ABB 1SDA062844R1 Moulded Case Circuit Breaker - 4P LSIG

Part Number: 1SDA062844R1
Manufacturer
ABB
Part number
1SDA062844R1

Quick Summary

ABB 1SDA062844R1 Moulded Case Circuit Breaker protects large power circuits in industrial switchgear. Engineers face downtime and arc-flash risk when protection devices are slow to isolate faults or difficult to service. This model carries CE conformity, IEC standard compliance, and RoHS/REACH declarations, ensuring regulatory alignment and material integrity. Designed for Tmax T7 families with front-terminal 4P construction, it simplifies installation, reduces wiring errors, and accelerates maintenance. For procurement teams, the unit offers reliable protection with high current capability (1000 A) and robust short-circuit performance, supporting safer, compliant, and cost-effective power distribution in manufacturing and data-center environments.

Product Information

Extended Description

1SDA062844R1 ABB: C.BREAKER TMAX T7V 1000 FIXED FOUR-POLE WITH FRONT TERMINALS AND LEVER OPERATING MECHANISM AND SOLID-STATE RELEASE IN AC PR331/P-LSIG R 1000
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Product Environmental Information Tmax T7 | Breakers - Packaging disposal information
EAN
8015644653934
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
280 mm
Product Net Height
268 mm
Product Net Depth / Length
154 mm
Product Net Weight
12.5 kg
Package Level 1 Units
1 piece
Package Level 1 Width
360 mm
Package Level 1 Height
350 mm
Package Level 1 Depth / Length
360 mm
Package Level 1 Gross Weight
14 kg
Package Level 1 EAN
8015644653934
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable For
T7
Suitable for Product Class
Moulded Case Circuit Breakers
Version
F
Electrical Durability
3000 cycle | 60 cycles per hour
Mechanical Durability
10000 cycle | 60 cycles per hour
Number of Poles
4P
Power Loss
at Rated Operating Conditions per Pole 50 W
Rated Current (In)
1000 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 200 kA | (230 V AC) 200 kA | (380 V AC) 150 kA | (400 V AC) 150 kA | (415 V AC) 150 kA | (440 V AC) 130 kA | (500 V AC) 100 kA | (690 V AC) 45 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 15 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 200 kA | (230 V AC) 200 kA | (380 V AC) 150 kA | (400 V AC) 150 kA | (415 V AC) 150 kA | (440 V AC) 130 kA | (500 V AC) 100 kA | (690 V AC) 60 kA
Rated Uninterrupted Current (Iu)
1000 A
Release
PR331/P LSIG
Release Type
EL
Short-Circuit Performance Level
V
Standards
IEC
Sub-type
T7
Terminal Connection Type
Fixed Circuit-Breakers | Front
Data Sheet, Technical Information
1SDC210015D0201
Declaration of Conformity - CE
EC Declaration of Conformity Tmax T7
GL Certificate
1SDL000163R0056
Wiring Diagram
Wiring diagram T7-T7M
Instructions and Manuals
1SDC210015D0201
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39121100
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature: Four-pole fixed front-terminal design with PR331/P LSIG release enhances installation speed and wiring clarity. Business Impact: Reduces commissioning time and minimizes wiring errors, improving overall reliability in switchgear assemblies. Application: Ideal for large distribution panels, motor control centers, and transformer protection in industrial plants. Feature: Rated current of 1000 A and high fault current capacity up to 200 kA Icu (low voltages) and 60 kA at 690 V. Business Impact: Delivers scalable protection for demanding loads, enabling safe operation under peak fault conditions. Application: Power distribution and critical machinery across manufacturing facilities. Feature: Solid-state release (EL) with LSIG alignment and front-terminal design. Business Impact: Provides precise tripping coordination and straightforward maintenance access. Application: Transformer protection and feeder circuits in Tmax T7 equipment. Feature: Mechanical durability of 10,000 cycles and electrical durability of 3,000 cycles at standard duty. Business Impact: Extends service life in high-usage environments, reducing replacement intervals and total cost of ownership. Application: Continuous duty panels in energy-intensive operations. Feature: Compliance and sustainability declarations (RoHS, REACH, CMRT) with IEC standards and CE conformity. Business Impact: Eases regulatory audits and supports responsible sourcing. Application: Global deployments requiring risk-managed supply chains in automotive, data center, and process industries.

Get a Quick Quote for a ABB 1SDA062844R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA062844R1? Enquire Now

FAQs

The 1SDA062844R1 uses fixed, front-terminal connections in a four-pole arrangement. Follow the Wiring Diagram for T7-T7M and ensure correct busbar alignment, torque per terminal guidelines, and adequate clearance. The front-terminal design simplifies wiring, reduces installation time, and minimizes field wiring errors, making it well-suited for switchgear in manufacturing and data centers.
Key specs include rated current 1000 A, rated operational voltage 690 V AC, rated insulation voltage 1000 V, and short-circuit breaking capacity up to 60 kA at 690 V. It features a PR331/P LSIG release and four poles (4P). The device supports high fault current scenarios and is designed for Tmax T7 protection in industrial installations.
Yes. The device is a Tmax T7 family member with a PR331/P LSIG release, compatible with Tmax T7 switchgear configurations. It is designed for front-terminal mounting, 4P operation, and aligned with the Tmax T7 product ecosystem, making it a consistent choice for reliable protection in transformer and distribution panels.
The 1SDA062844R1 includes CE Declaration of Conformity, RoHS Declaration, REACH Declaration, CMRT, TSCA declaration, and a GL certificate. It also references applicable IEC standards and product environmental information. These declarations facilitate regulatory compliance, sustainability reporting, and responsible procurement for global deployments.
Electrical durability is rated at 3,000 cycles and mechanical durability at 10,000 cycles at standard duty (60 cycles per hour). This translates to longer service intervals in high-uptime plants. Front-terminal accessibility simplifies inspection and maintenance, supporting faster remediation and lower total cost of ownership in industrial environments.