ABB 1SDA062961R1 Moulded Case Circuit Breaker - 690V
Part Number: 1SDA062961R1
Quick Summary
ABB 1SDA062961R1 Moulded Case Circuit Breaker protects industrial power distribution by interrupting fault currents in panels. Site operators often contend with costly downtime from unexpected trips, nuisance tripping under transient faults, and difficult maintenance access. This unit delivers IEC-compliant protection with RoHS and REACH declarations and leverages the PR231/P-I release for precise, reliable operation in Tmax T7 deployments. For panel builders and maintenance teams, the front-terminal, fixed-connection design paired with a 1250 A rating enables faster installations, simpler field service, and reduced total cost of ownership. Rated for 690 V AC operation with up to 60 kA Icu, it supports modern distribution architectures and scalability for growing facilities.
Product Information
Extended Description
1SDA062961R1 ABB: C.BREAKER TMAX T7V 1250 FIXED THREE-POLE WITH FRONT TERMINALS AND LEVER OPERATING MECHANISM AND SOLID-STATE RELEASE IN AC PR231/P-I R 1250
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Product Environmental Information Tmax T7 | Breakers - Packaging disposal information
EAN
8015644655105
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
210 mm
Product Net Height
268 mm
Product Net Depth / Length
154 mm
Product Net Weight
9.7 kg
Package Level 1 Units
1 piece
Package Level 1 Width
280 mm
Package Level 1 Height
350 mm
Package Level 1 Depth / Length
360 mm
Package Level 1 Gross Weight
11.2 kg
Package Level 1 EAN
8015644655105
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable For
T7
Suitable for Product Class
Moulded Case Circuit Breakers
Version
F
Electrical Durability
3000 cycle | 60 cycles per hour
Mechanical Durability
10000 cycle | 60 cycles per hour
Number of Poles
3P
Power Loss
at Rated Operating Conditions per Pole 78.3 W
Rated Current (In)
1250 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 200 kA | (230 V AC) 200 kA | (380 V AC) 150 kA | (400 V AC) 150 kA | (415 V AC) 150 kA | (440 V AC) 130 kA | (500 V AC) 100 kA | (690 V AC) 45 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 15 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 200 kA | (230 V AC) 200 kA | (380 V AC) 150 kA | (400 V AC) 150 kA | (415 V AC) 150 kA | (440 V AC) 130 kA | (500 V AC) 100 kA | (690 V AC) 60 kA
Rated Uninterrupted Current (Iu)
1250 A
Release
PR231/P-I
Release Type
EL
Short-Circuit Performance Level
V
Standards
IEC
Sub-type
T7
Terminal Connection Type
Fixed Circuit-Breakers | Front
Data Sheet, Technical Information
1SDC210015D0201
Declaration of Conformity - CE
EC Declaration of Conformity Tmax T7
GL Certificate
1SDL000163R0056
Wiring Diagram
Wiring diagram T7-T7M
Instructions and Manuals
1SDC210015D0201
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39121100
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature → Business Impact → Application: The 3P design handles high-power feeder protection with a 1250 A nominal current, enabling robust protection for large motors and distribution panels while maintaining system stability and reducing the risk of cascading faults in heavy industry environments. This translates to fewer unplanned outages and more predictable maintenance windows in automotive, metals, and process industries. Feature → Business Impact → Application: PR231/P-I release provides precise tripping and selective protection, improving reliability and reducing nuisance trips during transient events, which is essential for critical production lines and data center infrastructure where uptime is a priority. Feature → Business Impact → Application: Front-terminal, fixed-connection design simplifies wiring, speeds panel assembly, and eases fault finding during service campaigns, especially in cramped control cabinets and retrofit projects across manufacturing plants. Feature → Business Impact → Application: Conforms to IEC standards with RoHS REACH and CMRT declarations, supporting compliance workflows and sustainability targets, while easing procurement across multinational sites. Feature → Business Impact → Application: High short-circuit capability up to 60 kA Icu at 690 V and Ics up to 200 kA at lower voltages provide rugged protection for complex power networks, improving safety and reducing equipment damage in automation systems and transformers.
Get a Quick Quote for a ABB 1SDA062961R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA062961R1?
Enquire Now
FAQs
This MCCB uses fixed front terminals, so plan panel cutouts and wiring routes accordingly. Ensure conductor sizes match the terminal ratings, apply correct torque values per installation guidance, maintain adequate clearance for heat dissipation, and verify that wiring is accessible from the front for inspection and testing during commissioning.
Rated current (In) is 1250 A, with a rated operational voltage of 690 V AC and rated insulation of 1000 V. The device provides a rated ultimate short-circuit breaking capacity (Icu) up to 60 kA at 690 V, and a rated service short-circuit breaking capacity (Ics) up to 200 kA at 220–230 V, with reduced values at higher voltages.
Yes. It is a Tmax T7 series moulded case circuit breaker with fixed, front-terminal connections designed for direct panel mounting. It supports 3P configurations and is suitable for integration into standard medium-voltage protection schemes, simplifying retrofit projects and new builds alike.
The unit carries IEC standards compliance and is RoHS and REACH declared. Documentation includes CMRT for conflict minerals reporting and TSCA declarations. It also provides CE-related conformity documentation, WEEE considerations, and a clear Declaration of Conformity for Tmax T7 products, supporting regulatory and sustainability targets.
With a mechanical durability rating up to 10,000 cycles and electrical durability around 3,000 cycles, the breaker offers long service life under typical plant duty. Front-terminal wiring reduces maintenance time, while high Icu/Ics ratings minimize unplanned outages. In practice, these features lower downtime costs and extend intervals between spare-part replacements.