ABB 1SDA064783R1 Moulded Case Circuit Breaker - UL
Part Number: 1SDA064783R1
Quick Summary
ABB 1SDA064783R1 Moulded Case Circuit Breaker protects industrial power systems by interrupting fault currents in panelboards. Engineers often face space constraints and lengthy commissioning times when upgrading protection schemes, making compact, easy-to-wire MCCBs a priority. This Tmax T7 device carries UL recognition, CE conformity, RoHS compliance, TSCA declaration, and CMRT data, helping you meet global regulatory requirements. With a four-pole, front-terminal design and a 1000 A rating, plus a PR232/P-LSI stored-energy release, it delivers fast, reliable protection for demanding loads. In practice, choosing Tmax T MCCBs reduces panel footprint, simplifies maintenance, and improves fault-ride-through coordination for critical processes.
Product Information
Extended Description
1SDA064783R1 ABB: C.BREAKER TMAX T7S 1000 UL/CSA FIXED FOUR-POLE WITH FRONT TERMINALS AND STORED ENERGY OPERATING MECHANISM AND SOLID-STATE RELEASE IN AC PR232/P-LSI R 1000
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Product Environmental Information Tmax T7 | Breakers - Packaging disposal information
Order Code US and Canada
T7MSBP4DC000000XX
EAN
8015644676780
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
280 mm
Product Net Height
268 mm
Product Net Depth / Length
178 mm
Product Net Weight
14 kg
Package Level 1 EAN
8015644676780
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable For
T7M
Suitable for Product Class
Moulded Case Circuit Breakers
Version
F
Mechanical Durability
10000 cycle | 60 cycles per hour
Number of Poles
4P
Power Loss
at Rated Operating Conditions per Pole 30 W
Rated Current (In)
1000 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
600 V AC
Rated Uninterrupted Current (Iu)
1000 A
Release
PR232/P-LSI
Release Type
EL
Short-Circuit Performance Level
S
Standards
UL
Sub-type
T7
Terminal Connection Type
Fixed Circuit-Breakers | Front
Test Voltage Max (Utest)
3500 V
Interrupting Rating acc. to UL489
(240 V AC) 65 kA | (480 V AC) 50 kA | (600 V AC) 25 kA
Data Sheet, Technical Information
9AKK105713A5947
Declaration of Conformity - CE
EC Declaration of Conformity Tmax T7
GL Certificate
1SDL000163R0055
Instructions and Manuals
Tmax. T Generation - Low voltage molded case circuit breakers up to 1200 A - UL 489 and CSA C22.2 Standard
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature: Four-pole fixed-front terminal design enables straightforward wiring and faster panel assembly, reducing commissioning time and potential wiring errors. Business Impact: Shorter project cycles and improved installation safety, especially in tight electrical rooms. Application: MCCB upgrades in factory automation panels and switchgear. Feature: Rated current of 1000 A supports high-load protection without oversizing devices. Business Impact: Better coordination with large motors and transformers, lowering total cost of ownership through fewer components. Application: Medium- to high-power distribution in manufacturing lines. Feature: Rated operational voltage 600 V AC and rated insulation voltage 1000 V improve compatibility with common plant electrical systems. Business Impact: Broad compatibility reduces re-engineering and stock variety. Application: Machine rooms and panelboards across process industries. Feature: PR232/P-LSI stored-energy release and EL release type enable fast, reliable tripping with compact actuation. Business Impact: Enhanced protection speed and reliability while maintaining safe operation during maintenance windows. Application: Critical load protection in data centers and processing lines. Feature: High short-circuit interrupting ratings (UL489) up to 65 kA at 240 V, 50 kA at 480 V, and 25 kA at 600 V. Business Impact: Superior fault clearance, reduced risk of equipment damage, and improved safety margins. Application: Protection for feeders to transformers and large motor drives. Feature: RoHS, REACH, CMRT, and TSCA declarations ensure regulatory compliance and sustainable procurement. Business Impact: Streamlined supplier qualification and reduced compliance audits. Application: Global procurement for multinational facilities. Feature: Mechanical durability rated at 10,000 cycles supports long service life in frequent switching environments. Business Impact: Lower maintenance costs and fewer replacements in high-usage installations. Application: Panel boards with frequent load changes and routine testing.
Get a Quick Quote for a ABB 1SDA064783R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA064783R1?
Enquire Now
FAQs
For fixed-front-terminal MCCBs like the 1SDA064783R1, ensure panel cutouts match the device footprint, provide adequate clearance for front-terminal wiring, and torque connections to the manufacturer’s specification. Use proper labeling and alignment to support safe operation and efficient maintenance access.
According to UL489 ratings, the device provides 65 kA interrupting capability at 240 V, 50 kA at 480 V, and 25 kA at 600 V, enabling robust fault clearance for a range of distribution configurations and transformer feeds.
Yes. With 4P construction, 1000 A rating, 8 kV impulse withstand, and a PR232/P-LSI release, it supports reliable transformer protection in low- to medium-voltage applications while enabling precise coordination with upstream protections.
The unit carries UL recognition, CE Declaration of Conformity, RoHS and REACH compliance, CMRT reporting, and TSCA declarations, which help meet global procurement and regulatory requirements across multiple regions.
Stored-energy releases reduce recharge time and improve tripping reliability. Regular inspection of mechanical durability (up to 10,000 cycles) and release mechanism alignment is recommended to sustain fast response, minimize downtime, and extend service life in high-switching environments.