ABB 1SDA065773R1 Moulded Case Circuit Breaker - PR332/P LSIG

Part Number: 1SDA065773R1
Manufacturer
ABB
Part number
1SDA065773R1

Quick Summary

ABB 1SDA065773R1 Moulded Case Circuit Breaker protects industrial power systems by interrupting fault currents. Users often face nuisance trips, extended downtime, and challenging front-terminal wiring during maintenance. This unit ships with CE conformity, RoHS compliance, and TSCA declarations to support regulatory compliance and sustainability goals. Built on the Tmax T platform, it delivers robust protection for high-demand networks while offering easy front-access installation and reliable replacement in legacy systems. The compact 3P design and 2000 A rated current scale well from transformer feeders to large distribution panels, helping engineering teams reduce downtime and plan lifecycle maintenance with confidence. Secondary keywords: electronic protection, industrial electrical safety, modular MCCB integration.

Product Information

Extended Description

1SDA065773R1 ABB: C.BREAKER TMAX T8V 2000 FIXED THREE-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC PR332/P-LSIG R 2000
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Product Environmental Information Tmax T8 | Breakers - Packaging disposal information
Order Code US and Canada
T8VFD3GS000000XX
EAN
8015644686840
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
427 mm
Product Net Height
382 mm
Product Net Depth / Length
282 mm
Product Net Weight
9.7 kg
Package Level 1 Units
1 piece
Package Level 1 Width
525 mm
Package Level 1 Height
475 mm
Package Level 1 Depth / Length
695 mm
Package Level 1 Gross Weight
11.2 kg
Package Level 1 EAN
8015644686840
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
Electrical Durability
4500 cycle | 20 cycles per hour
Mechanical Durability
15000 cycle | 60 cycles per hour
Number of Poles
3P
Power Loss
at Rated Operating Conditions per Pole 46 W
Rated Current (In)
2000 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA | (230 V AC) 100 kA | (380 V AC) 100 kA | (400 V AC) 100 kA | (415 V AC) 100 kA | (440 V AC) 100 kA | (500 V AC) 75 kA | (690 V AC) 60 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 40 A
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 1.3 kA | (230 V AC) 1.3 kA | (380 V AC) 130 kA | (400 V AC) 130 kA | (415 V AC) 130 kA | (440 V AC) 130 kA | (500 V AC) 100 kA | (690 V AC) 80 kA
Rated Uninterrupted Current (Iu)
2000 A
Release
PR332/P LSIG
Release Type
EL
Short-Circuit Performance Level
V
Standards
IEC
Sub-type
T8
Terminal Connection Type
Fixed Circuit-Breakers | Front
Data Sheet, Technical Information
Tmax. T Generation - Low voltage molded case circuit breakers up to 1200 A - UL 489 and CSA C22.2 Standard
Declaration of Conformity - CE
EC Declaration of Conformity Tmax T8
Wiring Diagram
Wiring diagram T8
Instructions and Manuals
1SDC210033D0202
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
IDEA Granular Category Code (IGCC)
4932 >> 3 Pole Non-Interchangeable Trip Electronic Circuit Breakers
Object Classification Code
Q
UNSPSC
39121616
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature: 3P Tmax T8 molded case design with front terminals. Benefit: Simplifies wiring during installation and maintenance, enabling faster panel commissioning and safer front-access work. Application: Large distribution panels and utility feeders where space and accessibility are at a premium. Feature: Release PR332/P LSIG and 2000 A rated current. Benefit: Provides reliable overcurrent protection for high-load circuits, reducing unplanned outages and equipment damage. Application: Heavy-load motor feeders and transformer protection in manufacturing plants. Feature: Rated operational voltage 690 V AC and rated insulation voltage 1000 V. Benefit: Supports integration into European and global power networks with robust insulation margins. Application: Industrial power distribution and transformer protection near high-energy equipment. Feature: Short-circuit capacity Ics up to 100 kA (varies by voltage). Benefit: Strong fault-clearing capability for critical lines, improving system resilience. Application: High-energy distribution networks and large machinery feed circuits. Feature: Electrical durability of 4500 cycles and mechanical durability of 15000 cycles. Benefit: Longer service life and predictable maintenance windows, reducing lifecycle costs. Application: Frequent switching environments like press lines and batch processes. Feature: Front-terminal connection and compact footprint. Benefit: Easier retrofits, faster wiring checks, and safer maintenance. Application: Retrofit projects and new installs in space-constrained switchgear. Feature: Compliance with RoHS, CMRT, and TSCA declarations. Benefit: Regulatory compliance and supply-chain transparency across regions. Application: Global deployments requiring environmental and conflict-mineral reporting.

Get a Quick Quote for a ABB 1SDA065773R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA065773R1? Enquire Now

FAQs

To install the ABB 1SDA065773R1 with front terminals, follow the wiring diagram provided (Wiring Diagram T8) and ensure the panel supports front-access connections. Use appropriate torque on terminal screws and verify alignment within the 3P enclosure. This design simplifies wiring checks during commissioning and routine maintenance, reducing installation time and risk of connection faults.
Key specs include a rated current of 2000 A, rated operational voltage of 690 V AC, rated insulation voltage of 1000 V, and rated impulse withstand voltage of 8 kV. The device provides up to 100 kA short-circuit current withstand (Ics) depending on voltage, and electrical durability of 4500 cycles with 15000 mechanical cycles for reliability in demanding environments.
Yes. The ABB 1SDA065773R1 carries RoHS declarations in line with EU and global directives, CMRT for conflict minerals reporting, and TSCA declarations. These certifications support regulatory compliance in manufacturing and supply chains, helping you meet sustainability and procurement requirements across regions.
Tmax T8 MCCBs are ideal for transformer feeders, large motor protection, and main distribution panels in industrial facilities. With 690 V AC operation, solid-state release, and front-terminal configuration, they are well-suited for transformer/generator protection, high-load distribution, and retrofit projects seeking reliable protection with easy maintenance.
The device offers durable mechanical and electrical performance, with 15000 mechanical and 4500 electrical cycles, translating to longer service intervals and predictable maintenance. Power loss of 46 W per pole reduces heat load during operation, contributing to energy efficiency and reduced cooling costs. These factors collectively support lower total cost of ownership over the product lifecycle.