ABB 1SDA063002R1 Moulded Case Circuit Breaker - IEC
Part Number: 1SDA063002R1
Quick Summary
ABB 1SDA063002R1 is a Tmax T7S moulded case circuit breaker for high‑current power distribution. Engineers often struggle with space constraints, wiring access, and reliable protection in demanding MCC environments. This device is CE‑conformant, RoHS and REACH compliant, and offers front terminals with a front‑operating lever for easy maintenance. With robust protection for transformers, MCCs, and large distribution boards, it delivers dependable operation while enabling compact layouts and reduced installation time.
Product Information
Extended Description
1SDA063002R1 ABB: C.BREAKER TMAX T7S 1600 FIXED FOUR-POLE WITH FRONT TERMINALS AND LEVER OPERATING MECHANISM AND SOLID-STATE RELEASE IN AC PR231/P-LS/I R 1600
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
SCIP
f5ae75b3-19f3-4670-89b9-1daa73df72f4 Italy (IT)
Simplified SCIP
15eabed6-d74f-4c07-9291-0eaa2e769d21 Germany (DE) | 4b0b9961-ec16-4682-9d6e-0987154291ea Greece (GR) | 7203af46-7612-4f17-b2a2-398bbc532cd2 Spain (ES) | d0ba7ec5-8fe4-4825-ad07-2315c1440423 Netherlands (NL) | 5cf08004-747f-487a-9a4b-0cbad3340926 France (FR) | 39a382b2-15ff-4462-841a-aa646ce8ed14 Netherlands (NL) | e2c88925-33d3-4dc9-bb43-eea6566c57cb Germany (DE) | 13903a9c-0f45-4bc0-a176-b0a948fd5e4a Germany (DE) | c657aa44-6dbb-4df6-a8fc-3c7a4158f6c5 France (FR) | 0cedd7a8-3533-42ff-b256-d471ba98fbdc Sweden (SE) | df57f470-a4ae-49db-8569-e076a2d4dc5b Norway (NO) | 621efefe-63e6-41b5-8ba6-42f2bdcad513 Finland (FI) | 0155cc00-e4ee-4fc9-8faa-ffb389ebf277 Poland (PL) | 86d8703d-9c08-4135-aed8-bd8cab52a3c4 Netherlands (NL) | 5aa19561-f1ef-4b07-a54a-981888a5beea Germany (DE) | cd11357e-5252-4441-9aeb-6014b76168ed Denmark (DK) | 9f62d16b-4790-4890-ac7c-8364a401e277 Germany (DE) | 004793bc-51f6-4b30-8370-122b13fc6c81 Poland (PL) | 5785731e-d2ff-44dd-a777-9cac30709a38 Netherlands (NL) | 3937e7f9-f574-483a-9952-d3c2b7906443 Netherlands (NL) | fb00c32f-1dcc-4b16-83f9-e6dea08f5c54 Croatia (HR) | adf2c125-7d4e-4160-b30e-49a35d4ea066 Czech Republic (CZ) | 0fbd6065-e778-4f33-abce-05b27a704697 Sweden (SE) | a9d392cc-37c2-449a-8449-4b4d58844edc Poland (PL) | ca8fa6a5-6d86-4f54-a39b-7c0e1c8dd391 Portugal (PT) | 9d6b4551-bbb4-40e7-99fa-68fc9d299dca Bulgaria (BG) | e3a78167-284e-4a15-adc5-6ed0067f4d72 Estonia (EE)
Environmental Information
Product Environmental Information Tmax T7 | Breakers - Packaging disposal information
EAN
8015644655518
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
280 mm
Product Net Height
268 mm
Product Net Depth / Length
154 mm
Product Net Weight
17.619 kg
Package Level 1 Units
1 piece
Package Level 1 Width
360 mm
Package Level 1 Height
350 mm
Package Level 1 Depth / Length
360 mm
Package Level 1 Gross Weight
18.546 kg
Package Level 1 EAN
8015644655518
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable For
T7
Suitable for Product Class
Moulded Case Circuit Breakers
Version
F
Electrical Durability
2000 cycle | 60 cycles per hour
Mechanical Durability
10000 cycle | 60 cycles per hour
Number of Poles
4P
Power Loss
at Rated Operating Conditions per Pole 77 W
Rated Current (In)
1600 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 85 kA | (230 V AC) 85 kA | (380 V AC) 50 kA | (400 V AC) 50 kA | (415 V AC) 50 kA | (440 V AC) 50 kA | (500 V AC) 40 kA | (690 V AC) 30 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 20 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 85 kA | (230 V AC) 85 kA | (380 V AC) 50 kA | (400 V AC) 50 kA | (415 V AC) 50 kA | (440 V AC) 50 kA | (500 V AC) 40 kA | (690 V AC) 30 kA
Rated Uninterrupted Current (Iu)
1600 A
Release
PR231/P-LS/I
Release Type
EL
Short-Circuit Performance Level
S
Standards
IEC
Sub-type
T7
Terminal Connection Type
Fixed Circuit-Breakers | Front
Data Sheet, Technical Information
1SDC210015D0201
Declaration of Conformity - CE
EC Declaration of Conformity Tmax T7
GL Certificate
1SDL000163R0055
Instructions and Manuals
1SDC210015D0201
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39121100
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature → Business Impact → Application: Four‑pole, fixed front terminals, and a 1600 A rated current enable compact yet high‑capacity protection for MCCs and switchgear, reducing panel size and wiring complexity while improving fault isolation. Application: Main feeders and transformer protection in industrial facilities. Feature → Business Impact → Application: PR231/P‑LS/I release provides selective, fast tripping under short‑circuit events, lowering downtime and equipment damage risk in critical lines. Application: Transformer feeders and vibrating loads in process industries. Feature → Business Impact → Application: High short‑circuit withstand (Ics up to 85 kA, Ui 1000 V, Uimp 8 kV) ensures reliable protection for diverse voltages, supporting compliance with IEC standards. Application: Industrial power distribution at 690 V AC. Feature → Business Impact → Application: RoHS and REACH declarations, CMRT and SCIP identifiers minimize regulatory risk and simplify supplier compliance for global manufacturing. Application: Global rollout of MCCBs. Feature → Business Impact → Application: 77 W per pole power loss with durable mechanical life (10000 cycles) reduces operating costs and maintenance frequency. Application: Continuous operation in heavy‑duty environments.
Get a Quick Quote for a ABB 1SDA063002R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA063002R1?
Enquire Now
FAQs
ABB 1SDA063002R1 uses fixed front terminals, enabling straightforward wiring access and cleaner panel layouts. When planning installation, verify clearance for front accessibility, ensure proper torque on terminals, and accommodate cable routing to avoid strain. The front‑termination design supports faster assembly and easier maintenance in compact switchgear and MCC enclosures.
The device offers up to 85 kA short‑circuit withstand (Ics) and up to 85 kA ultimate breaking capacity (Icu) across applicable voltages, with a rated impulse withstand up to 8 kV. This enables reliable fault interruption in demanding 690 V AC distribution while maintaining safety margins and minimizing damage to downstream equipment.
Yes. Its 690 V AC rating, 1000 V insulation voltage, and front‑mounted PR231/P‑LS/I release are well suited for transformer feeders and MCC protection. The device supports robust short‑circuit protection, rapid tripping, and reliable operation in transformer adjacent circuits, aligning with IEC and industry best practices for transformer protection.
This Tmax T7S MCCB carries CE conformity and is RoHS and REACH declared, with CMRT and SCIP identifiers for responsible sourcing. It includes a DoC/Conformity declaration, GL certification, and standard installation manuals to support global procurement and regulatory audits across manufacturing sites.
With 10000 mechanical durability cycles and 2000 electrical durability cycles, the 1SDA063002R1 delivers extended service life in demanding environments. Low operating power loss (77 W per pole) reduces heat and energy waste, while front‑terminals simplify servicing. These factors translate to lower maintenance costs, reduced downtime, and improved overall equipment effectiveness.