ABB 1SDA063024R1 Moulded Case Circuit Breaker - 8kV

Part Number: 1SDA063024R1
Manufacturer
ABB
Part number
1SDA063024R1

Quick Summary

Moulded Case Circuit Breaker ABB is designed to protect and control power distribution in industrial plants. For engineers facing downtime and protection gaps, this model delivers high current handling with reliable front-terminal installation and stored-energy release. The solution aligns with IEC standards while carrying RoHS and REACH declarations, plus CE conformity. In practice, it enables compact panels, faster commissioning, and safer operation, supporting Tmax T7 system integration with a 4P design and 690 V AC capability. This combination reduces maintenance intervals and improves system reliability, while offering compatibility with PR332/P-LSIRc releases for enhanced protection and ease of service.

Product Information

Extended Description

1SDA063024R1 ABB: C.BREAKER TMAX T7S 1600 FIXED FOUR-POLE WITH FRONT TERMINALS AND STORED ENERGY OPERATING MECHANISM AND SOLID-STATE RELEASE IN AC PR332/P-LSIRc R 1600
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Product Environmental Information Tmax T7 | Breakers - Packaging disposal information
EAN
8015644655730
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
280 mm
Product Net Height
268 mm
Product Net Depth / Length
178 mm
Product Net Weight
14 kg
Package Level 1 Units
1 piece
Package Level 1 Width
360 mm
Package Level 1 Height
350 mm
Package Level 1 Depth / Length
360 mm
Package Level 1 Gross Weight
15.5 kg
Package Level 1 EAN
8015644655730
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable For
T7M
Suitable for Product Class
Moulded Case Circuit Breakers
Version
F
Electrical Durability
2000 cycle | 60 cycles per hour
Mechanical Durability
10000 cycle | 60 cycles per hour
Number of Poles
4P
Power Loss
at Rated Operating Conditions per Pole 77 W
Rated Current (In)
1600 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 85 kA | (230 V AC) 85 kA | (380 V AC) 50 kA | (400 V AC) 50 kA | (415 V AC) 50 kA | (440 V AC) 50 kA | (500 V AC) 40 kA | (690 V AC) 30 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 20 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 85 kA | (230 V AC) 85 kA | (380 V AC) 50 kA | (400 V AC) 50 kA | (415 V AC) 50 kA | (440 V AC) 50 kA | (500 V AC) 40 kA | (690 V AC) 30 kA
Rated Uninterrupted Current (Iu)
1600 A
Release
PR332/P-LSIRc
Release Type
EL
Short-Circuit Performance Level
S
Standards
IEC
Sub-type
T7
Terminal Connection Type
Fixed Circuit-Breakers | Front
Data Sheet, Technical Information
1SDC210015D0201
Declaration of Conformity - CE
EC Declaration of Conformity Tmax T7
GL Certificate
1SDL000163R0055
Instructions and Manuals
1SDC210015D0201
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature → Business Impact → Application: 1) Four-pole front-terminal fixed design enables straightforward installation and safer wiring practices in crowded switchboards, reducing panel footprint and assembly time; application: large-scale distribution panels in manufacturing facilities. 2) 1600 A rated current with high short-circuit capability provides robust protection for feeders and transformers, lowering risk of arc-flash events and limiting downstream downtime in critical processes; application: Tmax T7 protection in large power networks. 3) PR332/P-LSIRc release with stored-energy mechanism improves reliability and trip accuracy, minimizing nuisance trips and maintenance costs; application: high-demand capacitor banks and generator interconnections. 4) 690 V AC operating voltage and 8 kV rated impulse withstand voltage (Uimp) meet industrial safety standards, supporting compliant protection in diverse environments; application: motor drives and transformer protection. 5) RoHS and REACH declarations, CE conformity ensure compliance across regional supply chains, simplifying procurement and audit processes; application: global manufacturing and multi-site deployments.

Get a Quick Quote for a ABB 1SDA063024R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA063024R1? Enquire Now

FAQs

This four-pole fixed circuit breaker is designed for front-terminal installation, enabling easy access wiring and reduced panel depth. For retrofit projects, ensure existing busbar spacing matches the 280 mm width and 178 mm depth, and verify clearance for maintenance and lever operation. The unit supports standard Tmax T7 configurations and PR332/P-LSIRc release.
Key specs include a rated current I_n of 1600 A, service short-circuit breaking capacity I_cs up to 85 kA depending on voltage, and a rated impulse withstand voltage U_imp of 8 kV. The device operates at 690 V AC, with a 4P configuration and a front-terminal connection, suitable for high-demand power circuits.
Yes. The 1SDA063024R1 is a Tmax T7 moulded case circuit breaker designed for transformer and generator protection in high-current applications. Its front-terminal design, 4P configuration, and PR332/P-LSIRc release provide robust protection, fast tripping, and compatibility with typical Tmax T7 protection schemes in 690 V networks.
The device carries CE conformity, RoHS compliance, and REACH declarations. It also references CMRT for conflict minerals and TSCA declarations, aligning with global environmental and regulatory expectations for electrical protection devices.
The combination of a stored-energy release, front-terminal access, and high current rating reduces commissioning time, minimizes nuisance trips, and lowers maintenance costs over the lifecycle. By meeting IEC standards and RoHS/REACH compliance, it also simplifies audits and supplier qualification, contributing to lower total cost of ownership in multi-site operations.