminal design simplifies wiring and installation, reducing commissioning time and wiring errors, especially in compact switchgear assemblies used in manufacturing lines. Application: Panel builders gain faster installations and more reliable field service in automotive and general industry environments. Feature → Business Impact → Application: Rated 1000 A and 690 V AC coverage deliver robust protection for medium-to-large distribution panels, enabling safe escalation of load without compromising safety. Application: Main feeders and bus-section protection in process plants and packaging lines. Feature → Business Impact → Application: High Ics up to 200 kA and Icu up to 60 kA provide substantial fault-margin, improving system availability and reducing outage risk during transformer or generator connections. Application: Transformer bays and generator drives in power plants and data centers. Feature → Business Impact → Application: PR332/P LI release and T7 sub-type deliver fast, precise tripping with predictable coordination, lowering nuisance trips and maintenance costs. Application: Protection schemes requiring quick, reliable tripping across 3P circuits. Feature → Business Impact → Application: RoHS and REACH declarations, CMRT/TSCA data ensure regulatory compliance across Europe, North America, and emerging markets. Application: Global sourcing for multinational projects and industrial rollouts. Feature → Business Impact → Application: Front-terminal, fixed-breaker construction reduces panel depth requirements and supports retrofits in legacy installations. Application: Upgrades in retrofits for aging switchgear without major enclosure changes. Feature → Business Impact → Application: Power loss of 50 W per pole under rated conditions supports thermal management budgeting and efficiency planning. Application: Energy-conscious design in machine enclosures and distribution boards. Feature → Business Impact → Application: Mechanical durability 10000 cycles and electrical durability 3000 cycles at 60 cycles/hour ensure long service life with predictable maintenance windows. Application: High-usage manufacturing lines and critical infrastructure where uptime matters.

Get a Quick Quote for a ABB 1SDA062837R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA062837R1? Enquire Now

FAQs

This is a 3P fixed-front-terminal moulded case circuit breaker designed for straightforward panel integration. Its front-terminal connection simplifies wiring in retrofit projects and reduces enclosure modifications. Ensure compatible bus bars, mounting spacing, and that the device’s rated current and voltage align with the distribution panel specifications for reliable protection.
Key specs include In 1000 A, Ui 1000 V, Ue 690 V AC, Uimp 8 kV, Ics up to 200 kA, and Icu up to 60 kA depending on voltage. The device also offers 50 W power loss per pole and a rated service current of 1000 A, delivering strong fault protection while maintaining efficiency in medium-to-large panels.
Yes. With its Tmax T7 family designation, 3P configuration, and high short-circuit ratings, it is well-suited for transformer protection and generator connections in distribution schemes. Its compatibility with 690 V AC systems and high Ics/Icu margins supports reliable operation in industrial plants and power distribution networks.
The unit carries IEC-based standards compliance and CE conformity. RoHS and REACH declarations are provided, along with CMRT and TSCA where applicable, ensuring global regulatory coverage for procurement and cross-border deployments.
PR332/P LI release offers precise, predictable tripping and simplified maintenance planning. The device’s electrical durability of 3000 cycles and mechanical durability of 10000 cycles at 60 cycles/hour support longer service intervals and reduced lifecycle costs, contributing to overall uptime improvements and lower total cost of ownership.