ABB 1SDA063010R1 Moulded Case Circuit Breaker - Icu 85 kA
Part Number: 1SDA063010R1
Quick Summary
ABB 1SDA063010R1 Moulded Case Circuit Breaker is a high‑capacity protection device for industrial power distributions up to 690 V AC. Engineers often struggle with reliability and maintenance in dense switchgear, where complex wiring and manual trips slow projects. This MCCB aligns with CE conformity, RoHS compliance, and SCIP CMRT reporting, helping sustain regulatory compliance across regions. By pairing a front-terminal design with a stored-energy operating mechanism and a 1600 A rating, it enables safer, faster commissioning and lower lifecycle costs for critical feeders in manufacturing, data centers, and process plants.
Product Information
Extended Description
1SDA063010R1 ABB: C.BREAKER TMAX T7S 1600 FIXED THREE-POLE WITH FRONT TERMINALS AND STORED ENERGY OPERATING MECHANISM AND SOLID-STATE RELEASE IN AC PR231/P-LS/I R 1600
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
SCIP
488a5172-8d1a-4663-bc07-90b399071309 Italy (IT)
Simplified SCIP
7726390a-d0c7-4b82-8751-e397aaa97ecf Germany (DE) | 540373bf-4f51-4757-81e4-5774e81efc97 Norway (NO) | cb327c4a-b912-4646-8752-47e5908b938d Finland (FI) | 75342d0a-2743-4a33-9703-94a2d5072839 Spain (ES) | 13d3d07d-bb52-4e8d-a581-ad4d76bd0e49 Netherlands (NL) | 5ca4efe5-49b0-42c8-8ab6-60fc851a0665 Germany (DE) | 0ff4616e-67ba-40a3-bb84-aea4bbb69b93 Sweden (SE) | 30304210-9b47-4c19-989f-2585ca7580d4 France (FR) | 76ca9f7d-3666-4afd-8303-723729ab6c55 Germany (DE) | de90cd90-6fa1-4c1b-b056-dd5f9429e421 Netherlands (NL) | af8197ea-60fb-4775-92bf-0075b654a003 France (FR) | d74bb24e-d16b-45cf-8640-d8e7690a5667 Estonia (EE) | 8dbca767-3eec-402d-bf77-d7717099e5e4 Greece (GR) | 12914a44-430c-49fe-be67-358fdbba3937 Bulgaria (BG) | 704b7a47-260b-4b5d-9a8c-123362044e70 Portugal (PT) | 66421bab-715b-4a08-85b4-481f43bb48a3 Sweden (SE) | 25d7f573-6c44-423c-9bef-8fda055f8fc4 Poland (PL) | 1655ec0e-733e-4d50-a00e-16f57bbbcfa7 Netherlands (NL) | 5513df25-e182-438e-9012-e55e65a424b2 Netherlands (NL) | 7fd9c111-3caa-46fd-943e-25185b7ab732 Czech Republic (CZ) | f383b0ab-ec08-4465-9a2b-44e744d8b7e7 Croatia (HR) | b8d81a71-200d-441a-a594-a2940f7c798e Poland (PL) | 6433c27f-0213-4fc5-a922-ba7cd0ac1023 Germany (DE) | 4a581c2b-d7d0-46dd-ac87-5cfe9382d89d Germany (DE) | 252a70a4-a4d4-470f-a706-64a6b0faf1ef Netherlands (NL) | 7ab9818c-c7b7-41d6-a19f-452e26bb8ba2 Denmark (DK) | df5a2365-95e7-443b-a27a-1ce414c2a1ab Poland (PL)
Environmental Information
Product Environmental Information Tmax T7 | Breakers - Packaging disposal information
EAN
8015644655594
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
210 mm
Product Net Height
268 mm
Product Net Depth / Length
178 mm
Product Net Weight
14.481 kg
Package Level 1 Units
1 piece
Package Level 1 Width
280 mm
Package Level 1 Height
350 mm
Package Level 1 Depth / Length
360 mm
Package Level 1 Gross Weight
15.243 kg
Package Level 1 EAN
8015644655594
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable For
T7M
Suitable for Product Class
Moulded Case Circuit Breakers
Version
F
Electrical Durability
2000 cycle | 60 cycles per hour
Mechanical Durability
10000 cycle | 60 cycles per hour
Number of Poles
3P
Power Loss
at Rated Operating Conditions per Pole 77 W
Rated Current (In)
1600 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 85 kA | (230 V AC) 85 kA | (380 V AC) 50 kA | (400 V AC) 50 kA | (415 V AC) 50 kA | (440 V AC) 50 kA | (500 V AC) 40 kA | (690 V AC) 30 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 20 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 85 kA | (230 V AC) 85 kA | (380 V AC) 50 kA | (400 V AC) 50 kA | (415 V AC) 50 kA | (440 V AC) 50 kA | (500 V AC) 40 kA | (690 V AC) 30 kA
Rated Uninterrupted Current (Iu)
1600 A
Release
PR231/P-LS/I
Release Type
EL
Short-Circuit Performance Level
S
Standards
IEC
Sub-type
T7
Terminal Connection Type
Fixed Circuit-Breakers | Front
Data Sheet, Technical Information
1SDC210015D0201
Declaration of Conformity - CE
EC Declaration of Conformity Tmax T7
GL Certificate
1SDL000163R0055
Instructions and Manuals
1SDC210015D0201
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature: 3P fixed front-terminal design with stored-energy operating mechanism and PR231/P-LS/I release. Business Impact: Simplified wiring, faster installation, and enhanced operator safety during maintenance. Application: Main feeders and distribution panels in industrial facilities. Feature: 690 V AC rated insulation with Ui 1000 V and Uimp 8 kV. Business Impact: Higher surge tolerance and reliable insulation coordination, reducing nuisance trips and equipment damage. Application: Motor starter circuits and transformer protection in harsh environments. Feature: High fault withstand with Icu 85 kA, Ics 85 kA, and Icw 20 kA for 1 s. Business Impact: Superior fault interruption capability minimizes downstream disruption and protects critical loads. Application: Data centers, processing lines, and heavy industry power rails. Feature: Front-terminal mounting and compact footprint with documented dimensions and weight. Business Impact: Easier retrofits and panel space optimization, lowering installation and retrofit costs. Application: Retrofitting older MCCB assemblies in existing switchgear. Feature: Regulatory and technical documentation including CE, RoHS, SCIP, CMRT, and DoC references. Business Impact: Streamlined procurement, audit readiness, and sustainable sourcing across global supply chains. Application: Global manufacturing networks and multi-site projects. Note: Power loss of 77 W per pole and 1600 A rated current support energy efficiency goals and reliable long-term operation in continuous duty environments.
Get a Quick Quote for a ABB 1SDA063010R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA063010R1?
Enquire Now
FAQs
This ABB MCCB uses fixed front-terminal connections designed for quick, secure mounting in 3P switchgear. Its front-terminal configuration simplifies wiring runs and enables straightforward retrofit into existing panels without extensive rework.
The device is rated for 690 V AC with Ui 1000 V and Uimp 8 kV. It provides IN 1600 A, Icu 85 kA, Ics 85 kA, and Icw 20 kA for 1 s, enabling high fault withstand and reliable interruption for demanding loads.
Yes. With 3P construction, front terminals, and high breaking capacity, it is well-suited for transformer protection and main feeder duties in industrial plants, data centers, and processing facilities, aligning with Tmax T7 family characteristics.
The unit is CE certified with a DoC, RoHS compliant, and supports SCIP/CMRT reporting. Additional declarations include REACH, TSCA, and CMRT, which facilitate regulatory compliance and supplier audits.
Stored-energy release and front-terminal wiring reduce maintenance time and risk during testing. The 1600 A rating and high fault current capabilities minimize downtime during faults, contributing to lower total cost of ownership over the equipment lifecycle.