ABB 1SDA062982R1 Moulded Case Circuit Breaker - 8 kV Uimp
Part Number: 1SDA062982R1
Quick Summary
ABB 1SDA062982R1 is a three-pole moulded-case circuit breaker used for high-current protection in industrial power distribution. It helps engineers reduce panel space and wiring complexity while delivering reliable trips when faults occur. The device aligns with CE conformity, RoHS declarations, and IEC standards to simplify regulatory approvals and field service. By combining a front-terminal design with a stored-energy operating mechanism and PR332/P LSI release, it supports faster installation, safer maintenance, and consistent performance in demanding environments. In practice, this translates to lower total cost of ownership and improved system reliability for energy-intensive facilities and critical manufacturing lines. This makes it a trusted choice for plant upgrades and new installations where reliability and serviceability matter most.
Product Information
Extended Description
1SDA062982R1 ABB: C.BREAKER TMAX T7V 1250 FIXED THREE-POLE WITH FRONT TERMINALS AND STORED ENERGY OPERATING MECHANISM AND SOLID-STATE RELEASE IN AC PR332/P-LSI R 1250
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Product Environmental Information Tmax T7 | Breakers - Packaging disposal information
Order Code US and Canada
T7MVFB3AR000000XX
EAN
8015644655310
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
210 mm
Product Net Height
268 mm
Product Net Depth / Length
178 mm
Product Net Weight
11 kg
Package Level 1 Units
1 piece
Package Level 1 Width
280 mm
Package Level 1 Height
350 mm
Package Level 1 Depth / Length
360 mm
Package Level 1 Gross Weight
12.5 kg
Package Level 1 EAN
8015644655310
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable For
T7M
Suitable for Product Class
Moulded Case Circuit Breakers
Version
F
Electrical Durability
3000 cycle | 60 cycles per hour
Mechanical Durability
10000 cycle | 60 cycles per hour
Number of Poles
3P
Power Loss
at Rated Operating Conditions per Pole 78.3 W
Rated Current (In)
1250 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 200 kA | (230 V AC) 200 kA | (380 V AC) 150 kA | (400 V AC) 150 kA | (415 V AC) 150 kA | (440 V AC) 130 kA | (500 V AC) 100 kA | (690 V AC) 45 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 15 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 200 kA | (230 V AC) 200 kA | (380 V AC) 150 kA | (400 V AC) 150 kA | (415 V AC) 150 kA | (440 V AC) 130 kA | (500 V AC) 100 kA | (690 V AC) 60 kA
Rated Uninterrupted Current (Iu)
1250 A
Release
PR332/P LSI
Release Type
EL
Short-Circuit Performance Level
V
Standards
IEC
Sub-type
T7
Terminal Connection Type
Fixed Circuit-Breakers | Front
Data Sheet, Technical Information
1SDC210015D0201
Declaration of Conformity - CE
EC Declaration of Conformity Tmax T7
GL Certificate
1SDL000163R0056
Wiring Diagram
Wiring diagram T7-T7M
Instructions and Manuals
1SDC210015D0201
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Three-pole fixed construction with front terminals and a stored-energy operating mechanism (SEOM) provides rapid, reliable tripping when faults occur, reducing downtime and enabling safer maintenance. The integrated PR332/P LSI release enhances selectivity and coordination with downstream protection, improving system reliability in energized switchgear. 1250 A rated current and 690 V AC rated operational voltage support heavy feeders and motor protection in large industrial panels, enabling a single device to manage high load without frequent replacements. The 8 kV rated impulse withstand voltage (Uimp) adds robustness against transients common in plant environments, contributing to lower rupture risk. RoHS and REACH declarations help ensure regulatory compliance across global supply chains, reducing risk during audits and supplier diversification. CE declaration of conformity and IEC standards align the product with international safety requirements, streamlining procurement across regions. Front-terminal connections simplify wiring in switchgear and speed up installation; compact 210 mm width, 268 mm height, and 178 mm depth support space-constrained panels. Electrical durability 3000 cycles at 60 cycles per hour and mechanical durability 10000 cycles at 60 cycles per hour ensure long service life in demanding environments. Packaging details, including 1 piece per package and EAN 8015644655310, enable efficient logistics and clear traceability.
Get a Quick Quote for a ABB 1SDA062982R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA062982R1?
Enquire Now
FAQs
For ABB 1SDA062982R1, use fixed circuit-breaker mounting with front-terminal connections to simplify wiring and enable front-access maintenance. Ensure compatibility with Tmax T switchgear and panel layouts, and observe the 210 mm width, 268 mm height, and 178 mm depth for space planning. Verify correct torque on terminals and proper clearance per IEC guidelines.
Key specs include 1250 A rated current, 690 V AC rated operational voltage, 1000 V rated insulation, and 8 kV Uimp. Short-circuit capabilities vary by voltage: up to 200 kA Ics at lower voltages and 60 kA at 690 V. The device also supports 3P configuration with a PR332/P LSI release for selective protection in feeders and motors.
Yes. The product carries RoHS declarations and a CE conformity declaration, aligning with EU directives and IEC standards. This supports regulatory approvals across multiple regions and simplifies supplier qualification processes for global projects.
Electrical durability is rated at 3000 cycles (60 cycles per hour) and mechanical durability at 10000 cycles (60 cycles per hour). This combination delivers reliable operation under frequent switching, reduces unexpected outages, and extends service life in demanding industrial settings.
The device reduces wiring time with front terminals, provides long-term reliability through high Ics/Icu capabilities, and ensures regulatory compliance with RoHS and CE. These factors together lower maintenance costs, minimize downtime, and improve panel assembly efficiency, especially in energy-intensive facilities and critical manufacturing lines.