ABB 1SDA062980R1 Moulded Case Circuit Breaker - CE

Part Number: 1SDA062980R1
Manufacturer
ABB
Part number
1SDA062980R1

Quick Summary

ABB 1SDA062980R1 is a moulded case circuit breaker designed for industrial power distribution and machine protection. Engineers face challenges coordinating protection with uptime when expanding panels, leading to costly downtime and non-compliant layouts. This device carries CE conformity, GL certification, and RoHS/REACH declarations, underscoring reliability and regulatory compliance across European and global facilities. Designed for SACE Tmax T protection schemes and front-terminal assembly, it streamlines installation, improves maintenance access, and reduces downtime in high-energy industrial environments. With a rated current of 1250 A and a 690 V AC operating voltage, it supports scalable protection for large MCCs and panel boards.

Product Information

Extended Description

1SDA062980R1 ABB: C.BREAKER TMAX T7V 1250 FIXED THREE-POLE WITH FRONT TERMINALS AND STORED ENERGY OPERATING MECHANISM AND SOLID-STATE RELEASE IN AC PR331/P-LSIG R 1250
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Product Environmental Information Tmax T7 | Breakers - Packaging disposal information
Order Code US and Canada
T7MVFB3AE000000XX
EAN
8015644655297
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
210 mm
Product Net Height
268 mm
Product Net Depth / Length
178 mm
Product Net Weight
11 kg
Package Level 1 Units
1 piece
Package Level 1 Width
280 mm
Package Level 1 Height
350 mm
Package Level 1 Depth / Length
360 mm
Package Level 1 Gross Weight
12.5 kg
Package Level 1 EAN
8015644655297
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable For
T7M
Suitable for Product Class
Moulded Case Circuit Breakers
Version
F
Electrical Durability
3000 cycle | 60 cycles per hour
Mechanical Durability
10000 cycle | 60 cycles per hour
Number of Poles
3P
Power Loss
at Rated Operating Conditions per Pole 78.3 W
Rated Current (In)
1250 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 200 kA | (230 V AC) 200 kA | (380 V AC) 150 kA | (400 V AC) 150 kA | (415 V AC) 150 kA | (440 V AC) 130 kA | (500 V AC) 100 kA | (690 V AC) 45 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 15 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 200 kA | (230 V AC) 200 kA | (380 V AC) 150 kA | (400 V AC) 150 kA | (415 V AC) 150 kA | (440 V AC) 130 kA | (500 V AC) 100 kA | (690 V AC) 60 kA
Rated Uninterrupted Current (Iu)
1250 A
Release
PR331/P LSIG
Release Type
EL
Short-Circuit Performance Level
V
Standards
IEC
Sub-type
T7
Terminal Connection Type
Fixed Circuit-Breakers | Front
Data Sheet, Technical Information
1SDC210015D0201
Declaration of Conformity - CE
EC Declaration of Conformity Tmax T7
GL Certificate
1SDL000163R0056
Wiring Diagram
Wiring diagram T7-T7M
Instructions and Manuals
1SDC210015D0201
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
The MCCB features a 3P fixed-front-terminal design and a PR331/P LSIG release, which translates to precise, reliable tripping and effortless maintenance in demanding panels. This capability reduces nuisance trips and improves protection coordination, delivering noticeable uptime gains in heavy-usage environments such as metalworking and chemical processing. The 1250 A rated current paired with 690 V AC operating voltage enables scalable protection for large motor control centers, minimizing space constraints while maintaining robust fault handling in power distribution rooms. The device withstands up to 8 kV impulse, enhancing resilience against transient disturbances common in industrial facilities, translating into fewer outages and safer equipment operation. RoHS and REACH compliance, plus CE conformity, give you confidence in regulatory alignment and easier cross-border procurement. Durability factors, including electrical endurance of 3000 cycles and mechanical endurance of 10000 cycles, support long service life and lower lifecycle costs. Front-terminal wiring simplifies installation and future upgrades, making retrofits faster and less error-prone. Designed to integrate with Tmax T family protection schemes and standard IEC practices, it offers reliable performance in panel boards and MCCs while keeping wiring accessible. The compact footprint and clear labeling aid in space-constrained installations, supporting safer, easier maintenance planning across multiple sites.

Get a Quick Quote for a ABB 1SDA062980R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA062980R1? Enquire Now

FAQs

Install the 3P fixed-front-terminal unit in a suitable enclosure, ensure panel mounting fits the 210 mm width and 268 mm height, connect conductors to the front terminals with the proper torque, and verify the stored-energy mechanism is correctly engaged. Ensure the PR331/P LSIG release aligns with your protection scheme and perform a functional test after wiring to confirm correct tripping and coordination within the IEC framework.
At 690 V, the device offers a high short-circuit rating with Icu up to 60 kA and Ics up to 200 kA depending on system configuration, plus Icw of 15 kA for 1 s. These ratings support safe interruption in demanding applications such as MCCs and transformer protection, reducing the risk of equipment damage during faults.
Yes. The product is part of the SACE Tmax T family and carries the main type designation SACE Tmax T, with suitability for T7M-class protection schemes. Its front-terminal design and PR331/P LSIG release are aligned with Tmax T7M configurations, enabling straightforward integration into existing Tmax protection architectures and standard IEC installation practices.
The MCCB carries CE conformity with a Declaration of Conformity, a GL certificate, and RoHS/REACH declarations. Additional compliance evidence includes CMRT for conflict minerals, TSCA declaration, and WEEE categorization. These certifications help ensure regulatory alignment across major markets and support sustainable procurement.
Electrical durability is rated at 3000 cycles and mechanical durability at 10000 cycles, reducing overhaul frequency. Power loss is 78.3 W per pole, contributing to lower energy waste. Combined with front-terminal wiring for faster installation and longer intervals between replacements, this translates to lower maintenance costs and improved uptime in high-demand applications like MCCs and transformer substations.