ABB 1SDA064878R1 Moulded Case Circuit Breaker - UL
Part Number: 1SDA064878R1
Quick Summary
ABB 1SDA064878R1 is a moulded case circuit breaker designed for high-current protection in industrial switchgear and panel boards. Engineers often struggle with reliable fault clearing and safe front-terminal access in compact spaces. Certified to UL489 with CE conformity, and RoHS compliant per EU directives, supporting sustainable procurement. The unit supports T7 system configurations and is designed for fast installation with front terminals, enabling quick maintenance and reduced downtime. With CMRT and TSCA considerations, it aligns with global compliance programs while delivering predictable performance in demanding environments. Its 1200 A rating, four-pole construction, and PR332/P LSI release provide a robust solution for critical power distribution in manufacturing, data centers, and process facilities, improving safety margins and lifecycle cost efficiency for buyers and operators.
Product Information
Extended Description
1SDA064878R1 ABB: C.BREAKER TMAX T7S 1200 UL/CSA FIXED FOUR-POLE WITH FRONT TERMINALS AND LEVER OPERATING MECHANISM AND SOLID-STATE RELEASE IN AC PR332/P-LSI R 1200
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Product Environmental Information Tmax T7 | Breakers - Packaging disposal information
Order Code US and Canada
T7S1200RW-4
EAN
8015644677770
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
280 mm
Product Net Height
268 mm
Product Net Depth / Length
154 mm
Product Net Weight
12.5 kg
Package Level 1 EAN
8015644677770
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable For
T7
Suitable for Product Class
Moulded Case Circuit Breakers
Version
F
Mechanical Durability
10000 cycle | 60 cycles per hour
Number of Poles
4P
Power Loss
at Rated Operating Conditions per Pole 47 W
Rated Current (In)
1200 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
630 V AC
Rated Uninterrupted Current (Iu)
1200 A
Release
PR332/P LSI
Release Type
EL
Short-Circuit Performance Level
S
Standards
UL
Sub-type
T7
Terminal Connection Type
Fixed Circuit-Breakers | Front
Test Voltage Max (Utest)
3500 V
Interrupting Rating acc. to UL489
(240 V AC) 65 kA | (480 V AC) 50 kA | (600 V AC) 25 kA
Data Sheet, Technical Information
9AKK105713A5947
Declaration of Conformity - CE
EC Declaration of Conformity Tmax T7
Instructions and Manuals
Tmax. T Generation - Low voltage molded case circuit breakers up to 1200 A - UL 489 and CSA C22.2 Standard
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature → Business Impact → Application: The ABB Tmax T7 family footprint delivers reliable fault clearing with a 1200 A continuous rating, enabling feeders to withstand high fault currents without unnecessary tripping, which translates to reduced unplanned downtime in production lines and safer shutdown sequences in emergencies. Application: use in main distribution panels guarding motors and process lines where 630 V AC operational voltage and 1000 V insulation support heavy-duty, multi-branch circuits. Feature → Business Impact → Application: Four-pole configuration (4P) with front terminals simplifies wiring and improves installation speed, reducing commissioning time and panel depth requirements in compact switchgear. Application: ideal for new builds and panel modernizations in data centers and automotive manufacturing. Feature → Business Impact → Application: PR332/P LSI release enables selective tripping, providing coordination with upstream protection and decreasing collateral outages. Application: critical processes requiring fast, staged protection in Tmax T installations. Feature → Business Impact → Application: 8 kV impulse withstand and UL/CE compliance meet safety and regulatory demands, supporting regulator-approved assemblies and long-term reliability across factory floors. Application: suitable for OEMs and service providers delivering compliant power distribution solutions. Feature → Business Impact → Application: RoHS and CMRT declarations simplify procurement and supply-chain governance, reducing documentation overhead and ensuring responsible sourcing. Application: engineering teams can confidently specify this unit in green procurement programs and global supply chains.
Get a Quick Quote for a ABB 1SDA064878R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA064878R1?
Enquire Now
FAQs
For fixed front-terminal configurations, ensure adequate clearance for wiring and lever operation. Use the 4P design to match your panel layout and align with UL 489 wiring guidelines. Verify that conductor sizes, torque specs, and terminal plate clearances meet the manufacturer’s installation instructions to achieve safe, durable connections.
This unit is rated for 1200 A and 630 V AC nominal operating voltage with 1000 V rated insulation voltage. It provides a short-circuit performance level of S and an interrupting rating suitable for the specified voltages (up to 65 kA at 240 V). With 8 kV impulse withstand, it offers strong surge resilience essential for industrial power distribution.
Yes. Its four-pole fixed design, front terminals for quick wiring, and high current rating make it ideal for data centers, manufacturing lines, and process plants. The PR332/P LSI release supports selective tripping, minimizing downtime during faults, while UL/CE compliance and RoHS/CMRT readiness align with industry procurement standards.
Key certifications include UL489, CE conformity via DoC, RoHS compliance per EU directives, and CMRT for conflict minerals reporting. These ensure regulatory acceptance across North America and Europe, support sustainable sourcing, and simplify supplier qualification during audits and tender processes.
The unit improves reliability with high interrupting capacity and selective protection, reducing unplanned outages and maintenance time. Front-terminal wiring accelerates installation, and RoHS/CMRT compliance eases procurement and lifecycle governance. While ROI depends on specific project scale, typical gains include faster commissioning, lower downtime, and streamlined compliance documentation.