ABB 1SDA062975R1 Moulded Case Circuit Breaker - LSIG
Part Number: 1SDA062975R1
Quick Summary
ABB 1SDA062975R1 is a high-capacity moulded case circuit breaker for transformer and generator protection in medium-voltage power systems. In demanding industrial environments, space constraints, reliability, and downtime costs demand robust protection and fast fault isolation. This device complies with IEC standards, CE declarations of conformity, and RoHS/REACH compliance, aligning with regulatory and sustainability goals. The 4P front-terminal design and LSIG release support straightforward installation and precise tripping, while the 1250 A rating delivers dependable service for high-load feeders. For teams deploying Tmax T7 family products, this breaker integrates with existing switchgear, reducing total cost of ownership and improving maintenance planning.
Product Information
Extended Description
1SDA062975R1 ABB: C.BREAKER TMAX T7V 1250 FIXED FOUR-POLE WITH FRONT TERMINALS AND LEVER OPERATING MECHANISM AND SOLID-STATE RELEASE IN AC PR332/P-LSIG R 1250
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Product Environmental Information Tmax T7 | Breakers - Packaging disposal information
EAN
8015644655242
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
280 mm
Product Net Height
268 mm
Product Net Depth / Length
154 mm
Product Net Weight
12.5 kg
Package Level 1 Units
1 piece
Package Level 1 Width
360 mm
Package Level 1 Height
350 mm
Package Level 1 Depth / Length
360 mm
Package Level 1 Gross Weight
14 kg
Package Level 1 EAN
8015644655242
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable For
T7
Suitable for Product Class
Moulded Case Circuit Breakers
Version
F
Electrical Durability
3000 cycle | 60 cycles per hour
Mechanical Durability
10000 cycle | 60 cycles per hour
Number of Poles
4P
Power Loss
at Rated Operating Conditions per Pole 78.3 W
Rated Current (In)
1250 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 200 kA | (230 V AC) 200 kA | (380 V AC) 150 kA | (400 V AC) 150 kA | (415 V AC) 150 kA | (440 V AC) 130 kA | (500 V AC) 100 kA | (690 V AC) 45 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 15 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 200 kA | (230 V AC) 200 kA | (380 V AC) 150 kA | (400 V AC) 150 kA | (415 V AC) 150 kA | (440 V AC) 130 kA | (500 V AC) 100 kA | (690 V AC) 60 kA
Rated Uninterrupted Current (Iu)
1250 A
Release
PR332/P LSIG
Release Type
EL
Short-Circuit Performance Level
V
Standards
IEC
Sub-type
T7
Terminal Connection Type
Fixed Circuit-Breakers | Front
Data Sheet, Technical Information
1SDC210015D0201
Declaration of Conformity - CE
EC Declaration of Conformity Tmax T7
GL Certificate
1SDL000163R0056
Wiring Diagram
Wiring diagram T7-T7M
Instructions and Manuals
1SDC210015D0201
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39121100
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature → The device delivers a 1250 A rated current in a four-pole configuration, enabling protection of large feeders and minimizing the need for parallel devices. Business Impact → This reduces footprint and lifecycle costs while improving fault isolation speed. Application → Ideal for transformer and generator protection within medium-voltage Tmax T7 installations. Feature → Front-terminal fixed connection design simplifies wiring and reduces installation time. Business Impact → Faster cabinet assembly, lower field labor costs, and improved reliability from a solid, accessible connection. Application → Suitable for retrofit and new-build switchgear in distributed power systems. Feature → LSIG release with PR332/P mechanism and a robust mechanical/electrical durability profile (3000 cycles electrical, 10000 cycles mechanical). Business Impact → Predictable performance over the lifecycle with minimized maintenance intervals. Application → Critical for continuous operation in industrial plants and substations. Feature → High short-circuit capability (Ics up to 200 kA, Icu up to 60 kA at 690 V) and 8 kV rated impulse withstand. Business Impact → Enhanced protection for high-energy fault scenarios, reducing equipment damage and downtime. Application → Suitable for high-energy transformer and generator protection schemes. Feature → Compliance and sustainability focus (IEC standard, RoHS/REACH, CMRT, TSCA) plus packaging and logistics data. Business Impact → Regulatory risk mitigation and streamlined supplier chain management. Application → Meets global procurement standards for multinational facilities. Feature → Documentation and compatibility resources (Data Sheet 1SDC210015D0201, CE Declaration, Wiring Diagram). Business Impact → Faster commissioning, reduced mismatch risk, and smoother integration with Tmax T7 ecosystems. Application → Used across distribution boards and protection panels in modern substations.
Get a Quick Quote for a ABB 1SDA062975R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA062975R1?
Enquire Now
FAQs
The fixed front-terminal configuration simplifies wiring, reduces installation time, and minimizes field-access challenges. This layout supports clean cable management and faster commissioning in new switchgear assemblies or retrofit projects.
Rated current is 1250 A with a four-pole configuration. Ics reaches up to 200 kA and Icu up to 60 kA at 690 V. Insulation voltage Ui is 1000 V, and the rated impulse withstand Uimp is 8 kV, ensuring robust fault handling for high-energy faults.
Yes. The product carries RoHS and REACH declarations, aligns with CE conformity, and is supported by CMRT for responsible sourcing, helping meet regulatory and ESG objectives across multinational facilities.
It is designed for Tmax T7 protection schemes, transformer and generator protection, and large feeders in medium-voltage switchgear. Its 4P, front-terminal design and LSIG release simplify integration with existing substations and new distribution boards.
Durability specs indicate 3000 electrical cycles and 10000 mechanical cycles, supporting long service life with predictable performance. Power loss is about 78.3 W per pole, guiding thermal and energy management in protected circuits.