ABB 1SDA063017R1 Moulded Case Circuit Breaker - PR231/P-I

Part Number: 1SDA063017R1
Manufacturer
ABB
Part number
1SDA063017R1

Quick Summary

ABB 1SDA063017R1 Moulded Case Circuit Breaker protects power distribution from fault currents in heavy industrial systems. Engineers often wrestle with bulky protection gear, lengthy servicing, and gaps in short-circuit protection for 690 V networks. It complies with IEC standards and CE conformity, backed by RoHS and REACH declarations. Designed for Tmax T families with a front-terminal, fixed-mount arrangement, it supports scalable protection and quick servicing, lowering downtime. This combination translates into predictable reliability, simpler spares management, and lower total cost of ownership.

Product Information

Extended Description

1SDA063017R1 ABB: C.BREAKER TMAX T7S 1600 FIXED FOUR-POLE WITH FRONT TERMINALS AND STORED ENERGY OPERATING MECHANISM AND SOLID-STATE RELEASE IN AC PR231/P-I R 1600
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Product Environmental Information Tmax T7 | Breakers - Packaging disposal information
EAN
8015644655662
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
280 mm
Product Net Height
268 mm
Product Net Depth / Length
178 mm
Product Net Weight
14 kg
Package Level 1 Units
1 piece
Package Level 1 Width
360 mm
Package Level 1 Height
350 mm
Package Level 1 Depth / Length
360 mm
Package Level 1 Gross Weight
15.5 kg
Package Level 1 EAN
8015644655662
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable For
T7M
Suitable for Product Class
Moulded Case Circuit Breakers
Version
F
Electrical Durability
2000 cycle | 60 cycles per hour
Mechanical Durability
10000 cycle | 60 cycles per hour
Number of Poles
4P
Power Loss
at Rated Operating Conditions per Pole 77 W
Rated Current (In)
1600 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 85 kA | (230 V AC) 85 kA | (380 V AC) 50 kA | (400 V AC) 50 kA | (415 V AC) 50 kA | (440 V AC) 50 kA | (500 V AC) 40 kA | (690 V AC) 30 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 20 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 85 kA | (230 V AC) 85 kA | (380 V AC) 50 kA | (400 V AC) 50 kA | (415 V AC) 50 kA | (440 V AC) 50 kA | (500 V AC) 40 kA | (690 V AC) 30 kA
Rated Uninterrupted Current (Iu)
1600 A
Release
PR231/P-I
Release Type
EL
Short-Circuit Performance Level
S
Standards
IEC
Sub-type
T7
Terminal Connection Type
Fixed Circuit-Breakers | Front
Data Sheet, Technical Information
1SDC210015D0201
Declaration of Conformity - CE
EC Declaration of Conformity Tmax T7
GL Certificate
1SDL000163R0055
Instructions and Manuals
1SDC210015D0201
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature → Business Impact → Application: High current capability of 1600 A in a 4-pole configuration enables protection of large feeders and equipment without multiple panels, reducing cabinet count and installation time in power distribution basements and plant rooms. This translates to faster commissioning and lower installation costs for heavy-duty drives and transformers. Feature → Front-terminal, fixed design enables straightforward wiring, safer maintenance, and easier retrofits in existing switchboards, minimizing downtime during filter and main feeder upgrades. Application: Deployment in switchgear and motor control centers for steel, chemical, and mining facilities where rapid serviceability is essential. Feature → PR231/P-I release provides reliable tripping logic with stored energy mechanisms, ensuring accurate fault interruption and safety during startup sequences. Application: Critical protection for primary feeders feeding Tmax T7 series modules in high-energy environments. Feature → High short-circuit ratings (Ics up to 85 kA, Icu up to 85 kA depending on voltage) and 690 V AC withstand enable robust transformer/generator protection. Application: Transformer protection and generator bus-tie protection with IEC compliance. Feature → RoHS and REACH declarations plus CMRT and TSCA disclosures support global sourcing and supply-chain compliance. Application: Procurement and compliance workflows for multinational manufacturing sites. Feature → Power loss of 77 W per pole under rated conditions supports thermal management planning and energy efficiency considerations. Application: End-user design optimization for cooling and energy budgeting in large MCCB installations.

Get a Quick Quote for a ABB 1SDA063017R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA063017R1? Enquire Now

FAQs

The device is a fixed, front-terminal MCCB with four poles (4P) designed for easy front wiring. Its footprint supports straightforward installation into standard switchgear, reducing field wiring time and enabling safer, faster maintenance in high-current applications.
Rated current is 1600 A, Rated Operational Voltage 690 V AC, Rated Insulation Voltage 1000 V, Uimp 8 kV, Ics up to 85 kA across applicable voltages, and Icw 20 kA for 1 s. It also lists a power loss of 77 W per pole under rated conditions, aiding thermal design and reliability planning.
Yes. The unit carries RoHS and REACH declarations, CE conformity, and related product declarations. Additional certifications include CMRT and TSCA where applicable, supporting global procurement and regulatory compliance across multiple regions.
Ideal for power distribution and protection of heavy feeders, transformer and generator protection in Tmax T installations. Its 4P, 1600 A rating with front-terminal design suits large switchgear, motor control centers, and transformer protection schemes in industrial plants.
Front-terminal wiring simplifies installation, reduces commissioning time, and eases future upgrades. The robust front-access design combined with high Ics/Icu ratings enhances reliability, minimizes downtime, and supports longer service intervals—yielding lower total cost of ownership in high-demand environments.