ABB 1SDA062986R1 Moulded Case Circuit Breaker - 8kV
Part Number: 1SDA062986R1
Quick Summary
Moulded Case Circuit Breaker is designed to protect industrial power systems by interrupting fault currents in distribution panels. Engineers confront reliability gaps, space constraints, and maintenance challenges in MCC installations, making robust protection essential. This ABB Tmax T7V 4P device carries CE conformity with IEC standards and RoHS/REACH declarations, reinforcing regulatory compliance across global sites. In addition to a stored-energy mechanism and front-terminal fixed installation, the 1250 A rating supports high-demand feeders while maintaining rapid response under short-circuit events. For procurement, the combination of compact footprint, clear documentation, and compatibility with classic Tmax T7 accessories translates to faster commissioning, reduced downtime, and lower lifecycle costs. ABB Sace design lineage informs ongoing reliability and serviceable operation.
Product Information
Extended Description
1SDA062986R1 ABB: C.BREAKER TMAX T7V 1250 FIXED FOUR-POLE WITH FRONT TERMINALS AND STORED ENERGY OPERATING MECHANISM AND SOLID-STATE RELEASE IN AC PR231/P-LS/I R 1250
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Product Environmental Information Tmax T7 | Breakers - Packaging disposal information
EAN
8015644655358
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
280 mm
Product Net Height
268 mm
Product Net Depth / Length
178 mm
Product Net Weight
14 kg
Package Level 1 Units
1 piece
Package Level 1 Width
360 mm
Package Level 1 Height
350 mm
Package Level 1 Depth / Length
360 mm
Package Level 1 Gross Weight
15.5 kg
Package Level 1 EAN
8015644655358
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable For
T7M
Suitable for Product Class
Moulded Case Circuit Breakers
Version
F
Electrical Durability
3000 cycle | 60 cycles per hour
Mechanical Durability
10000 cycle | 60 cycles per hour
Number of Poles
4P
Power Loss
at Rated Operating Conditions per Pole 78.3 W
Rated Current (In)
1250 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 200 kA | (230 V AC) 200 kA | (380 V AC) 150 kA | (400 V AC) 150 kA | (415 V AC) 150 kA | (440 V AC) 130 kA | (500 V AC) 100 kA | (690 V AC) 45 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 15 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 200 kA | (230 V AC) 200 kA | (380 V AC) 150 kA | (400 V AC) 150 kA | (415 V AC) 150 kA | (440 V AC) 130 kA | (500 V AC) 100 kA | (690 V AC) 60 kA
Rated Uninterrupted Current (Iu)
1250 A
Release
PR231/P-LS/I
Release Type
EL
Short-Circuit Performance Level
V
Standards
IEC
Sub-type
T7
Terminal Connection Type
Fixed Circuit-Breakers | Front
Data Sheet, Technical Information
1SDC210015D0201
Declaration of Conformity - CE
EC Declaration of Conformity Tmax T7
GL Certificate
1SDL000163R0056
Wiring Diagram
Wiring diagram T7-T7M
Instructions and Manuals
1SDC210015D0201
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
High current handling with In 1250 A and a 4P fixed-front terminal design supports large feeders and aggressive protection in demanding environments, reducing upstream miscoordination and improving uptime. This translates to measurable business value in manufacturing lines and data centers where protection speed and reliability drive overall equipment effectiveness. The device delivers robust short-circuit performance (Ics up to 200 kA at low voltages and up to 60 kA at 690 V), enabling safer fault clearance across critical feeders and reducing arc energy exposure for connected equipment. The stored-energy operating mechanism speeds reset after trips, improving maintenance efficiency and lowering downtime during servicing. RoHS and REACH declarations, along with CMRT and TSCA compliance, simplify global procurement and sustainability reporting, while documentation such as wiring diagrams and data sheets shorten commissioning time. Compatibility with Tmax T7 accessories and a front-terminal, fixed design supports rapid installation and scalable protection for evolving electrical rooms. Power loss of 78.3 W per pole helps lower heat generation in high-density switchgear, contributing to overall energy efficiency and reduced cooling costs in large installations. The 1250 A rating, 690 V AC operation, and 8 kV impulse withstand provide a precision, reliability, and safety profile that aligns with IEC standards and industry best practices for mission-critical protection.
Get a Quick Quote for a ABB 1SDA062986R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA062986R1?
Enquire Now
FAQs
This ABB 1SDA062986R1 in Tmax T7V MCCB applications requires a 4P fixed-front terminal mount in a ventilated enclosure rated for 690 V AC. Confirm space for a 178 mm depth, 280 mm width, and 268 mm height, plus the 1250 A rating. Use correct accessories, follow wiring diagrams, and ensure stored-energy mechanism is safely discharged during maintenance.
This device delivers 1250 A rated current and 690 V AC rated operational voltage, with an 8 kV impulse withstand and 1000 V insulation. It provides Ics up to 200 kA at low voltages and up to 60 kA at 690 V, Icw 15 kA for 1 s, and Iu 1250 A. It uses a PR231/P-LS/I release and 4P front-terminal configuration.
Yes. The product carries RoHS information and REACH Declaration for ABB Sace circuit breakers, along with CMRT and TSCA declarations. It also provides the EC Declaration of Conformity for Tmax T7 and a GL certificate. This compliance supports global procurement, sustainability reporting, and regulatory alignment across multiple sites. RoHS status complies with EU Directive 2011/65/EU and amendment 2015/863. This helps auditors and procurement teams.
Suitable for large feeders and motor protection in heavy industry, data centers, and process plants. The 4P fixed front-terminal design enables quick wiring in compact MCC rooms, while the Tmax T7 family compatibility supports easy spares and accessories. With 690 V AC operation and high short-circuit ratings, it protects feeders and switchgear against faults while minimizing downtime.
The product references documentation 1SDC210015D0201 including data sheets, wiring diagrams, and manuals; an EC Declaration of Conformity, GL certificate, and WEEE packaging guidance are provided. EAN 8015644655358 and packaging details support logistics, while the device's compatibility with Tmax T7 accessories simplifies installation and service. For after-sales support, ABB Sace provides field data and spare-part information.