ABB 1SDA064157R1 Moulded Case Circuit Breaker - IEC Tmax T5
Part Number: 1SDA064157R1
Quick Summary
Moulded Case Circuit Breaker 1SDA064157R1 protects 3‑pole industrial power panels from overload and short‑circuit faults. Engineers often struggle with nuisance trips and limited front-access terminals that slow commissioning, increasing downtime on demanding machines. It supports CE conformity, IEC standards, and RoHS/REACH compliance, with additional CMRT and TSCA declarations for global deployments, helping teams meet supplier audits and regulatory readiness. Compatible with Tmax T accessories and fixed-front terminals, it delivers installation efficiency and lifecycle cost reductions for mission-critical protection, and its compatibility with Tmax T accessories also accelerates upgrades and simplifies serviceability across sites.
Product Information
Extended Description
1SDA064157R1 ABB: C.BREAKER TMAX T5N 630 FIXED THREE-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC Ekip M-LRIU R 400
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Product Environmental Information Tmax T5 | Breakers - Packaging disposal information
EAN
8015644670207
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
140 mm
Product Net Height
205 mm
Product Net Depth / Length
103.5 mm
Product Net Weight
5.1 kg
Package Level 1 Units
1 piece
Package Level 1 Width
228 mm
Package Level 1 Height
228 mm
Package Level 1 Depth / Length
286 mm
Package Level 1 Gross Weight
5.1 kg
Package Level 1 EAN
8015644670207
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable For
T5
Suitable for Product Class
Moulded Case Circuit Breakers
Version
F
Electrical Durability
7000 cycle | 60 cycles per hour
Mechanical Durability
20000 cycle | 120 cycles per hour
Number of Poles
3P
Power Loss
at Rated Operating Conditions per Pole 41 W
Rated Current (In)
400 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 70 kA | (230 V AC) 70 kA | (380 V AC) 36 kA | (400 V AC) 36 kA | (415 V AC) 36 kA | (440 V AC) 30 kA | (500 V AC) 25 kA | (690 V AC) 20 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 70 kA | (230 V AC) 70 kA | (380 V AC) 36 kA | (400 V AC) 36 kA | (415 V AC) 36 kA | (440 V AC) 30 kA | (500 V AC) 25 kA | (690 V AC) 20 kA
Rated Uninterrupted Current (Iu)
630 A
Release
Ekip M-LRIU
Release Type
EL
Short-Circuit Performance Level
N
Standards
IEC
Sub-type
T5
Terminal Connection Type
Fixed Circuit-Breakers | Front
Test Voltage Max (Utest)
3500 V
Data Sheet, Technical Information
Tmax. T Generation - Low voltage molded case circuit breakers up to 1200 A - UL 489 and CSA C22.2 Standard
Declaration of Conformity - CE
EC Declaration of Conformity Tmax T5
Instructions and Manuals
1SDC210033D0202
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39121100
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Paragraph 1: Feature: This ABB Tmax T5 three-pole molded case circuit breaker uses fixed front terminals, enabling straightforward wiring and compact panel layouts. Business Impact: The front-terminal design reduces field cabling time, simplifies clearance checks, and lowers installation costs during panel assembly. Application: It is well suited for motor starters and transformer protection in manufacturing environments where space is tight and reliability is non-negotiable. It also supports standard Tmax T accessories for selective coordination and future upgrades.Paragraph 2: Feature: Ekip M-LRIU release and EL operating mechanism deliver precision tripping and selective protection. Business Impact: The design improves fault discrimination, minimizing unintended outages and protecting downstream equipment. Application: Distribution panels serving conveyors, pumps, and process equipment where uptime is critical. The design also simplifies preventive maintenance and field service with clear terminal access and intuitive wiring paths.Paragraph 3: Feature: High breaking capacity and voltage ratings—Ics up to 70 kA at multiple voltages, Ui 1000 V, In 400 A, and Uimp 8 kV. Business Impact: This broad fault-current capability provides margins for future expansion and safer short-circuit interruption. Application: Transformers, feeders and motor circuits in medium- to high-power installations. It supports 690 V systems and broader distribution architectures.Paragraph 4: Feature: Mechanical and electrical durability—7000 electrical cycles (60 cycles/hour), 20000 mechanical cycles (120 cycles/hour), and a rated power loss of 41 W per pole. Business Impact: The device maintains performance under repetitive switching with predictable heat generation, lowering cooling costs and extending service life. Application: Suitable for heavy-duty drives and automation loops in continuous-process environments. Additionally, the low power loss per pole minimizes heat load in cabinets, improving enclosure thermal management and extending component life.Paragraph 5: Feature: Environment and compliance suite—RoHS declaration, REACH declaration, CMRT, TSCA, CE conformity, and a product environmental information (EPD) with packaging disposal guidance. Business Impact: Strengthens regulatory compliance across global sites and simplifies supplier qualification. Application: Global procurement for OEMs and service partners in power distribution and control.
Get a Quick Quote for a ABB 1SDA064157R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA064157R1?
Enquire Now
FAQs
The unit uses fixed-front terminals, designed for straightforward installation in standard switchgear and panel boards. It supports front-access wiring, making it easier to assemble into spaces constrained by equipment and allowing quick verification during commissioning. It is compatible with Tmax T accessories for selective coordination and future upgrades.
Rated current is 400 A, rated operational voltage 690 V AC, rated insulation voltage 1000 V, rated impulse withstand voltage 8 kV, and service short-circuit breaking capacity Ics up to 70 kA across listed voltages. It also provides 70 kA Icu at similar levels and a 3P configuration with fixed front terminals.
Yes. The data indicates RoHS Status and RoHS Declaration, REACH Declaration, CMRT, TSCA declarations, and CE Declaration of Conformity for Tmax T5. This coverage supports regulatory compliance across regions, reduces supplier risk, and enables smoother cross-border installation and audits.
Ideal for motor protection, transformer feeders, and distribution panels in manufacturing and process industries. Its 3P fixed-front design and Tmax T release support fast protection against overloads and short circuits, with reliable discrimination to limit outages to the affected circuit. The device also facilitates selective coordination for scalable protection schemes.
Durability values show 7000 electrical cycles and 20000 mechanical cycles with 41 W power loss per pole, contributing to predictable maintenance planning and lower cooling costs. The device's RoHS/REACH/CMRT compliance and packaging data aid spare parts planning and cross-site procurement, delivering lower total cost of ownership and improved uptime across facilities.