ABB 1SDA064132R1 Moulded Case Circuit Breaker - UL/CSA TMA

Part Number: 1SDA064132R1
Manufacturer
ABB
Part number
1SDA064132R1

Quick Summary

ABB 1SDA064132R1 Moulded Case Circuit Breaker provides reliable transformer and distribution protection in industrial power systems. Engineers often juggle space constraints, front-terminal access, and UL/CSA compliance across demanding installations. Certified to UL/CSA standards with CE declarations and RoHS compliance, plus CMRT reporting, it supports regulatory adherence and sustainability goals. Its front-terminal, fixed two-pole design simplifies wiring in compact switchgear, enabling faster installation and easier maintenance. By combining robust protection with ABB Sace engineering, this device delivers consistent uptime, easier procurement standardization, and improved total cost of ownership across demanding industrial environments.

Product Information

Extended Description

1SDA064132R1 ABB: C.BREAKER TMAX T5N 400 UL/CSA FIXED TWO-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMA R 300 I3=1500...3000 A
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
SCIP
5351d647-10ea-4099-a9bf-1af8e3b27f2d Italy (IT)
Simplified SCIP
7bf73749-25f5-4d1b-be49-8eb0b2498389 Finland (FI) | 058a5555-12e8-4fa5-815a-68fbebe44a82 Estonia (EE) | 3a373309-5b1c-4716-9f50-d8c5d9353573 Belgium (BE) | 2aada375-af95-498c-ba06-ef28b3c35d4e Belgium (BE) | 5680a408-8dde-49df-995d-04077d10861d Hungary (HU) | 80cd186f-324f-4549-bbbf-41d9d82aedc4 Spain (ES) | a2786e6f-eec9-4848-96f4-2752ddd6f126 Croatia (HR) | aaf80689-8342-4f59-af1c-d0c1ffd8a78c Germany (DE) | 4b2903ab-a937-47e2-b2ac-97c14f480980 Germany (DE) | 1f7c14ad-42a5-4ccc-bb98-17d562a8287b France (FR) | 0dd6ee30-5abb-4c1d-accb-dff8270b5028 France (FR) | 563c715b-a618-4f81-b818-9e50a9522b21 Germany (DE) | f8042b07-07d1-4a6d-83bd-158199794ae8 Greece (GR) | f0a6cfca-8bd4-45f4-8058-a251ba3fa6d1 Germany (DE) | 01476c60-446a-448a-bffb-78876989ff03 Sweden (SE) | 2e92ea9f-b6b0-440e-a862-f4a234234955 Denmark (DK) | 17daf1ef-4b5a-45cb-af18-2f11aba29e99 Portugal (PT) | 5351e663-7695-4ea1-8863-3fb005dc3cbb Germany (DE) | 6ea74ced-26c5-4b01-9f15-2229e7e3c841 Czech Republic (CZ) | a31c0b5b-157a-43dc-8e00-59b8ae702900 Norway (NO) | b1f65800-7dd6-42b5-8f3d-729b0e7df046 Sweden (SE) | c9acca1b-bbf0-48f9-9a14-8ff64d535110 Netherlands (NL) | 16e87161-8e1d-4793-b7da-3f5b5ee083c9 Poland (PL) | 7722dea7-48f7-4978-938c-96b91965541f Bulgaria (BG) | 430972c1-4c4c-4b76-846d-c2da0171ba1d Poland (PL) | 8d1a376a-1578-476b-bb26-ec63f1580e3e Poland (PL) | 532067fe-12a3-481c-ab65-7b109f842421 Hungary (HU)
Environmental Information
Product Environmental Information Tmax T5 | Breakers - Packaging disposal information
Order Code US and Canada
T5N300TW-2
EAN
8015644669935
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
140 mm
Product Net Height
205 mm
Product Net Depth / Length
103.5 mm
Product Net Weight
3.25 kg
Package Level 1 EAN
8015644669935
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable For
T5
Suitable for Product Class
Moulded Case Circuit Breakers
Version
F
Mechanical Durability
20000 cycle | 120 cycles per hour
Number of Poles
2P
Rated Current (In)
300 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
600 V AC | 600 V DC
Rated Uninterrupted Current (Iu)
400 A
Release
TMA
Release Type
TM
Short-Circuit Performance Level
N
Standards
UL
Sub-type
T5
Terminal Connection Type
Fixed Circuit-Breakers | Front
Interrupting Rating acc. to UL489
(240 V AC) 65 kA | (480 V AC) 25 kA | (600 V AC) 18 kA | (500 V DC) 2 Poles in Series 25 kA | (600 V DC) 3 Poles in Series 16 kA
Declaration of Conformity - CE
EC Declaration of Conformity Tmax T5
Instructions and Manuals
Tmax. T Generation - Low voltage molded case circuit breakers up to 1200 A - UL 489 and CSA C22.2 Standard
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
IDEA Granular Category Code (IGCC)
4927 >> Molded case circuit breakers
UNSPSC
39121616
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature: Two-pole, 300 A rated current, 600 V operating voltage, front-terminal mounting. Business Impact: Enables reliable protection of feeders with straightforward wiring in tight spaces, reducing installation time while maintaining clear fault isolation. Application: Suitable for transformer and distribution feeders within compact switchgear. Feature: UL/CSA interrupting ratings up to 65 kA at 240 V, 25 kA at 480 V, and 18 kA at 600 V. Business Impact: Ensures rapid fault interruption across voltage classes, improving system safety and uptime. Application: Critical protection for high-energy industrial circuits and sensitive loads. Feature: Thermal-magnetic release (TMA) with TM type and 2P configuration. Business Impact: Delivers precise overcurrent protection with reliable tripping characteristics, reducing nuisance trips and equipment stress. Application: Widely applicable in motor feeders and transformer protection schemes. Feature: Front-terminal connection and fixed-mount design. Business Impact: Simplifies installation and future maintenance, lowers labor costs, and supports fast replacements. Application: Ideal for retrofit projects and new builds in space-constrained panels. Feature: Compliance and environmental declarations (CE, RoHS, REACH, CMRT). Business Impact: Mitigates regulatory risk and supports sustainability initiatives with traceable supply chain data. Application: Aligns with enterprise ESG programs and procurement standards.

Get a Quick Quote for a ABB 1SDA064132R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA064132R1? Enquire Now

FAQs

ABB 1SDA064132R1 uses fixed front terminals with a compact footprint (140 mm width, 205 mm height, 103.5 mm depth). Plan for front-access wiring in crowded panels and ensure the device is mounted in a manner that preserves access to the terminals for testing and maintenance. The two-pole Tmax T design supports straightforward integration with adjacent protection devices in standard switchgear.
Under UL489, the breaker provides 65 kA interrupting at 240 V AC, 25 kA at 480 V AC, and 18 kA at 600 V AC. For DC service, two-pole in series offers 25 kA at 500 V DC, while three-pole series achieves 16 kA at 600 V DC. These ratings support selective coordination in industrial feeders.
Yes. The 1SDA064132R1 is part of the Tmax T family and is designed for transformer and generator protection. With a 300 A rating and 600 V operation, it fits standard transformer feeder schemes and pairs well with other Tmax T devices in conventional switchgear to achieve coordinated protection and reliability.
The breaker carries UL/CSA listings, a CE Declaration of Conformity, and RoHS compliance. It also supports REACH declarations and CMRT reporting for the supply chain. These certifications help reduce regulatory risk, facilitate regional approvals, and support sustainability programs in manufacturing environments.
The device offers about 20,000 mechanical cycles at 120 cycles per hour, with a 300 A rated current and 400 A Iu. Regular inspection and front-terminal access facilitate quick checks and maintenance. Following ABB's manuals ensures continued UL/CSA compliance and reliable performance over the equipment’s lifecycle.