ABB 1SDA062965R1 Moulded Case Circuit Breaker - IEC Tmax T7
Part Number: 1SDA062965R1
Quick Summary
ABB 1SDA062965R1 Moulded Case Circuit Breaker is designed to protect power distribution in industrial switchgear and control panels. In practice, uptime is often threatened by fault conditions, difficult maintenance access, and the need for rapid restoration of service; this MCCB addresses those pain points with front-terminal accessibility and robust protection. The solution aligns with IEC standards and environmental declarations, including RoHS and REACH, plus CE conformity and TSCA declarations, ensuring regulatory compliance across sensitive markets. By delivering reliable current control, minimal energy loss, and compatibility with the Tmax T7 family, it enables panel builders and OEMs to reduce maintenance cycles, improve safety, and lower total cost of ownership over the device lifecycle.
Product Information
Extended Description
1SDA062965R1 ABB: C.BREAKER TMAX T7V 1250 FIXED THREE-POLE WITH FRONT TERMINALS AND LEVER OPERATING MECHANISM AND SOLID-STATE RELEASE IN AC PR332/P-LI R 1250
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Product Environmental Information Tmax T7 | Breakers - Packaging disposal information
EAN
8015644655143
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
210 mm
Product Net Height
268 mm
Product Net Depth / Length
154 mm
Product Net Weight
9.7 kg
Package Level 1 Units
1 piece
Package Level 1 Width
280 mm
Package Level 1 Height
350 mm
Package Level 1 Depth / Length
360 mm
Package Level 1 Gross Weight
11.2 kg
Package Level 1 EAN
8015644655143
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable For
T7
Suitable for Product Class
Moulded Case Circuit Breakers
Version
F
Electrical Durability
3000 cycle | 60 cycles per hour
Mechanical Durability
10000 cycle | 60 cycles per hour
Number of Poles
3P
Power Loss
at Rated Operating Conditions per Pole 78.3 W
Rated Current (In)
1250 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 200 kA | (230 V AC) 200 kA | (380 V AC) 150 kA | (400 V AC) 150 kA | (415 V AC) 150 kA | (440 V AC) 130 kA | (500 V AC) 100 kA | (690 V AC) 45 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 15 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 200 kA | (230 V AC) 200 kA | (380 V AC) 150 kA | (400 V AC) 150 kA | (415 V AC) 150 kA | (440 V AC) 130 kA | (500 V AC) 100 kA | (690 V AC) 60 kA
Rated Uninterrupted Current (Iu)
1250 A
Release
PR332/P LI
Release Type
EL
Short-Circuit Performance Level
V
Standards
IEC
Sub-type
T7
Terminal Connection Type
Fixed Circuit-Breakers | Front
Data Sheet, Technical Information
1SDC210015D0201
Declaration of Conformity - CE
EC Declaration of Conformity Tmax T7
GL Certificate
1SDL000163R0056
Wiring Diagram
Wiring diagram T7-T7M
Instructions and Manuals
1SDC210015D0201
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39121100
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature: 3P fixed front-terminal design enables quick installation and straightforward maintenance. Business Impact: Reduces commissioning time and service interruptions, delivering faster project timelines and lower labor costs. Application: Ideal for power distribution in control panels and switchgear where front-access terminals simplify wiring and testing. Feature: Rated current of 1250 A with 690 V AC operation and 1000 V insulation voltage. Business Impact: Supports high-load feeders and transformer protection with a generous safety margin, improving system reliability. Application: Suitable for medium to large industrial feeders and Tmax T7 protection schemes. Feature: Short-circuit performance with Ics up to 200 kA at lower voltages and 60 kA at 690 V, plus Icw 15 kA for 1 s. Business Impact: Enhanced fault clearance capability and reduced equipment damage risk. Application: Critical protection for motors, feeders, and transformer installations. Feature: Release PR332/P LI with EL type and a front-operating lever. Business Impact: Simplifies tripping and resetting, improving operator confidence and response times. Application: Control panels requiring clear mechanical feedback and reliable actuation. Feature: Energy efficiency with 78.3 W power loss per pole. Business Impact: Lower heat generation and cooling requirements, reducing ongoing energy costs. Application: Long-running installations where sustained current is common. Feature: Comprehensive compliance and declarations (CE, RoHS, REACH, CMRT, TSCA). Business Impact: Streamlined procurement and risk management, easing audits and customer disclosures. Application: Global deployments across regulated markets. Feature: Product dimensions and weight (210 mm W x 268 mm H x 154 mm D, 9.7 kg). Business Impact: Predictable space planning and mounting compatibility in standard enclosures. Application: Retrofit projects and new builds in control rooms and MCCs. Feature: WIRING DIAGRAM available and documented documentation (1SDC210015D0201). Business Impact: Reduces field errors and guarantees correct wiring during commissioning. Application: System upgrades and spare-part replacement programs.
Get a Quick Quote for a ABB 1SDA062965R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA062965R1?
Enquire Now
FAQs
This is a fixed front-terminal MCCB designed for panel mounting. Ensure the enclosure provides access to the front terminals, follow the wiring diagram T7‑T7M, and secure connections per the manufacturer torque specs. The 3P configuration and 210 mm width fit standard MCC racks, simplifying retrofit or new builds.
Rated current is 1250 A with rated operational voltage 690 V AC and rated insulation voltage 1000 V. Impulse withstand voltage is 8 kV, and the device delivers short‑circuit protection up to 200 kA at 230 V and 60 kA at 690 V (Ics). Icw is 15 kA for 1 s, and Iu is 1250 A, supporting demanding industrial feeders.
Yes. The product is part of the Tmax T family and uses the PR332/P LI release with an EL type, designed for moulded case circuit protection in transformer and generator installations. The 3P fixed front configuration and performance data align with typical Tmax T7 protection schemes.
The device carries CE conformity, RoHS and REACH declarations, CMRT (Conflict Minerals), and TSCA declarations. Wiring diagrams and official documentation are available (1SDC210015D0201), supporting regulatory compliance and traceability.
Electrical durability is rated at 3000 cycles and mechanical durability at 10000 cycles, with 78.3 W power loss per pole. These metrics indicate longer intervals between maintenance, lower energy waste, and lower lifecycle costs in high‑duty applications such as MCCs and protection schemes.