ABB 1SDA063001R1 Moulded Case Circuit Breaker - 8 kV
Part Number: 1SDA063001R1
Quick Summary
Moulded Case Circuit Breaker is designed for high-current protection in switchgear applications. Engineers often face slow fault isolation and challenging maintenance in crowded panels, which can extend downtime and raise operating costs. This ABB Tmax T4P device delivers CE conformity, IEC standards alignment, and RoHS/REACH compliance to support regulatory commitments and sustainability goals. With a 1600 A rating, four poles, and front-terminal installation, it integrates seamlessly into control rooms and distribution boards, improving uptime while reducing wiring complexity and maintenance time.
Product Information
Extended Description
1SDA063001R1 ABB: C.BREAKER TMAX T7S 1600 FIXED FOUR-POLE WITH FRONT TERMINALS AND LEVER OPERATING MECHANISM AND SOLID-STATE RELEASE IN AC PR231/P-I R 1600
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Product Environmental Information Tmax T7 | Breakers - Packaging disposal information
EAN
8015644655501
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
280 mm
Product Net Height
268 mm
Product Net Depth / Length
154 mm
Product Net Weight
12.5 kg
Package Level 1 Units
1 piece
Package Level 1 Width
360 mm
Package Level 1 Height
350 mm
Package Level 1 Depth / Length
360 mm
Package Level 1 Gross Weight
14 kg
Package Level 1 EAN
8015644655501
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable For
T7
Suitable for Product Class
Moulded Case Circuit Breakers
Version
F
Electrical Durability
2000 cycle | 60 cycles per hour
Mechanical Durability
10000 cycle | 60 cycles per hour
Number of Poles
4P
Power Loss
at Rated Operating Conditions per Pole 77 W
Rated Current (In)
1600 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 85 kA | (230 V AC) 85 kA | (380 V AC) 50 kA | (400 V AC) 50 kA | (415 V AC) 50 kA | (440 V AC) 50 kA | (500 V AC) 40 kA | (690 V AC) 30 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 20 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 85 kA | (230 V AC) 85 kA | (380 V AC) 50 kA | (400 V AC) 50 kA | (415 V AC) 50 kA | (440 V AC) 50 kA | (500 V AC) 40 kA | (690 V AC) 30 kA
Rated Uninterrupted Current (Iu)
1600 A
Release
PR231/P-I
Release Type
EL
Short-Circuit Performance Level
S
Standards
IEC
Sub-type
T7
Terminal Connection Type
Fixed Circuit-Breakers | Front
Data Sheet, Technical Information
1SDC210015D0201
Declaration of Conformity - CE
EC Declaration of Conformity Tmax T7
GL Certificate
1SDL000163R0055
Instructions and Manuals
1SDC210015D0201
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39121100
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Front-terminal, fixed 4P design enables safer wiring and faster installation, reducing project lead times and panel space requirements while boosting reliability in dense switchgear. The 1600 A rated current and 690 V AC operating voltage provide robust protection for high-demand loads, supporting continuity of service in transformers and generation interfaces. PR231/P-I release, solid-state protection options, and a compact Tmax T family footprint translate to simpler commissioning, easier testing, and fewer spare parts needed over the lifecycle. With an 8 kV rated impulse withstand voltage and 85 kA short-circuit capability at common utility voltages, the MCCB delivers dependable fault clearance, minimizing downtime and equipment damage during faults in critical networks. The product also aligns with RoHS, REACH, and CMRT declarations, ensuring regulatory compliance and responsible sourcing across regional supply chains. Industry-specific considerations such as maintenance windows, lifecycle cost reduction, and safe front-access servicing are addressed by its modular design and clear documentation, enabling technicians to plan replacements and fault analysis with confidence.
Get a Quick Quote for a ABB 1SDA063001R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA063001R1?
Enquire Now
FAQs
For ABB 1SDA063001R1, ensure front-terminal mounting is used to simplify wiring within compact switchgear and panels. Verify four-pole configuration and correct locking of the PR231/P-I release. Check clearances and heat dissipation in the enclosure, and plan for 690 V AC operating voltage and 1600 A nominal current to prevent nuisance trips and ensure safe, fast maintenance access.
Key ratings include a rated current of 1600 A, rated operational voltage 690 V AC, rated insulation voltage 1000 V, and rated impulse withstand voltage of 8 kV. It provides a short-time withstand current of 20 kA for 1 s, a service short-circuit breaking capacity of up to 85 kA (depending on voltage), and a 4P configuration with front-terminal connections.
Yes. The product carries a CE Declaration of Conformity for Tmax T, RoHS declarations for ABB Sace circuit breakers, and REACH compliance statements. It also references CMRT for conflict minerals reporting and TSCA-related declarations, aligning with modern compliance expectations across European and North American markets.
Ideal for transformer protection, generator protection, and distribution switchgear in industrial facilities, power plants, and large commercial complexes. The 4P design and high current capacity suit applications with heavy motor loads and critical process equipment, while front-terminal access and robust Icu/Icw ratings support reliable protection and fast fault isolation in demanding environments.
Plan periodic inspections and functional testing of the PR231/P-I release, verify front-terminal integrity, and monitor insulation and seal conditions in the enclosure. The 2000 electrical durability cycles and 10000 mechanical durability cycles guide replacement timing. Keep spare contacts, release units, and wiring harnesses available to minimize downtime during scheduled maintenance or fault analysis.