ABB 1SDA062867R1 Moulded Case Circuit Breaker - 8 kV Uimp PR232/P-LSI

Part Number: 1SDA062867R1
Manufacturer
ABB
Part number
1SDA062867R1

Quick Summary

Moulded Case Circuit Breaker protection guards industrial power systems from overloads and short circuits in distribution panels. Choosing a high-current, front-terminal breaker for Tmax T7 installations can be challenging when space, wiring, and downtime expectations clash. The device is manufactured to IEC standards, CE certified, and RoHS compliant, supporting compliant performance in regulated environments. This model delivers reliable protection for large-scale systems with a rated current of 1250 A and a robust PR232/P-LSI release, designed for front-terminal installations in Tmax T7S configurations. For procurement teams, these features translate into reduced downtime, predictable lifecycle costs, and simplified maintenance within industrial power distribution environments.

Product Information

Extended Description

1SDA062867R1 ABB: C.BREAKER TMAX T7S 1250 FIXED THREE-POLE WITH FRONT TERMINALS AND LEVER OPERATING MECHANISM AND SOLID-STATE RELEASE IN AC PR232/P-LSI R 1250
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
SCIP
da03da0a-bc7d-4078-8477-a5a073e63e1f Italy (IT)
Simplified SCIP
c8ce81f6-bfcb-42ba-a05c-6b71a3c567c0 Germany (DE) | b765c4b8-b7eb-4ffb-884b-d1acfc9764b8 Norway (NO) | 66256520-6d6c-4cfe-b684-a1b0856260ea Germany (DE) | 8fd7d2f5-ec4c-48d7-91e2-34c13d29f1ce Croatia (HR) | 8be606ef-b7c8-48c2-8c7c-1a400706692b Netherlands (NL) | 4c600c92-1c40-43f5-bcf7-84f411d16f8c Estonia (EE) | 4b62ee63-d814-465c-a306-78b957520a1f Portugal (PT) | afdc82c4-0956-49ae-8ccc-b160a90bc7d1 Netherlands (NL) | 65d192c9-2e5e-4381-bc95-570682c45d8f Finland (FI) | 8378ab53-e951-490c-970f-d311b336b62e Sweden (SE) | 81950776-3d4b-4d63-a9ed-fe3a75cd01ea Poland (PL) | 80171f53-f048-4e80-8014-1ce3c97a9128 Germany (DE) | 499cbd00-ae72-4794-99c5-1c9c249f8f57 France (FR) | 16d474e1-a616-4664-bc87-cd14348f08a7 Netherlands (NL) | 0a266a94-cce8-4a73-8b9a-b0143069213e Spain (ES) | 5f2860f8-fd7a-4aea-8f8c-bd0e84755184 Netherlands (NL) | a4754275-a403-4c0b-b594-8235d791d58d Denmark (DK) | cee814fc-6744-4eaf-8b01-bde87c9ee716 Poland (PL) | e65b699a-e848-4578-b21d-d1c574efffb9 Poland (PL) | 330760d2-6a8f-4cec-8e31-d050933fb231 France (FR) | e55ab0ae-08f0-439c-a194-a0ed98e305d5 Netherlands (NL) | ab77f919-4c29-4bdf-84a5-3a45fb9ccfbb Czech Republic (CZ) | 2d00309a-6e69-4d4a-bc70-f043a40184e4 Sweden (SE) | db5548aa-45de-467e-8e02-a24aa0840f83 Bulgaria (BG) | 2c587e85-34c2-46af-8052-884be70d488b Germany (DE) | 93aac55c-08d2-4989-aef4-b9bf492fb487 Greece (GR) | 1e9efd3c-5e5e-498a-8c1d-3f03ecb997ed Germany (DE)
Environmental Information
Product Environmental Information Tmax T7 | Breakers - Packaging disposal information
EAN
8015644654160
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
210 mm
Product Net Height
268 mm
Product Net Depth / Length
154 mm
Product Net Weight
14.371 kg
Package Level 1 Units
1 piece
Package Level 1 Width
280 mm
Package Level 1 Height
350 mm
Package Level 1 Depth / Length
360 mm
Package Level 1 Gross Weight
14.372 kg
Package Level 1 EAN
8015644654160
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable For
T7
Suitable for Product Class
Moulded Case Circuit Breakers
Version
F
Electrical Durability
2000 cycle | 60 cycles per hour
Mechanical Durability
10000 cycle | 60 cycles per hour
Number of Poles
3P
Power Loss
at Rated Operating Conditions per Pole 47 W
Rated Current (In)
1250 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 85 kA | (230 V AC) 85 kA | (380 V AC) 50 kA | (400 V AC) 50 kA | (415 V AC) 50 kA | (440 V AC) 50 kA | (500 V AC) 40 kA | (690 V AC) 30 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 20 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 85 kA | (230 V AC) 85 kA | (380 V AC) 50 kA | (400 V AC) 50 kA | (415 V AC) 50 kA | (440 V AC) 50 kA | (500 V AC) 40 kA | (690 V AC) 30 kA
Rated Uninterrupted Current (Iu)
1250 A
Release
PR232/P-LSI
Release Type
EL
Short-Circuit Performance Level
S
Standards
IEC
Sub-type
T7
Terminal Connection Type
Fixed Circuit-Breakers | Front
Data Sheet, Technical Information
1SDC210015D0201
Declaration of Conformity - CE
EC Declaration of Conformity Tmax T7
GL Certificate
1SDL000163R0055
Instructions and Manuals
1SDC210015D0201
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39121100
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature: High current rating of 1250 A in a three-pole MCCB. Business Impact: Enables protection of large loads and heavy machinery without frequent device changes, reducing downtime and optimizing protection at scale. Application: Suitable for 690 V AC distribution in manufacturing plants and processing facilities. The ABB Tmax T7S family supports scalable protection for expanding sites, with front-terminal access simplifying wiring and future upgrades. Feature: High short-circuit and fault withstand specifications (Ics up to 85 kA; Icw 20 kA for 1 s; Uimp 8 kV). Business Impact: Delivers fast, reliable interruption of high fault currents, minimizing damage to upstream equipment and reducing repair costs. Application: Transformer and motor protection in high-energy environments where fault currents are unpredictable. Feature: Front-terminal, fixed circuit-breaker design. Business Impact: Reduces installation time and wiring errors, enabling quicker panel assembly and safer maintenance with easy front access. Application: Control cabinets and switchgear where rear space is limited or unavailable. Feature: Release and compatibility (PR232/P-LSI; 3P; 690 V rated). Business Impact: Provides precise tripping performance and compatibility with Tmax T7 systems, improving reliability and simplifying spare-part planning. Application: New installations and retrofits in existing Tmax T7 panels, supporting lifecycle continuity. Feature: Compliance and environmental data (CE, RoHS, SCIP, TSCA). Business Impact: Helps meet regulatory requirements and sustainability goals, reducing compliance risk and enabling transparent supply chains. Application: Global manufacturing and multi-region facilities requiring formal declarations and end-of-life data. Feature: Mechanical and electrical durability (Mechanical 10000 cycles; Electrical 2000 cycles) and energy loss consideration (47 W per pole). Business Impact: Predictable maintenance windows and lower total cost of ownership through known wear profiles and energy efficiency. Application: Continuous operation environments with high cycling demands, such as pumps and conveyors.

Get a Quick Quote for a ABB 1SDA062867R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA062867R1? Enquire Now

FAQs

Installation follows the MCCB’s fixed-front-terminal design. Use 3P alignment and connect to the front terminals as shown in ABB’s data sheet (1SDC210015D0201). Ensure correct wiring order, tighten connections to the specified torque, and verify the PR232/P-LSI release is compatible with the panel’s protection scheme. The part is designed for straightforward integration in Tmax T7 panels, minimizing commissioning time and wiring errors.
This model features a rated current In of 1250 A, rated impulse withstand voltage Uimp of 8 kV, rated short-time withstand current Icw up to 20 kA for 1 second, and a rated service short-circuit breaking capacity Ics of up to 85 kA depending on voltage. It operates at 690 V AC with a Ui of 1000 V, making it suitable for intensive industrial protection tasks.
Yes. The MCCB complies with CE declarations and RoHS requirements for SACE Tmax T devices. Additional environmental and regulatory information includes SCIP and TSCA declarations, enabling you to meet global regulatory and sustainability commitments while maintaining traceability in procurement records.
Best suited for high-current distribution and protection in 690 V AC systems, including large motors, transformers, and critical feeders in manufacturing and process facilities. Its front-terminal configuration simplifies wiring in space-constrained panels, and its PR232/P-LSI release provides reliable tripping in Tmax T7S installations, supporting dependable protection in demanding environments.
Electrical durability is rated at 2000 cycles and mechanical durability at 10000 cycles, with an energy loss of 47 W per pole. This translates to predictable maintenance intervals and improved lifecycle costs, as maintenance teams can plan replacements and test cycles around known wear profiles while ensuring protection levels remain consistent during operation.