ABB 1SDA062894R1 Moulded Case Circuit Breaker - 1250 A
Part Number: 1SDA062894R1
Quick Summary
ABB 1SDA062894R1 Moulded Case Circuit Breaker is a high-capacity protection device for industrial power distribution. Downtime from nuisance trips or unplanned outages is costly; this unit delivers front-terminal access and a stored-energy mechanism for quick, reliable operation. It carries CE conformity with IEC standards, RoHS and REACH compliance, and a Declaration of Conformity for Tmax T7 families, providing robust regulatory alignment. This combination supports safer installation, easier maintenance, and scalable protection across large motor loads and distribution boards, while offering predictable lifecycle costs and improved uptime for critical manufacturing processes.
Product Information
Extended Description
1SDA062894R1 ABB: C.BREAKER TMAX T7S 1250 FIXED FOUR-POLE WITH FRONT TERMINALS AND STORED ENERGY OPERATING MECHANISM AND SOLID-STATE RELEASE IN AC PR332/P-LSI R 1250
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Product Environmental Information Tmax T7 | Breakers - Packaging disposal information
Order Code US and Canada
T7MSFB4AR000000XX
EAN
8015644654436
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
280 mm
Product Net Height
268 mm
Product Net Depth / Length
178 mm
Product Net Weight
14 kg
Package Level 1 Units
1 piece
Package Level 1 Width
360 mm
Package Level 1 Height
350 mm
Package Level 1 Depth / Length
360 mm
Package Level 1 Gross Weight
15.5 kg
Package Level 1 EAN
8015644654436
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable For
T7M
Suitable for Product Class
Moulded Case Circuit Breakers
Version
F
Electrical Durability
2000 cycle | 60 cycles per hour
Mechanical Durability
10000 cycle | 60 cycles per hour
Number of Poles
4P
Power Loss
at Rated Operating Conditions per Pole 47 W
Rated Current (In)
1250 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 85 kA | (230 V AC) 85 kA | (380 V AC) 50 kA | (400 V AC) 50 kA | (415 V AC) 50 kA | (440 V AC) 50 kA | (500 V AC) 40 kA | (690 V AC) 30 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 20 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 85 kA | (230 V AC) 85 kA | (380 V AC) 50 kA | (400 V AC) 50 kA | (415 V AC) 50 kA | (440 V AC) 50 kA | (500 V AC) 40 kA | (690 V AC) 30 kA
Rated Uninterrupted Current (Iu)
1250 A
Release
PR332/P LSI
Release Type
EL
Short-Circuit Performance Level
S
Standards
IEC
Sub-type
T7
Terminal Connection Type
Fixed Circuit-Breakers | Front
Data Sheet, Technical Information
1SDC210015D0201
Declaration of Conformity - CE
EC Declaration of Conformity Tmax T7
GL Certificate
1SDL000163R0055
Instructions and Manuals
1SDC210015D0201
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature → Business Impact → Application: Four-pole design (4P) delivers strong phase isolation and coordinated protection for multi‑pole motor feeders in heavy industry, reducing fault propagation and enhancing safety. This translates to lower risk of collateral damage during faults and straightforward coordination with upstream protection schemes in process lines and packaging lines. Application: large‑scale motor drives and MCCs in steel, chemical, and automotive plants. Feature → Business Impact → Application: 1250 A rated current with 690 V AC operation enables protection of high‑current circuits and heavy loads, improving continuity for high‑demand feeders and minimizing nuisance trips under normal transient conditions. Application: main feeders and distribution boards feeding large motors. Feature → Business Impact → Application: Front terminals and fixed‑front connection simplify installation, reduce wiring errors, and speed commissioning in new builds or panel upgrades. Application: switchgear retrofits and OEM panel builds. Feature → Business Impact → Application: Stored energy operating mechanism (SEOM) provides fast, reliable tripping and reset, decreasing down-time during maintenance and test cycles. Application: routine testing, maintenance windows, and functional verification in critical lines. Feature → Business Impact → Application: PR332/P LSI release with EL type provides precise release characteristics, ensuring predictable protection curves and compliance with IEC standards. Application: motor control centers and distribution panels in manufacturing. Feature → Business Impact → Application: RoHS, REACH, CMRT, and TSCA declarations streamline supply chain compliance, enabling procurement teams to meet regulatory requirements with confidence. Application: global multi‑region projects and supplier audits. Feature → Business Impact → Application: 8 kV rated impulse withstand and 85 kA short-circuit breaking capacity (Ics) across specified voltages deliver robust short‑circuit performance for critical power buses. Application: data centers, process plants, and heavy machinery zones where fault tolerance is essential. Feature → Business Impact → Application: 14 kg device weight (net) with packaging that supports efficient palletization and logistics, reducing freight costs and storage footprint in distribution warehouses. Application: spare parts stocking and regional procurement planning. All features cited align with ABB Tmax T7 family performance, ensuring compatibility with Tmax accessories and standard installation practices, while addressing common concerns such as install-time, maintenance intervals, and regulatory compliance.
Get a Quick Quote for a ABB 1SDA062894R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA062894R1?
Enquire Now
FAQs
For front-terminal fixed connection MCCBs, ensure panel cutouts match the 280 mm width, 268 mm height, and 178 mm depth. Use torque specifications per the PR332/P LSI release and verify compatible busbar cross‑section. Front terminals simplify wiring, reduce cross‑section errors, and speed commissioning in new builds or upgrades.
Rated current is 1250 A with rated operational voltage 690 V AC and rated insulation voltage 1000 V. It offers an Ics up to 85 kA (at various voltages) and Icw of 20 kA for 1 s, enabling robust protection for high‑demand feeders and motor circuits while maintaining coordination with upstream protection.
Yes. The device carries RoHS information and REACH declarations for ABB Sace circuit breakers, plus CMRT and TSCA declarations, ensuring regulatory compliance across regions and simplifying supplier audits and procurement approvals.
Yes. It is part of the Tmax T family with the SACE Tmax T design philosophy, featuring PR332/P LSI release and front-terminal construction, making it an appropriate choice for large motor feeders and protection of distribution boards in manufacturing and process environments.
Electrical durability is rated at 2000 cycles and mechanical durability at 10000 cycles at standard operation, with a stored-energy mechanism supporting fast operation. This translates to predictable maintenance windows, lower unplanned downtime, and longer service intervals for mission-critical lines.