ABB 1SDA062858R1 Moulded Case Circuit Breaker - Icu 60 kA
Part Number: 1SDA062858R1
Quick Summary
ABB 1SDA062858R1 is a moulded case circuit breaker for industrial power distribution in data centers, manufacturing lines, and plant equipment. Engineers often grapple with reliable tripping, safe front-access installation, and stored-energy handling in space-constrained panels. It aligns with IEC standards and carries CE conformity and RoHS declarations, strengthening compliance across global installations. As part of the Tmax T family, this unit delivers robust protection, fast response, and predictable maintenance intervals. With a 1000 A rating at 690 V AC and a 60 kA short-circuit capacity, it offers scalable protection for high-demand feeders. Front terminals simplify wiring in panels, reducing assembly time and field wiring risks.
Product Information
Extended Description
1SDA062858R1 ABB: C.BREAKER TMAX T7V 1000 FIXED FOUR-POLE WITH FRONT TERMINALS AND STORED ENERGY OPERATING MECHANISM AND SOLID-STATE RELEASE IN AC PR231/P-LS/I R 1000
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Product Environmental Information Tmax T7 | Breakers - Packaging disposal information
EAN
8015644654078
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
280 mm
Product Net Height
268 mm
Product Net Depth / Length
178 mm
Product Net Weight
14 kg
Package Level 1 Units
1 piece
Package Level 1 Width
360 mm
Package Level 1 Height
350 mm
Package Level 1 Depth / Length
360 mm
Package Level 1 Gross Weight
15.5 kg
Package Level 1 EAN
8015644654078
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable For
T7M
Suitable for Product Class
Moulded Case Circuit Breakers
Version
F
Electrical Durability
3000 cycle | 60 cycles per hour
Mechanical Durability
10000 cycle | 60 cycles per hour
Number of Poles
4P
Power Loss
at Rated Operating Conditions per Pole 50 W
Rated Current (In)
1000 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 200 kA | (230 V AC) 200 kA | (380 V AC) 150 kA | (400 V AC) 150 kA | (415 V AC) 150 kA | (440 V AC) 130 kA | (500 V AC) 100 kA | (690 V AC) 45 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 15 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 200 kA | (230 V AC) 200 kA | (380 V AC) 150 kA | (400 V AC) 150 kA | (415 V AC) 150 kA | (440 V AC) 130 kA | (500 V AC) 100 kA | (690 V AC) 60 kA
Rated Uninterrupted Current (Iu)
1000 A
Release
PR231/P-LS/I
Release Type
EL
Short-Circuit Performance Level
V
Standards
IEC
Sub-type
T7
Terminal Connection Type
Fixed Circuit-Breakers | Front
Data Sheet, Technical Information
1SDC210015D0201
Declaration of Conformity - CE
EC Declaration of Conformity Tmax T7
GL Certificate
1SDL000163R0056
Wiring Diagram
Wiring diagram T7-T7M
Instructions and Manuals
1SDC210015D0201
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature → Business Impact → Application: Four-pole fixed circuit-breaker design with front terminals and stored-energy operating mechanism enables compact panel layouts while ensuring rapid fault clearance and safer maintenance access; this translates to reduced downtime and safer commissioning in motor control centers and feeders. Application: Use in large-scale industrial feeders and transformer sections where space is at a premium and reliability is critical. Feature → Business Impact → Application: 1000 A rated current and 690 V AC rated operational voltage deliver robust protection for heavy-load equipment, minimizing nuisance trips and allowing a single device to protect multiple loads in distribution boards. Application: Ideal for high-demand lines in process industries and packaging lines. Feature → Business Impact → Application: High short-circuit withstand capacity (Icu up to 60 kA) provides margin for fault clearance in systems with large inductive loads, reducing transformer/load disruption and enhancing plant uptime. Application: Main feeders feeding motors, pumps, and large machinery. Feature → Business Impact → Application: PR231/P-LS/I release and IEC conformity deliver precise tripping characteristics and safe energy release, supporting compliant emergency shutdown sequences. Application: Critical protection in safety-certified installations and hazardous environments. Feature → Business Impact → Application: Mechanical durability of 10,000 cycles and electrical durability of 3,000 cycles (60 cycles/hour) extend service life, lowering maintenance frequency and total cost of ownership. Application: Frequent switching applications and settings with recurring load changes. Feature → Business Impact → Application: Front-terminal configuration and fixed mounting streamline installation, cabling, and future panel upgrades, reducing commissioning time and helping service teams implement changes with minimal downtime. Application: Retrofit projects and new builds where rapid deployment is essential. Feature → Business Impact → Application: Compliance documentation including REACH, RoHS, CMRT, TSCA, and WEEE packaging information supports global sourcing and regulatory readiness. Application: Global manufacturing sites requiring audited supply chains and sustainability reporting.
Get a Quick Quote for a ABB 1SDA062858R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA062858R1?
Enquire Now
FAQs
This ABB MCCB is designed for front-terminal connections in fixed-panel installations. Begin by de-energizing the panel, verify busbar spacing and torque specifications, then align the four-pole mounting footprint. Connect phase conductors to the front terminals using appropriate lugs, secure with torque per the installation manual, and verify correct release alignment with the PR231/P-LS/I mechanism. Finally, perform a functional test to confirm trips under simulated faults while ensuring all safety interlocks are in place.
Key specs include a rated current of 1000 A, rated operational voltage of 690 V AC, and rated insulation voltage of 1000 V. It provides a rated impulse withstand voltage (Uimp) of 8 kV and a short-circuit withstand capacity (Icu) up to 60 kA. With a 4P configuration and front terminals, it is suited for large feeders and motor protection in industrial applications.
Yes. The unit is part of the SACE Tmax Tmax T family lineage and supports Tmax T protection schemes with a PR231/P-LS/I release. Its 4P fixed configuration, high Icu rating, and IEC conformity make it compatible with Tmax T panel designs, motor feeders, and transformer protection in industrial environments while delivering reliable, code-compliant performance.
The product includes CE conformity, RoHS compliance, and a Declaration of Conformity. It also references CMRT for conflict minerals, TSCA declaration for chemical compliance, and WEEE packaging information, ensuring global regulatory readiness and sustainable handling across manufacturing sites.
The MCCB offers an extended mechanical durability of 10,000 cycles and electrical durability of 3,000 cycles at 60 cycles/hour, reducing replacement frequency. Its front-terminal design accelerates installation and service work, lowering labor costs. Combined with high Icu capability and reliable tripping, the device minimizes unplanned downtime and extends mean time between outages, delivering a favorable total cost of ownership.